Verifying the f low on DN 40
to DN 250 AB-QM valves

AB-QM 3TP Flow Checker

Flow verification in an installation

To verify that an installation functions according to the design specifications checking only the most critical valve in the installation is needed (see figure 1).
The AB-QM maintains a constant differential pressure over the valve and any excess pressure will automatically be throt tled. If there is not enough differential pressure the valve cannot reach the set flow.
The valve that is furthest away from the pump or the valve in the circuit with the highest resistance has the lowest available differential pressure, so if this critical valve has enough pressure it means the other valves will also function properly.
Important :
To get a useful measurement the installation should run on full load, so all actuators in the installation should be opened fully. This ensures that you are measuring under the most unfavorable circumstances. The AB-QM’s will have more differential pressure available when the installation is working on partial load.Danfoss AB-QM 3TP Flow Checker - Fig 1

Method of verification

Measure the differential pressure across the control valve.
The measuring nipples are placed in such a way that p1−p2 is measured (see figure 2).
Therefore the measured differential pressure can be used to calculate the flow directly. It ’s necessary to use the table that was derived fromstatistical measurements Since the measurements across the measuring points are influenced by the dynamic pressure, turbulences, flow pat terns, internal tolerances, set ting accuracy and accuracy of the measuring equipment we believe that the total accuracy of the measurement is lower than performance of the valve.
Therefore we recommend not to adjust the set ting when the results are within 10 % of the expected flow.

Calculat ing the flow
Danfoss AB-QM 3TP Flow Checker - SymbolPcv=p1-p2
Danfoss AB-QM 3TP Flow Checker - Symbol 1
For kv Cv values see tables in figure 4 and 7Danfoss AB-QM 3TP Flow Checker - Fig 2

Presetting DN 40 DN 50 / DN 50HF DN 65 / DN 65HF DN 80 / DN 80HF DN 100 / DN 100HF
s % kvCv (m3/ h)
20.0 % 3.40 4.60 4.20 15.50 19.50
22.5 % 4.08 5.55 5.48 17.19 21.94
25.0 % 4.80 6.50 6.75 18.88 24.38
27.5 % 5.43 7.45 8.03 20.56 26.81
30.0 % 6.10 8.40 9.30 22.25 29.25
32.5 % 6.78 9.35 10.58 23.94 31.69
35.0 % 7.50 10.30 11.85 25.63 34.13
37.5 % 8.13 11.25 13.13 27.31 36.56
40.0 % 8.80 12.20 14.40 29.00 39.00
42.5 % 9.48 13.15 15.68 30.69 41.44
45.0 % 10.20 14.10 16.95 32.38 43.88
47.5 % 10.83 15.05 18.23 34.06 46.31
50.0 % 11.50 16.00 19.50 35.75 48.75
52.5 % 12.18 16.95 20.78 37.44 51.19
55.0 % 12.90 17.90 22.05 39.13 53.63
57.5 % 13.53 18.85 23.33 40.81 56.06
60.0 % 14.20 19.80 24.60 42.50 58.50
62.5 % 14.88 20.75 25.88 44.19 60.94
65.0 % 15.55 21.70 27.15 45.88 63.38
67.5 % 16.26 22.65 28.43 47.56 65.81
70.0 % 16.90 23.60 29.70 49.25 68.25
72.5 % 17.58 24.55 30.98 50.94 71.81
75.0 % 18.25 25.50 32.25 52.63 75.38
77.5 % 18.93 26.45 33.53 54.31 78.94
80.0 % 19.60 27.40 34.80 56.00 82.50
82.5 % 20.28 28.35 36.08 57.69 86.06
85.0 % 20.95 29.30 37.35 59.38 89.63
87.5 % 21.63 30.25 38.63 61.06 93.19
90.0 % 22.30 31.20 39.90 62.75 96.75
92.5 % 22.98 32.15 41.18 64.44 100.31
95.0 % 23.65 33.10 42.45 66.13 103.88
97.5 % 24.33 34.05 43.73 67.81 107.44
100.0 % 25.00 35.00 45.00 69.50 111.00

Fig. 4 The flow is according to setting if the calculated flow is in the range of ±10 % of the set flow.

Danfoss AB-QM 3TP Flow Checker - Fig 5

Presetting DN 125 / DN 125HF DN 150 / DN 150HF DN 200 / DN 200HF DN 250 / DN 250HF
s % kvCv (m3/ h)
20.0 % 40 53 57 86
22.5 % 45 60 66 99
25.0 % 49 67 75 112
27.5 % 53 74 85 125
30.0 % 57 81 94 138
32.5 % 61 88 104 150
35.0 % 65 95 113 163
37.5 % 69 101 122 176
40.0 % 73 108 132 189
42.5 % 77 115 141 202
45.0 % 82 122 151 215
47.5 % 86 129 160 227
50.0 % 90 136 170 240
52.5 % 94 143 179 253
55.0 % 98 150 188 266
57.5 % 102 157 198 279
60.0 % 106 163 207 292
62.5 % 110 170 217 304
65.0 % 114 177 226 317
67.5 % 119 184 235 330
70.0 % 123 191 245 343
72.5 % 127 198 254 356
75.0 % 131 205 264 369
77.5 % 135 212 273 381
80.0 % 139 219 283 394
82.5 % 143 225 292 407
85.0 % 147 232 301 420
87.5 % 152 239 311 433
90.0 % 156 246 320 446
92.5 % 160 253 330 458
95.0 % 164 260 339 471
97.5 % 168 267 348 484
100.0 % 172 274 358 497
102.5% 176 281 367 510
105.0% 180 287 377 523
107.5% 184 294 386 535
110.0% 189 301 396 548

Fig. 7 The flow is according to setting if the calculated flow is in the range of ±10% of the set flow.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.