Danfoss 80G8650 Gateway Unit
Specifications
- Model: Gateway Unit Type X-Gate
- Dimensions:
- Height: 75 mm (2.95 inches)
- Width: 25.4 mm (1.0 inches)
- Depth: 110 mm (4.33 inches)
- Ports:
- 1 USB 2.0 OTG (Type C, 500 mA max.)
- 2 Ethernet Ports (10/100 BaseT)
- RS485/CAN ports
- Power Supply: L2 (-) 24 V, L1 (+)
- CPU: i.MX6UL ARM Cortex A7 Single Core 528 MHz
- Operating System: Linux Yocto
- Memory: 4GB Flash, 512MB RAM
- Real-Time Clock (RTC Back-up): Yes (SuperCAP)
- Weight: 0.140 Kg
Product Usage Instructions
Installation
Ensure the unit is grounded to earth using terminal 3 on the power supply terminal block.
Power Supply
Verify that the power supply can provide sufficient power for the equipment’s operation.
Connection Setup
Connect ETH1/WAN via DHCP and ETH2/LAN with the IP Address 192.168.2.101, Subnet mask 255.255.255.0. Access settings at https://192.168.2.101/ with Username: admin and Password: PASS.
CAN Bus Termination
To enable CAN bus termination, connect pins 1-2 externally. The RS485 A+ has an internal pull-up resistor, and the RS485 B- has an internal pull-down resistor. RS485 +5V is optional for external bias resistors.
Optional Plugin Modules
The unit supports multiple optional plugin modules, allowing for various configurations.
FAQ
Q: What are the recommended IT security practices for the X-Gate series?
A: The X-Gate device should be installed behind a router and firewall, following general IT security recommendations and best practices to ensure secure operation.
Q: How do I configure the network settings for the X-Gate?
A: Connect ETH1/WAN via DHCP and ETH2/LAN with specific IP settings as mentioned in the manual. Access further settings using the provided URL, Username, and Password.
DIMENSION
INSTALLATION
The X-Gate is suitable for mounting on a DIN rail.
REAR VIEW
1 | USB 2.0 OTG (500 mA
max., Type C)(1) |
4 | RS485/CAN ports |
2 | Ethernet Port 2 (10/100 BaseT | 5 | Power supply |
3 | Ethernet Port 1 (10/100 BaseT) | 6 | Expansion slot for plug-in modules |
for maintenance only
FACTORY SETTINGS
- ETH1 / WAN : DHCP
- ETH2 / LAN : IP Address 192.168.2.101
- Subnet mask : 255.255.255.0
- Settings : https://192.168.2.101/
- Username : admin
- Password : PASS
Don’t open the panel rear cover when the power supply is applied.
General IT security recommendations
The X-Gate series device is an embedded controller designed to be installed behind an appropriate router and firewall. Whilst the X-Gate offers many IT industry security technologies, Danfoss strongly recommends the deployment using IT security best practices and protocols.
POWER SUPPLY
Power Connector, Female – R/C Terminal Blocks (XCFR2), manufactured by Weidmuller Inc., Cat. No. BLZ 5.08, torque 4.5 lb-in.
- 3 conductor 1,5 mmq wire size minimum, minimum temperature conductor rating 105 °C.
- Do not open the cabinet while the system is powered up.
- WARNING: Do not separate when energized.
- The unit must always be grounded to earth. Earth connection will have to be done using terminal 3 on the power supply terminal block.
- Ensure that the power supply has enough power capacity for the operation of the equipment.
CONNECTIONS
To enable CAN bus termination (R120Ω) pins 1-2 must be connected externally. The RS485 A+ comes with an internal pull-up/bias resistor of 680 Ω enabled by software.
OPTIONAL PLUGIN MODULE
The panels have several optional plugin module, multiple modules configurations are possible.
TECHNICAL DATA
Features | Description |
Model | X-Gate |
CPU | i.MX6UL ARM Cortex A7 Single Core – 528 MHz |
Operating System | Linux Yocto |
Flash | 4GB |
RAM | 512MB |
Real Time Clock (RTC Back-up) | Yes (SuperCAP) |
LED | 1 – RGB |
Ethernet port | 2 – 10/100 BaseT |
USB port | 1 – USB 2.0 OTG (500 mA max., Type C) |
RS485 port | 1 (isolated, Modbus Master/Slave configuration) |
CAN/CAN-FD port | 1 (isolated) |
Expansion port | Yes |
Power supply | 24 V AC/DC (not isolated) +/-15% |
Current Consumption | 1.06A max. at 24 V AC, 1.56 A max. at 24 V DC |
Input Protection | Electronic Fuse |
Operating Temp | -20 – +60 °C |
Storage Temp | -30 – +70 °C |
Operating / Storage Humidity | 5 – 90% RH, non-condensing |
Protection Class | IP20 |
Weight | 0.140 Kg |
PRODUCT IDENTIFICATION
INSTALLATION PROCEDURE
The products have been designed in compliance with:
- EN 61000-6-3
- EN 61000-6-2
- FCC Part 15 Subpart B Class A
- ICES-003 issue7 Class B
This device cannot be disposed of as a domestic waste but according to WEEE European Directive 2012/19/EU
User Manual available on su: www.danfoss.com
Reproduction of the contents of this copyrighted document, in whole or part, without written permission of Danfoss, is prohibited.
DISCLAIMER: Professional Use Only
- This product is not subject to the UK PSTI regulation, as it is for supply to and use only by professionals with the necessary expertise and qualifications. Any misuse or improper handling may result in unintended consequences. By purchasing or using this product, you acknowledge and accept the professional-use-only nature of its application. Danfoss does not assume any liability for damages, injuries, or adverse consequences (“damage”) resulting from the incorrect or improper use of the product and you agree to indemnify Danfoss for any such damage resulting from your incorrect or improper use of the product.
DanfossA/S - Climate Solutions • danfoss.com • +45 7488 2222
- Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals,
catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, on line or via download, shall be considered informative, and is only binding if and to the
extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. - Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or . COMfunction of the product.
- All trademarks in this material are property of Danfoss A/5 or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/5. All rights reserved.
Documents / Resources
![]() |
Danfoss 80G8650 Gateway Unit [pdf] Installation Guide 80G8650, 80G8651, 80G8607, 80G8652, 80G8653, 80G8650 Gateway Unit, 80G8650, Gateway Unit, Unit |