DALCNET-DLM12XX-1CV-DLM-Single-Channel-Multi-Input-LOGO

DALCNET DLM12XX-1CV DLM Single Channel Multi-InputDALCNET-DLM12XX-1CV-DLM-Single-Channel-Multi-Input-PRO

FEATURES

  •  FADER+DIMMER+DRIVER
  •  DC Input: 12-24-48 Vdc or 12-24 Vdc
  •  MULTI INPUT – Analogic Automatic Detection of the Local command:
    •  Normally Open push-button
    •  Analog input 0-10V
    •  Analog input 1-10V
    •  Potentiometer 10KOhm
  •  PUSH MENU’ – Possibility to set:
    •  The minimum value of dimming
    •  Fade In
    •  Fade Out
  •  Constant Voltage variant for Common Anode applications
  •  Voltage outputs for R-L-C loads, DLM1248-1CV variant
  • Voltage outputs for R loads, DLM1224-1CV variant
  •  Memory function
  •  Adjusting the brightness of white light or monochromatic color
  •  Adjusting the brightness up to complete off
  •  Soft start and soft stop
  •  Sync function – Master/Slave
  •  Optimized output curve
  •  Typical efficiency > 95%
  • 100% Functional test – 5 Years warranty

For the whole and updated Device, Manual refer to the producer’s website: http://www.dalcnet.comDALCNET-DLM12XX-1CV-DLM-Single-Channel-Multi-Input-FIG-1

CONSTANT VOLTAGE VARIANTS

CODEInput voltageOutputChannelsAnalogic Auto Detection
 

DLM1248-1CV

 

12-48V DC

 

1 x 6,5A

 

1

N° 1 N.O. Push Button N° 1 analog signal 0-10V N° 1 analog signal 1-10V

N° 1 Potentiometer 10K

 

DLM1224-1CV

 

12-24V DC

 

1 x 10A

 

1

N° 1 N.O. Push Button N° 1 analog signal 0-10V N° 1 analog signal 1-10V

N° 1 Potentiometer 10K

Application: Dimmer 

The LED dimmer is produced by default with:

  •  Analogic Automatic Detection of local command set as N.O. Push Button
  •  Dimming minimum level 1%

PROTECTIONS

DLM1248-1CVDLM1224-1CV
OTPOver temperature protection1
OVPOver voltage protection2
UVPUnder voltage protection2
RVPReverse polarity protection2
IFPInput fuse protection2
SCPShort circuit protection
OCPOpen circuit protection
CLPCurrent limit protection
EN 61347-1Lamp controlgear – Part 1: General and safety requirements
EN 55015Limits and methods of measurement of radio disturbance characteristics of electrical lighting and similar equipment
EN 61547Equipment for general lighting purposes – EMC immunity requirements
IEC 60929-E.2.1Control interface for controllable ballasts – control by d.c. voltage – functional specification
ANSI E 1.3Entertainment Technology – Lighting Control Systems – 0 to 10V Analog Control Specification

TECHNICAL SPECIFICATIONS

DLM1248-1CV VariantDLM1224-1CV Variant
Constant voltageConstant voltage
Supply voltagemin: 10,8 Vdc .. max: 52,8 Vdcmin: 10,8 Vdc .. max: 26,4 Vdc
Output voltage= Vin= Vin
Input currentmax 6,5Amax 10A
Output current6,5A 310A 3
Absorbed nominal power3@12V78 W120 W
@24V156 W240 W
@48V312 W
Power loss in standby mode<500mW<500mW
Type of LoadR – L – CR
Thermal shutdown4150°C
Command supply current0,5mA (per 1-10V)0,5mA (per 1-10V)
Command required current (max)0,1mA (per 0-10V)0,1mA (per 0-10V)
D-PWM dimming frequency300Hz300Hz
D-PWM resolution16 bit16 bit
D-PWM range0,1 – 100%0,1 – 100%
Storage Temperaturemin: -40 max: +60 °Cmin: -40 max: +60 °C
Ambient Temperaturemin: -10 max: +40 °Cmin: -10 max: +40 °C
Wiring2.5mm2 solid – 2.5mm2 stranded – 30/12 AWG1.5mm2 solid – 1mm2 stranded – 30/16 AWG
Wire preparation length5.5 – 6.5 mm5 – 6 mm
Protection gradeIP20IP20
Casing materialPlasticPlastic
Packaging unit (pieces/unit)Single Carton Box 1 pzCarton Box 10pz
Mechanical dimensions44 x 57 x 25 mm44 x 57 x 19 mm
Package dimensions56 x 68 x 35 mm164 x 117x 70 mm
Weight40g306g
  • Maximum value, dependent on the ventilation conditions. This value is measured at 40°C, it is maximum ambient temperature.
  • Thermal Protection on the output channel in case of high temperature. The thermal intervention is detected by transistor.

INSTALLATION

To set the product, follow the instruction on the picture below:

  1.  connect the power supply (12-24 Vdc or 12-48 Vdc depending on the dimmer model) to terminal blocks “DC IN” of the device.
  2.  connect the LOCAL COMMAND to the terminal blocks “INPUT” of the device.
  3.  connect the LED in the output terminal blocks “OUT” of the device.

LOCAL COMMAND

AUTOMATIC DETECTION OF THE TYPE OF LOCAL COMMAND

At the first switch, the device is set by default to automatic recognition of push button N.O. Command.

AUTOMATIC DETECTION OF THE 0/1-10V & POTENTIOMETER COMMAND

The automatic recognition of analog signal 0/1-10V or potentiometer starts as a 0/1-10V value between 3V and 7V is sent out or setting the potentiometer with a value included from 30% and 70%.

COMMAND 0-10VCOMMAND 1-10VPOTENTIOMETER

AUTOMATIC DETECTION OF THE N.O. PUSH BUTTON COMMAND

The N.O. push button s identified automatically after 5 clicks in rapid sequence. In mode N.O. push button, function memory is always active.

SYNC INSTALLATION

SYNC FUNCTION WITH SINGLE POWER SUPPLY
It is possible to connect multiple device of the family DLM-1CV among them in mode Master/Slave
Connect the local command desired to the device used as Master. Connect master “TX” signal to the “RX” entrances of slave. Example of Master/Slave:

SYNC FUNCTION WITH ONE POWER SUPPLY FOR DIMMER
In the case multiple power supplies are used to power “master” dimmer and “slave” dimmers, connect all the “COM” inputs of the LedDimmer to each other.

SYNC FUNCTION WITH ONE POWER SUPPLY FOR DIMMER
In the case multiple power supplies are used to power “master” dimmer and “slave” dimmers, connect all the “COM” inputs of the LedDimmer to each other.

NOTE FOR MASTER/SLAVE INSTALLATION

  1.  Using one power supply every single dimmer, first power on the Master unit and after that give power to the Slave.
  2.  When doing maintenance on the installation take care of shutting down power to the Slave units first and than to the Master.
  3.  When power to the Master unit is missing, the Slave set up automatically to the default ex-factory settings (power on 100%) or to the settings previously saved.

TECHNICAL NOTE

Installation: 

  •  Installation and maintenance must be performed only by qualified personnel in compliance with current regulations.
  •  The product must be installed inside an electrical panel protected against overvoltages.
  •  The product must be installed in a vertical or horizontal position with the cover / label upwards or vertically; Other positions are not permitted. It is not permitted to bottom-up position (with the cover / label down).
  •  Keep separated the circuits at 230V (LV) and the circuits not SELV from circuits to low voltage (SELV) and from any connection with this product. It is absolutely forbidden to connect, for any reason whatsoever, directly or indirectly, the 230V mains voltage to the bus or to other parts of the circuit.

Power supply: 

  • For the power supply use only a SELV power supplies with limited current, short circuit protection and the power must be dimensioned correctly. In case of using power supply with ground terminals, all points of the protective earth (PE = Protection Earth) must be connected to a valid and certified protection earth.
  •  The connection cables between the power source “low voltage” and the product must be dimensioned correctly and they should be isolated from every wiring or parts at voltage not SELV. Use double insulated cables.
  •  Dimension the power supply for the load connected to the device. If the power supply is oversized compared with the maximum absorbed current, insert a protection against over-current between the power supply and the device.

Command: 

  •  The length of the connection cables between the local commands (N.O. Push button, 0-10V, 1-10V, Potentiometer or other) and the product must be less than 10m; the cables must be dimensioned correctly and they should be isolated from every wiring or parts at voltage not SELV. Use double insulated shielded and twisted cables.
  •  The length and type of the connection cables at the BUS SYNC must be less than 3m and they should be isolated from every wiring or parts at voltage not SELV. It is suggested to use double insulated shielded and twisted cables.
  •  All the product and the control signal connect at the bus and at the local command (N.O. Push button, 0-10V, 1-10V, Potentiometer or other) must be SELV (the devices connected must be SELV or supply a SELV signal)

Outputs: 

The length of the connection cables between the product and the LED module must be less than 10m; the cables must be dimensioned correctly and they should be isolated from every wiring or parts at a voltage, not SELV. Is preferable to use shielded and twisted cables.

MECHANICAL DIMENSION

PUSH DIMMER FEATURE

ButtonIntensity
ClickOn/Off
Double ClickMaximum intensity
Long pressure (>1s) from OFFTurn ON at 1% (Nightly Time), then dimmer up/down
Long pressure (>1s) from ONDimmer up/down
15 Click in 5 second-timeEnter in to PUSH MENU’

The intensity and the status change (ON/OFF) are controlled by the N.O. push button.

0-10V & 1-10V & POTENTIOMETER FEATURE

ButtonFunctionIntensity
0-10V

1-10V

Potentiometer 10K

Dimmer: 0-1V=0%                                                                                                              10V=100%

The intensity is controlled by input voltage variation.

PUSH MENU

FUNCTION AVAILABLE

  •  MINIMUM VALUE OF DIMMING
  •  POWER-ON RAMP (FADE IN)
  •  POWER-OFF RAMP (FADE OUT)

ACCESS TO MENU’ 

When you turn-on the LED dimmer, the output is set at 100% and the minimum of dimming is at 1 %. To access the device menu, click the push button 15 times in 5 seconds time.
When the Load flashes, you are in “MENU’ 1”.

 MENU’ 1 – MINIMUM VALUE OF DIMMING
Every single click make it changing the minimum value of dimming There are six level of minimum: 0,1%, 1%, 5%, 10%, 20%, 30% and 100% After setting the minimum value of dimming press long to confirm. A double flashing confirms the storage and you can go to “MENU’ 2”
Note: if you set the minimum level to 100%, once the settings is confirmed, the device automatically exits the MENU’.

MENU 2 – POWER-ON RAMP (FADE IN)
Every single click make it changing the power-on ramp There are five levels of power-on ramp (FADE IN): Instantaneous, 1 second, 2 seconds, 3 seconds, 6 seconds. After setting the FADE IN press a long to confirm. Three flashes confirm the storage and you can go to “MENU’ 3”

MENU’ 3 – POWER-OFF RAMP (FADE OUT)
Every single click make it change the power-off ramp There are five levels of power-off ramp (FADE OUT): Instantaneous, 1 second, 2 seconds, 3 seconds, 6 seconds. After setting the FADE OUT press long to confirm. Three quick flashes confirm the storage and you go out from the “DEVICE MENU’”  When you are out of the Menu’, the Lamp which is connected to the LED Dimmer turns on at the minimum level of dimming previously set.

DALI BUS SETUP

In DALI BUS SETUP all the leds are controlled by an external DALI controller.

 BUS CONNECTION

COMMAND

STANDARD COMMAND
DIRECT ARC POWERü
OFFü
UPü
DOWNü
STEP UPü
STEP DOWNü
RECALL MAX LEVELü
RECALL MIN LEVELü
STEP DOWN AND OFFü
ON AND STEP UPü
GOTO SCENE (0 to 15)ü
RESETü
STORE ACTUAL LEVEL IN THE DTRü
STORE THE DTR AS MAX LEVELü
STORE THE DTR AS MIN LEVELü
STORE THE DTR AS SYSTEM FAILURE LEVELü
STORE THE DTR AS POWER ON LEVELü
STORE THE DTR AS FADE TIMEü
STORE THE DTR AS FADE RATEü
STORE THE DTR AS SCENE (0 to 15)ü
REMOVE FROM SCENE (0 to 15)ü
ADD TO GROUP (0 to 15)ü
REMOVE FROM GROUP (0 to 15)ü
STORE DTR AS SHORT ADRESSü
ENABLE WRITE MEMORYû
QUERY STATUS5
QUERY BALLASTü
QUERY LAMP FAILURE5
QUERY LAMP POWER ONü
QUERY LIMIT ERRORü
QUERY RESET STATEü
QUERY MISSING SHORT ADDRESSü
QUERY VERSION NUMBERü
QUERY CONTENT DTRü
QUERY DEVICE TYPE6
QUERY PHYSICAL MINIMUM LEVELü
QUERY POWER FAILUREü
QUERY CONTENT DTR1ü
QUERY CONTENT DTR2ü
QUERY ACTUAL LEVELü
QUERY MAX LEVELü
QUERY MIN LEVELü
QUERY SYSTEM FAILURE LEVELü
QUERY FADE TIME / FADE RATEü
QUERY SCENE LEVEL (0 to 15)ü
QUERY GROUPS 0-7ü
QUERY GROUPS 8-15ü
QUERY ADDRESS Hü
QUERY ADDRESS Mü
QUERY ADDRESS Lû
READ MEMORY LOCATIONû
SPECIAL COMMAND
TERMINATEü
DATA TRANSFERT REGISTERü
INITIALIZEü
RANDOMIZEü
COMPAREü
WITHDRAWü
SEARCHADOR Hü
SEARCHADOR Mü
SEARCHADOR Lü
PROGRAM SHORT ADDRESSü
VERIFY SHORT ADDRESSü
QUERY SHORT ADDRESSü
PHYSICAL SELECTIONû
ENABLE DEVICE TYPEû
DATA TRANSFER REGISTER 1ü
DATA TRANSFER REGISTER 2ü
WRITE MEMORY LOCATIONû

DEFAULT VALUE

FACTORYRESET
ACTUAL LEVEL254254
POWER ON LEVEL254254
SYSTEM FAILURE LEVEL254254
MIN LEVEL11
MAX LEVEL254254
FADE RATE77
FADE TIME00
SHORT ADDRESSFF(no change)
SEARCH ADDRESSFF FF FFFF FF FF
RANDOM ADDRESSFF FF FFFF FF FF
GROUP 0-700
GROUP 8-1500
SCENE 0-15MASKMASK
STATUS INFORMATION1??0????0?100???
VERSION NUMBER1(no change)
PHYSICAL MIN. LEVEL1(no change)
ANSI E1.11Entertainment Technology – USITT DMX512-A – Asynchronous Serial Digital Data Transmission Standard for

Controlling Lighting Equipment and Accessories

ANSI E1.20Entertainment Technology-RDM-Remote Device Management over USITT DMX512 Networks

CHANNEL MAPS

ChannelFunctionValue
1DimmerIntensity [0..255]

RDM COMMAND

REQUESTED PARAMETERS
DISC_UNIQUE_BRANCHü
DISC_UN_MUTEü
SUPPORTED_PARAMETERSü
PARAMETERS_DESCRIPTIONü
DEVICE_INFOü
SOFTWARE_VERSION_LABELü
DMX_START_ADDRESSü
IDENTIFY_DEVICEü

SUPPORTED PARAMETERS
PRODUCT_DETAIL_ID_LISTü
DEVICE_MODEL_DESCRIPTIONü
MANUFACTURER_LABELü
DEVIDE_LABELü
BOOT_SOFTWARE_VERSION_IDü
BOOT_SOFTWARE_VERSION_LABELü
DMX_PERSONALITYü
DMX_PERSONALITY_DESCRIPTIONü
SLOT_INFOü
SLOT_DESCRIPTIONü
DEFAULT_SLOT_VALUEü

Documents / Resources

DALC NET DLM12XX DLM Single Channel Device [pdf] Instruction Manual
DLM12XX, DLM Single Channel Device

References

Leave a comment

Your email address will not be published. Required fields are marked *