Danfoss 080Z2830 Gas Detecting Sensor

DGS sensors can be used in stand-alone or integrated systems, where continuous real-time, automatic monitoring with Danfoss ADAP-KOOL® Refrigeration Control & Monitoring System and/or Building Management Systems is applied.
DGS supports our customers in complying with environmental F-Gas Regulations and Health & Safety requirements on new or existing systems in:
- supermarkets
- process refrigeration plants
- refrigerated storage and warehousing
- special application areas/zones
Typical refrigerant gas applications include:
- halocarbons: HFCs, HCFCs, CFCs
- carbon dioxide (CO₂/R744)
- hydrocarbons (e.g. R290)
- other special application gases to customer request
Sensing technology varies to make the best detection for a given gas, in terms of performance and cost. DGS-IR is based on infra-red sensor technology, DGS-SC is based on semi-conductor and DGS-PE is based on pellistor.

Product specification
Technical Data
Table 1: Technical data
| Power supply | 24 V DC ± 20 % ; reverse polarity protected 24 V AC – 10 % / + 15 % | ||
| Power Consumption (24 V DC) | Max. 250 mA (6 VA) | ||
| Digital output |
|
||
| Analogue output signal | Proportional, overload and short-circuit proof, load ≤ 500 Ohm Measuring range: 0 – 10 V / 2 – 10 V / 0 – 20 mA / 4 – 20 mA | ||
| MODBUS Physical | 5 V DC, 250 mA max. overload, short-circuit and reverse-polarity protected | ||
| Enclosure rate | IP 65 | ||
| Humidity range | 15 – 90 % RH not-condensing | ||
| Burning behaviour | UL 94 V2 | ||
| Housing colour | Black | ||
| Dimensions (W x H x D in mm) | 94 x 130 x 57 | ||
| Installation | Wall mounting | ||
| Cable entry | 2 x M12 / 3 x M20 | ||
| Wire connection: | Power supply, MODBUS: Screw-type terminals 0.25 – 2.5 mm2 Analogue output, Digital input: Screw-type terminals 0.25 – 1.3 mm2 Sensor head: 3-pin plug connector | ||
| Sensor information | DGS-IR (CO2) | DGS-SC (HFC) | DGS-PE (Propane) |
| Temperature range | -35 – 50 °C | -30 – 60 °C | -30 – 60 °C |
| Response time T90 | <90 sec. | ≤ 150 sec. | <15 sec. |
| Recovery time, T0 | 90 sec. | 180 sec. | 120 sec. |
| Maximum calibration interval | 60 months | 12 months | 12 months |
| Measuring range | 0 – 20000 ppm | 0 – 2000 ppm | 0 – 5000 ppm |
| Lowest threshold | 10% of the measuring range | 10% of the measuring range | 10% of the measuring range |
| Default alarm threshold | 5000 ppm | 500 ppm | 800 ppm |
| Compliance | EN61010-1 | ||
| B&L – Buzzer and Light (option by product selection) | Light (LED): Red / yellow /green (alarm – fault – operation – service) Buzzer: >85 dB (A) (0.1 distance ) 2300 Hz ± 300 Hz | ||
Ordering
Table 2: Ordering

- HFC gHFC grrp 1: R1234zp 1: R1234zee, R454C, , R454C, R1234yfR1234yf, R452A, R455A, R454B, R452A, R455A, R454B, R513A, R1233z, R513A, R1233zdd, R515b, R515b
- HFC gHFC grrp 2: R407Fp 2: R407F, R416A, R417A, R407A, R422A, R427A, R449A, R437A, , R416A, R417A, R407A, R422A, R427A, R449A, R437A, R134AR134A, R438A, R422D, R438A, R422D, R450A, R450A HFC gHFC grrp 3: R448A, R125, R404A, R32, R507A, R434A, R410A, R452Bp 3: R448A, R125, R404A, R32, R507A, R434A, R410A, R452B, , R407CR407C, R143B, R143B
Bold = calibration gas
NOTE: DGS is also available for alternative refrigerant gases on request. Please contact your local Danfoss Sales Office for details.
Accessories
Hand-held Service tool
Figure 1: Hand-held Service tool

- Hand-held device for display, calibration, addressing and parameters changes.
- Communication and power supply will be ensured via a cable that is plugged into the respective devices.
Features
- User-friendly design
- Simple menu structure
- Two-line display / 16 characters
- Six operating buttons
- Three LEDs for status display
- Communication / power supply via a cable
Gas detecting sensor, type DGS
Table 3: Specifications
| Features | Description |
| Electrial | |
| Power supply | 5 V DC from device, reverse-polarity protected |
| Power consumption | 50 mA, max. (0.25 VA) |
| Serial interface local bus | 5 V level / 19200 Baud |
| Ambient Conditions | |
| Temprature range | -10 – +40 °C (14 – 104 °F) |
| Humidity range | 0 – 90% RH non-condensing |
| Physical | |
| Housing | Polycarbonate |
| Dimensions | 117 x 78 x 25 mm |
| Weight | Ca. 200g |
| Protection Class | IP65 |
| Cable Length | 1.50 m |
| Regulations | |
| Directives | EMC directives 2014/30/EU CE Conformity to:EN 61010-1:2010ANSI/UL 61010-1CAN/CS-C22.2 No. 61010-1 |
Strobe & Horn
Figure 2: Strobe & Horn

Electronic sounder that allows two levels of alarm (warning, critical) controllable via independent electric contacts.
Features
- Selectable tones
- Separate electric control for strobe and horn
Table 4: Specifications
| Alarm Sounder | Description |
| Operating voltage | 12 – 24 V DC |
| Operating temperature | -40 – +55 °C |
| Number of user-selectable tones | 32 |
| Lens colour | Red |
| IP rating | IP 65 |
Sensor head protection
Figure 3: Sensor head protection

- Plastic protective cap with non-slip, knurled rim, for covering sensors of the DGS series.
- The elastic protective cap is placed on the sensor to protect it from contamination during installation, cleaning and painting work and to protect the sensor element from poisoning, e.g. by silicone vapours.
- When commissioning, it is essential to remove the tight-fitting cap to ensure the proper functioning of the sensor.
Features
- Easy to use
- Perfect coverage of the sensor head
- Protection against pollution/poisoning
Table 5: Specifications
| CAP | Description |
| Material | Plastic TPE |
| Colour | Red (RAL 3000) |
| Dimensions inside | Ca. 24 mm x 18 mm (D x G ) see figure below |
| Temperature range cap | -50 °C to +120 °C (-58 °F to 248 °F) |
Splash guard
Figure 4: Splash guard
- Cap for protecting the DGS sensor against splash water.
- The cap is placed over the sensor head and secured by means of a detachable zip tie. It protects the sensor against rain and splash water coming from all directions.
- The splash guard is used in gas warning systems, which are mounted outside unprotected from the weather. It can also be used to protect the sensor during cleaning work.
Features
- Protection against rain, splash water and other weather conditions.
- Easy installation. Assembly and disassembly possible at any time due to detachable zip tie.
Table 6: Specifications
| REDCAP | Description |
| Material | LDPE+PC |
| Dimensions | 25 x 37 mm (D x H) |
| Protection class | IP66 |
Duct set
The duct mounting set consists of a sampling tube with hose and adapter for DGS sensors. Duct mounting set for sampling from air ducts.
Features
- Easy to use
- Perfect coverage of the sensor head
- Double pipe can be cut to length for adaptation to the duct diameter
Table 7: Specifications
| Sampling SET | Description |
| Gas sampling | Via sampling tube / connecting hose |
| Flow rate | Min. 5000 m/h (3.1 mph), max. 20,000 m/h (12.4 mph) |
| Air duct diameter | Min. 0.1 m (3.94 in.), max. 1.0 m (39.37 in.) |
| Length of sampling tube | 250 mm (9.84 in.), adaptable to the duct diameter by cutting to length: 192 mm (7.56 in.), 133 mm (5.24 in.) or 77 mm (3.03 in.) |
| Hose length | 2 x 1000 mm (39.37 in.) |
| Assembly |
|
Calibration Adapter
Figure 5: Calibration Adapter
- Calibration adapter for comfortable gas supply to DGS sensors.
- The calibration adapter is used for the targeted supply of zero and test gases to the sensor head.
Features:
- Easy to use
- Perfect coverage of the sensor head
- Double pipe can be cut to length for adaptation to the duct diameter
Table 8: Specifications
| Item | Description |
| Cap | |
| Material | PE-LD |
| Dimensions (D x G) | 25 x 20 mm (0.98 x 0.79 in) |
| Hose | |
| Material | PVC-P polyvinyl chloride |
| Temperature range | -20 – +60 °C (-4 – +140 °F) |
| Diameter | OD = 7 mm, ID = 4 mm |
| Length | 1 m (39.37 in) |
Remote kit
Figure 6: Remote kit
- Cable extension with housing for remote mounting of DGS sensors.
- The remote kit is used as a cable extension for the remote installation of sensors.
Features
- Easy to use
- Perfect coverage of the sensor head
- Double pipe can be cut to length for adaptation to the duct diameter
Table 9: Specifications
| Features | Description |
| Physical | |
| Material | Polycarbonate |
| Flammability classification | UL 94 V2 |
| Dimensions (W x H x D) | 94 x 65 x 57 mm |
| Weight | 0.2 kg (0.66 lb) |
| Protection class | NEMA 4X (IP65) |
| Mounting | Wall mounting |
| Knockouts for cable entry | 2x M25 |
| Regulations | |
| Directives | EMC Directives 2014/30/EU CE, UKCA |
Certificates, declarations, and approvals
- The list contains all certificates, declarations, and approvals for this product type. Individual code number may have some or all of these approvals, and certain local approvals may not appear on the list.
- Some approvals may change over time. You can check the most current status at danfoss.com or contact your local Danfoss representative if you have any questions.
Table 10: Certificates, declarations, and approvals
| Document type | Document topic | Approval authority |
| EU Declaration | EMCD/LVD | Danfoss |
Online support
Danfoss offers a wide range of support along with our products, including digital product information, software, mobile apps, and expert guidance. See the possibilities below.
The Danfoss Product Store
The Danfoss Product Store is your one-stop shop for everything product-related—no matter where you are in the world or what area of the cooling industry you work in. Get quick access to essential information like product specs, code numbers, technical documentation, certifications, accessories, and more.
Start browsing at store.danfoss.com.- Find technical documentation
Find the technical documentation you need to get your project up and running. Get direct access to our official collection of data sheets, certificates and declarations, manuals and guides, 3D models and drawings, case stories, brochures, and much more.
Start searching now at www.danfoss.com/en/service-and-support/documentation.
- Danfoss Learning
Danfoss Learning is a free online learning platform. It features courses and materials specifically designed to help engineers, installers, service technicians, and wholesalers better understand the products, applications, industry topics, and trends that will help you do your job better.
Create your Danfoss Learning account for free at Kwww.danfoss.com/en/service-and-support/learning. - Get local information and support
Local Danfoss websites are the main sources for help and information about our company and products. Find product availability, get the latest regional news, or connect with a nearby expert—all in your own language.
Find your local Danfoss website here: www.danfoss.com/en/choose-region.
FAQs
What is the maximum calibration interval for the sensor?
The maximum calibration interval is specified by the manufacturer and should be followed to ensure accurate detection.
Can the sensor be used for residential applications?
The sensor is primarily designed for commercial buildings but can be adapted for specific residential use cases based on gas detection requirements.
Documents / Resources
![]() |
Danfoss 080Z2830 Gas Detecting Sensor [pdf] Owner's Manual 080Z2830, 080Z2831, 080Z2832, 080Z2833, 080Z2834, 080Z2835, 080Z2836, 080Z2837, 080Z2838, 080Z2839, 080Z2840, 080Z2841, 080Z2842, 080Z2830 Gas Detecting Sensor, 080Z2830, Gas Detecting Sensor, Detecting Sensor, Sensor |