Product Information

  • The EKE 80 Ejector Controller receives input signals from Danfoss controllers AK-PC 782A/AK-PC 782B or a PLC.
  • It can control multiple HP/LP ejectors and up to 2 modulating control valves to facilitate the ‘lift’ of the MT suction pressure, thereby decreasing energy consumption.
  • The EKE 80 drive controller is suitable for both new and retrofit systems.
  • Identify the connectors on the EKE 80 Ejector Controller according to the manual.
  • Connect the necessary input signals from the Danfoss controllers or PLC to the designated connectors on the EKE 80.
  • Ensure proper power supply connection to the controller.
  • Follow the specific wiring instructions for connecting HP/LP ejectors and modulating control valves.
  • Test the system to ensure proper functionality.
  • Refer to the manual for detailed information on connecting various components to the EKE 80 Ejector Controller.
  • Use the specified connectors and follow the wiring guidelines provided.
  • Power on the EKE 80 Ejector Controller.
  • Set the desired parameters using the interface connected to the controller.
  • Monitor the system performance and make adjustments as needed for optimal efficiency.

Introduction

  • The EKE 80 Ejector Controller receive inputs signals from the Danfoss controllers AK-PC 782A/AK-PC 782B or a PLC.
  • It can control multiple HP/LP ejectors and up to 2 modulating control valves to facilitate the ‘lift’ of the MT suction pressure and thereby decrease energy consumption.
  • The EKE 80 drive controller is suitable for both new and retrofit systems.

Identification

Danfoss-80G8280-Ejector-Controller-FIG-2

Application example

Danfoss-80G8280-Ejector-Controller-FIG-3

General features and warnings

Plastic housing features

  • DIN rail mounting complying with EN 60715
  • Self-extinguishing V0 according to IEC 60695-11-10 and glowing/hot wire test at 960 °C according to IEC 60695-2-12
  • Ball test: 125 °C according to IEC 60730-1. Leakage current: ≥ 250 V according to IEC 60112

Other features

  • Operating conditions CE: -20T60 / UL: 0T50, 90% RH non-condensing
  • Storage conditions: -30T80, 90% RH non-condensing
  • To be integrated into Class I and/or II appliances
  • Index of protection: IP40 only on the front cover
  • Period of electric stress across insulating parts: long
  • Suitable for use in environments with a degree of pollution 2
  • Category of resistance to heat and fire: D
  • Immunity against voltage surges: category II, category III for versions without display
  • Software class and structure: class A

Compliance
CE mark

  • This product is designed to comply with the following EU standards:
  • Low voltage directive LVD 2014/35/EU:
    • EN60730-1: 2011 (Automatic electrical control for household and similar use. General requirements)
    • EN60730-2-9: 2010 (Particular Requirements for Temperature Sensing Controls)
  • Electromagnetic compatibility EMC directive 2014/30/EU:
  • EN 61000-6-3: 2007 +A1: 2011 (Emission standard for residential, commercial and light-industrial environments)
  • EN 61000-6-2: 2005 (Immunity for industrial environments)
  • RoHS directive 2011/65/EU and 2015/863/EU:
    • EN50581: 2012
  • China RoHS
    UL approval:
  • UL file E31024

General warnings

  • Every use that is not described in this manual is considered incorrect and is not authorised by the manufacturer
  • Verify that the installation and operating conditions of the device respect the ones specified in the manual, especially concerning the supply voltage and environmental conditions
  • This device contains live electrical components therefor,e all the service and maintenance operations must be performed by qualified personnel
  • The device can’t be used as a safety device
  • Liability for injury or damage caused by the incorrect use of the device lies solely with the user

Installation warnings

  • Mounting position recommended: vertical
  • The installation must be executed according the local standards and legislation of the country
  • Always operate on the electrical connections with the device disconnected from the main power supply
  • Before carrying out any maintenance operations on the device, disconnect all the electrical connections
  • For safety reasons, the appliance must be fitted inside an electrical panel with no live parts accessible
  • Don’t expose the device to continuous water sprays or to relative humidity greater than 90%.
  • Avoid exposure to corrosive or pollutant gases, natural elements, environments where explosives or mixes of fiammable gases are present, dust, strong vibrations or shock, large and rapid fluctuations in ambient temperature that in combination with high humidity,y can condensate, strong magnetic and/or radio interference (e.g., transmitting antennae)
  • When connecting loads, beware of the maximum current for each relay and connector
  • Use cable ends suitable for the corresponding connectors. After tightening the screws of the connectors, slightly tug the cables to check their tightness
  • Use appropriate data communication cables. Refer to the Installation Guide “MCX hardware network specification” for the kind of cable to be used and setup recommendations
  • Reduce the path of the probe and digital input cables as much as possible, and avoid spiral paths enclosing power devices. Separate from inductive loads and power cables to avoid possible electromagnetic noises
  • Avoid touching or nearly touching the electronic components fitted on the board to avoid electrostatic discharges
  • The product is not suitable to be exposed directly to the Internet

DISCLAIMER: Professional Use Only

  • This product is not subject to the UK PSTI regulation, as it is for supply to and use only by professionals with the necessary expertise and qualifications.
  • Any misuse or improper handling may result in unintended consequences. By purchasing or using this product, you acknowledge and accept the professional-use-only nature of its application.
  • Danfoss does not assume any liability for damages, injuries, or adverse consequences (“damage”) resulting from the incorrect or improper use of the product and you agree to indemnify Danfoss for any such damage resulting from your incorrect or improper use of the product.

Technical specications

Power supply

  • 21 – 265 V AC, 50/60 Hz. Maximum power consumption: 15 W. Insulation between power supply and the extra-low voltage: reinforced
  • 40 – 230 V DC

Communication interface

Interface Use Connector label Technical data
CANbus Fieldbus for connection to user interfaces, MCX controllers, service tools etc. CAN CAN-RJ Physical layer according to ISO 11898-2 High Speed CAN bus Frame format according to CAN 2.0B specification

Transceiver not isolated (power supply has reinforced isolation)

USB device Prepared for future use USB-DEV Plug: Type Mini B
USB host For connection to the Flash drive for application software update, datalogging and service USB-H Plug: Type A
RS485-1

RS485-2 (MCX20B2 only)

Communication bus to BMS (e.g. Modbus slave), service tools, smart devices (e.g. Modbus master), RS485-1 can be polarized as master from the application RS485-1 RS485-2 Physical layer according to EIA 485 Ref3

Provide 500 V peak transient galvanic isolation

Ethernet For web server functionality, integration (e.g. Modbus TCP)

NOTICE! Do not route cable outside of buildings. Connect only to IT equipment compliant with EN 60950 or EN 62368 (Information technology equipment. Safety. General requirements)

ETHERNET Interface type: 10 BASE-T and 100 BASE-TX, IEEE 802.3.

MDI-X (Automatic medium- dependent interface crossover)

Wire lengths

Interface Max wire length (m) Max. baudrate (bps) Min. wire size
Ethernet 100 10/100 M  
  1000 50 K AWG18
  500 125 K AWG22
CANbus 250 250 K AWG24
  80 500 K AWG26
  30 1 M AWG26
RS485 1000 125 K AWG22
Signal wiring 30    

Connection

Connectors Type Dimensions
Top Board
Digital input 1 connector 3-way screw plug-in connector type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Analog input 11-14 connector 7-way screw plug-in connector type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Digital input 2 connector 3-way screw plug-in connector type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Digital input 3 connector 3-way screw plug-in connector type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Digital input 4 connector 3-way screw plug-in connector type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Digital input 5-8 connector 5-way screw plug-in connector type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Bottom Board
Digital output 1-5 connector 10-way screw plug-in connector type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Digital output 6 connector 6-way screw plug-in connector type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Ethernet connector 8 / 8 way RJ 45 plug type  
USB host connector USB Type A  
Analog input 1-5 connector 11-way screw plug-in connector type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Power supply connector 2-way screw plug-in connector type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Digital output 9-13 connector 10-way screw plug-in connector type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

Analog output 1-2 connector 8-way screw plug-in connector type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

RS485 -2 connector 3-way screw plug-in connector type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

RS485-1connector 3-way screw plug-in connector type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

CAN connector 4-way screw plug-in connector type •        pitch 5 mm

•        section cable 0.2 – 2.5 mm²

CAN-RJ connector 6/6 way telephone RJ12 plug type  
USB DEV connector USB Mini B  

User interface

LCD Display

  • display mode: STN blue transmissive
  • back-light: white LED back-light, adjustable via software
  • display format: 128 x 64 dots
  • active visible area: 58 x 29 mm
  • contrast: adjustable via software

Display settings adjustment

  • Settings of the LCD display like contrast and brightness, might need to be adjusted due to external ambient factors.
  • Press and release the Enter and X key after powering on to access the BIOS menu and select the DISPLAY menu.
  • Use UP and DOWN arrow keys to adjust the contrast or the brightness of the display at the desired level.

External display

Danfoss-80G8280-Ejector-Controller-FIG-4

Dimension

Dimension EKE 80

Danfoss-80G8280-Ejector-Controller-FIG-5

Connection, lower level

Warning
The supply voltage of AI may not share the signal with other controllers

Danfoss-80G8280-Ejector-Controller-FIG-6

Connection, upper level

Danfoss-80G8280-Ejector-Controller-FIG-7

AI Label Description Signal type choice Via software or fieldbus Default Modbus register Comment
AI-01 AI1 Capacity Reference 0–10 V

0–5 V

2–10 V

0–20 mA

4–20 mA

0–10 V 17902 Max 13.5 V input voltage.

Do not connect voltage sources without current limitation (overall 80 mA) to analog inputs while unit is not powered

AI-02 AI2 ICAD Ejector Mode Feedback 0–20 mA

4–20 mA

4–20 mA 17903
AI-03 AI3 ICAD Bypass Mode Feedback 0–20 mA

4–20 mA

4–20 mA 17904
AI-04 AI4 Pressure Transmitter 0–5 V

0–10 V

0–20 mA

4–20 mA

4–20 mA 17905
AI-05 AI5 Temperature Sensor 0–10 V NTC–10K PT1000 PT1000 17906
AI-06 N/A Not available for customer use N/A N/A Reserved Reserved
AI-07
AI-08
AI-09
AI-10
AI-11 AI11 Not used in logic. User configurable IO None NTC–10K PT1000 0–5 V

0–10 V

2–10 V

0–20 mA

4–20 mA

None 17907 Max 13.5 V input voltage.

Do not connect voltage sources without current limitation (overall 80 mA) to analog inputs while the unit is not powered

AI-12 AI12 17908
AI-13 AI13 17909
AI-14 AI14 17910
AI-15  

N/A

 

Not available for customer use

 

N/A

 

N/A

 

Reserved

 

Reserved

AI-16
A0 Label Description Signal type choice Default Modbus register Comment
A0-01 AO1 ICAD Ejector Mode Request OD 0–10 V

2–10 V

0–10 V 18102 Analog Outputs galvanically isolated, minimum load 1K Ω (10 mA) for each output
A0-02 AO2 ICAD Bypass Mode Request OD 0–10 V

2–10 V

0–10 V 18103
A0-03 N/A Not available for customer use N/A Reserved Reserved
A0-04
A0-05
A0-06
DI Label Description Signal type choice Default Modbus register Comment
DI-01 DI1 Not used in logic, User configurable IO 24 V or 230 V Depending on port used. See upper level diagram  

 

 

 

17498 24 V Opto isolated, 24 V AC 50/60 Hz or 24 V DC Rated current: 5 mA @ 24 V AC

230 V Opto isolated, 86–265 V AC / 50/60 Hz, Reinforced isolation, Rated current: 2,5 mA @ 265 V AC

DI-02 DI2 Not used in logic, User configurable IO 17499
DI-03 DI3 Not used in logic, User configurable IO 17500
DI-04 DI4 Not used in logic, User configurable IO 17501
DI-05 DI5 Suction Flow Control Dry contact and/or 24 V AC  

 

 

17503 As the inputs are not isolated, caution has to be used when applying 24 V AC: the same polarity of the supply MUST always be used on COM/GND connection. Counting function with max frequency of 16.6 Hz (30 ms minimum pulse time)
DI-06 DI6 Ejector Mode Signal Error 17504
DI-07 DI7 Bypass Mode Error Signal 17505
DI-08 N/A Not used in logic N/A N/A Reserved Reserved
DI-09
DI-10
DI-11
DI-12
DI-13
DI-14
DI-15
DI-16
DI-17
DI-18
DI-19
DI-20
DI-21
DI-22
DO Label Description Signal type choice Default Modbus register Comment
DO-01 DO1 Alarm output   17702 5 A 250 V AC for resistive loads – 100,000 cycles

3 A 250 V AC for inductive loads – 100,000 cycles with cos(phi) = 0.4

UL: 3 A resistive, 250 V AC, 100,000 cycles; 1/8 hp, 125/250 V AC, 30,000 cycles; C300 pilot duty, 125/250 V AC, 30,000 cycles

DO-02 N/A Not used in logic N/A N/A Reserved  
DO-03 DO3 User-assigned Ejector  

 

 

 

 

 

Not assigned Ejector 1

Ejector 2

Ejector 3

Ejector 4

Ejector 5-8 expansion module only

Not assigned 17703 Internal Solid State Relay for Industrial Ejector Coils:

15–280 Vrms, 0.5 A

UL: Making current: 7 A, Breaking current:

0.7 A, Pilot duty (cos θ 0.35), 240 V AC, N.O

IMPORTANT: For a Multi-Ejector, an external Solid State Relay is necessary between the assigned DO and the

Multi-Ejector solenoid coils that meet the following specifications:

Leakage current suppression.

At least 2 A rating for both 110 V and 230 V Multi-Ejector coils.

IMPORTANT: Ejectors 5 to 8 can only be assigned to an extension module. An extension module is the same controller device as this device except that it is user-configured/ defined as an extension module for control of extra Ejectors, i.e., When there are more than 4 Industrial Ejectors.

DO-04 DO4 User-assigned Ejector Not assigned 17704
DO-05 DO5 User-assigned Ejector Not assigned 17705
DO-06 DO6 User-assigned Ejector Not assigned 17706
DO-07 N/A Not used in logic N/A N/A Reserved N/A
DO-08
DO-09
DO-10
DO-11
DO-12
DO-13
DO-14
DO-15
DO-16
DO-17
DO-18
DO-19
DO-20

CONTACT

  • Danfoss A/S
  • Climate Solutions
  • danfoss.com
  • +45 7488 2222

Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals cataloques descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding it and to the extent, explicit reference is made in a quotation or order confrmation. Dantoss cannot accept any responsibility for possible errors in catalogues, brochures, videos, and other material. Janfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered, provided that such alterations can be made without changes to form, fit or function of the product.
All trademarks in this material are the property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

Danfoss-80G8280-Ejector-Controller-FIG-1

FAQ

Q: Can the EKE 80 Ejector Controller be used with third-party controllers?

A: The EKE 80 is designed to work with Danfoss controllers AK-PC 782A/AK-PC 782B or a PLC. Compatibility with third-party controllers may vary, it is recommended to consult with Danfoss support for further information.

Q: What is the maximum wire length supported for Ethernet connection?

A: The maximum wire length for Ethernet connection is 100 meters.