BRC1H Series Wired Remote Controller
“
Specifications
- Product: Wired remote controller BRC1H Series
- Supports DAIKIN APP
- Version: Ver.2.6.0
Product Information
The Wired remote controller BRC1H Series is designed to work
with the DAIKIN APP for efficient control of your Daikin HVAC
system. The controller offers various features and settings to
customize your comfort settings.
Product Usage Instructions
Cautions for Use
Before using the remote controller, make sure to read and
understand the cautions for use provided in the manual to ensure
safe and proper operation.
App Startup
Learn how to start up the DAIKIN APP and navigate through the
basic usage functionalities.
Basic Usage
Understand how to operate the remote controller in its basic
mode for simple temperature adjustments and fan speed settings.
Manual Setting Mode
Explore the manual setting mode to customize advanced settings
for your HVAC system, including installer settings, RC settings,
indoor unit settings, and more.
Work History
View the work history log to track changes and adjustments made
to the system over time.
Access the various options available in the app menu for
additional control and customization.
Troubleshooting
Refer to the troubleshooting section to address common issues
that may arise during operation.
About Display Messages
Learn about the different display messages that may appear on
the remote controller and their meanings.
About Trademarks and Copyright
Understand the trademarks and copyright information related to
the product and app.
FAQ
Q: How do I pair the remote controller with the app?
A: To pair the remote controller with the app, follow the
instructions provided in the “Remote controller preparation” and
“Pairing with the remote controller” sections of the operation
manual.
Q: Can I configure advanced settings such as setpoint range
limitation?
A: Yes, you can configure advanced settings like setpoint range
limitation by accessing the “Installer setting” and “Setpoint range
limitation” sections in the manual setting mode.
“`
Wired remote controller
BRC1H Series
DAIKIN APP
Support manual for Administrator
Ver.2.6.0
English Tagalog Melayu Orang indonesia Ting vit nam Español Português
CONTENTS
Cautions for use App startup Basic usage Manual setting mode Work history App menu Troubleshooting About display messages About trademarks and copyright
CONTENTS
Cautions for use
Cautions for use
1
App startup
Basic usage
Manual setting mode
Work history
App menu
Troubleshooting
About display messages
About trademarks and copyright
CONTENTS
Cautions for use
App startup
About devices that can be used
3
Language setting
5
User selection
6
Bluetooth and camera setting
7
Terms of service
8
Basic usage
Manual setting mode
Work history
App menu
Troubleshooting
About display messages
About trademarks and copyright
CONTENTS
Cautions for use App startup
Basic usage
How to read this operation manual
9
Remote controller preparation
9
Pairing with the remote controller
12
How to use the app
15
Manual setting mode
Work history
App menu
Troubleshooting
About display messages
About trademarks and copyright
CONTENTS
Cautions for use App startup Basic usage
Manual setting mode
Manual setting mode
17
Installer setting
Service menu
RC security
Work history
App menu
Troubleshooting
About display messages
About trademarks and copyright
CONTENTS
Cautions for use App startup Basic usage
Manual setting mode
Installer setting RC settings Indoor unit settings RC settings Sensor interlocking control RC display settings Service menu RC security Work history App menu Troubleshooting About display messages About trademarks and copyright
CONTENTS
Cautions for use App startup Basic usage
Manual setting mode
Installer setting
RC settings
Indoor unit settings
Filter auto clean
18
Auto draft prevention
20
Sensor settings
22
RC settings
Sensor interlocking control
RC display settings
Service menu
RC security
Work history
App menu
Troubleshooting
About display messages
About trademarks and copyright
CONTENTS
Cautions for use App startup Basic usage
Manual setting mode
Installer setting
RC settings
Indoor unit settings
RC settings
Setpoint configuration
26
Setpoint range limitation
29
Setback
31
Function lock
34
External input interlock
39
Schedule menu *BRC1H63 and above only
43
Holiday setting *BRC1H63 and above only
46
Schedule setting *BRC1H63 and above only
48
Hotel mode *BRC1H63 and above only
53
Sensor interlocking control
RC display settings
Service menu
RC security
Work history
App menu
Troubleshooting
About display messages
About trademarks and copyright
CONTENTS
Cautions for use App startup Basic usage
Manual setting mode
Installer setting
RC settings
Indoor unit settings
RC settings
Sensor interlocking control
Temperature sensor *BRC1H63 and above only
55
CO2 sensor *BRC1H63 and above only
59
Door/Window sensor *BRC1H63 and above only
64
Motion sensor *BRC1H63 and above only
68
RC display settings
Service menu
RC security
Work history
App menu
Troubleshooting
About display messages
About trademarks and copyright
CONTENTS
Cautions for use App startup Basic usage
Manual setting mode
Installer setting
RC settings
Indoor unit settings
RC settings
Sensor interlocking control
RC display settings
Date and time/DST
82
Celsius/Fahrenheit
87
Brightness control
89
Service menu
RC security
Work history
App menu
Troubleshooting
About display messages
About trademarks and copyright
CONTENTS
Cautions for use App startup Basic usage
Manual setting mode
Installer setting
RC settings
Indoor unit settings
RC settings
Sensor interlocking control
RC display settings
Service menu
Error code reset
92
Error history
93
RC security
Work history
App menu
Troubleshooting
About display messages
About trademarks and copyright
CONTENTS
Cautions for use App startup Basic usage
Manual setting mode
Installer setting
RC settings
Indoor unit settings
RC settings
Sensor interlocking control
RC display settings
Service menu
RC security
Owner password
96
Work history
App menu
Troubleshooting
About display messages
About trademarks and copyright
CONTENTS
Cautions for use App startup Basic usage Manual setting mode
Work history
Setting log confirmation procedure
101
App menu
Troubleshooting
About display messages
About trademarks and copyright
CONTENTS
Cautions for use App startup Basic usage Manual setting mode Work history
App menu
Application version
103
Terms of use
104
Open source licenses
105
Application language
106
Application time
107
User mode
108
Troubleshooting
About display messages
About trademarks and copyright
CONTENTS
Cautions for use App startup Basic usage Manual setting mode Work history App menu
Troubleshooting
The app cannot be found
109
Communication with the remote controller is not possible 110
Zigbee icon does not appear on the remote controller screen 114
Zigbee icon is blinking
116
Air conditioner is not interlocking
118
The sensor value is displayed as “-” on the remote controller screen 120
About display messages
About trademarks and copyright
CONTENTS
Cautions for use App startup Basic usage Manual setting mode Work history App menu Troubleshooting
About display messages
App screen (dialog displayed when writing to the remote controller) 121 About trademarks and copyright
CONTENTS
Cautions for use App startup Basic usage Manual setting mode Work history App menu Troubleshooting About display messages
About trademarks and copyright
About trademarks and copyright
124
1
Cautions for use
X DAIKIN APP (hereafter referred to as “app”) is an application provided by Daikin Industries, Ltd. which makes it simple to carry out RC settings of remote controllers made for industrial air conditioners.
X Communication fees which result from the download, update, or use of this app are the responsibility of the user. (This includes additional communication fees which result from updates of this app, re-setting of this app if not functioning correctly, etc.)
X Do not turn off the Bluetooth function of your smartphone while using this app.
2
Cautions for use
X App user should be in close proximity to the remote controller. Do not use Bluetooth low energy connection around wireless LAN or other wireless equipment, around equipment which produces radio waves, or in environments with poor signal conditions. There is a possibility that connection will be interrupted frequently, communication speed may be significantly reduced and errors may occur.
X If worried about your smartphone being infected by a computer virus, we recommend that you install separate anti-virus software.
X If unauthorized use of this app occurs, there is a possibility that the remote controller and air conditioner settings may be changed, so enable an authentication function (passcode, fingerprint authentication, face authentication, etc.) on the smartphone on which the app is installed.
3
App startup
About devices that can be used
Please use this app on a device compatible with Bluetooth low energy communication, as this app uses Bluetooth low energy communication to write setting information to the remote controller. Also, please use a device with a rearfacing camera, as this app scans QR codes after startup depending on usage. · Compatible OS versions:
iOS 18.0* Android 15.0*
· Equipped with rear-facing camera
· Please use a smartphone compatible with BLE 4.2*
* For compatibility with other OS and Bluetooth versions, contact your local Daikin sales office.
4
App startup
· This app can only connect with “BRC1H6” series wired remote controllers.
5
App startup
Language setting
Select the language to display when using this app.
6
App startup
User selection
Select “Owner/Administrator”.
7
App startup
Bluetooth and camera setting
Set the device Bluetooth function to available. If not set to available, this app cannot be used.
8
App startup
Terms of service
After initial startup and setting, upon reaching the end of initial setting, the terms of use of this app are displayed. Please read the terms of use to the end. You must agree to the terms of use to proceed with use of this app.
9
Basic usage
How to read this operation manual
Main : Represents the Main RC Sub : Represents the Sub RC
Remote controller preparation
For details on remote controller usage, refer to the installation manual included with the remote controller. Display the administrator menu
screen When using this app, it is necessary to display the administrator menu screen on the remote controller.
1. Display the home screen on the
remote controller.
30 °C
28
10
Basic usage
2. Press the center button on the
remote controller for 5 seconds or more, and display the information screen.
12:34
3. While the information screen is
displayed, press the center and left button, and keep them both pressed for 5 seconds or more to display the administrator password input screen.
* If a password has been set, the password input screen will be displayed. If a password has not been set, this screen will not be displayed, and continue to step 4.
1
11
Basic usage
4. After the administrator menu screen
is displayed, select the Bluetooth setting icon.
12
Basic usage
Pairing with the remote controller
1. After the Bluetooth setting screen is
displayed on the remote controller*, use this app to select the remote controller you want to connect to.
* The last 6 digits of the Bluetooth device address are displayed on the remote controller, select the same 6 digits that are also displayed on the app.
XX:XX:XX
-+
13
Basic usage
2. A 6 digit number is displayed on
the screens of both the remote controller and this app, so confirm that the displayed numbers are the same, then press “” on the remote controller side and press “Pairing” on the app side.
XXXXXX
-+
14
Basic usage
3. After pairing is complete, the
Administrator mode menu is displayed on the app.
15
Basic usage
How to use the app
CAUTION Once this app writes setting contents to the remote controller, the previous setting contents are overwritten.
From the app Administrator Mode Menu, select one of the option below:
1. Manual setting mode
Select any remote controller and carry out setting.
2. Work history
Review settings log for the remote controller.
3. App menu
X Application version You can confirm the software version of the app.
16
Basic usage
X Terms of use You can confirm the terms of use of the app.
X Open source licenses You can confirm the open-source software license this app uses.
X Application language You can change the language displayed by the app.
X Application time You can change whether the app displays time in 24-hour or 12-hour style.
X User mode You can change the user mode to Administrator or Installer. The app will restart when a change is made.
17
Manual setting mode
Select the remote controller to perform settings on.
* Functions that can be set vary according to the remote controller or air conditioner in use.
18
Manual setting mode
– Installer setting – RC settings – Indoor unit settings
Filter auto clean
Main
Set the time when you want to start the filter auto clean function. After all settings are complete, press the “Send to RC” button.
19
Manual setting mode
– Installer setting – RC settings – Indoor unit settings
X Time span Set the time when you want the filter auto clean function to operate.
X Forbid filter auto clean Set the filter auto clean function to enable/disable.
20
Manual setting mode
– Installer setting – RC settings – Indoor unit settings
Auto draft prevention
Main
Set the auto draft prevention function, so that people are not directly hit by indoor unit discharge air. After all settings are complete, press the “Send to RC” button.
21
Manual setting mode
– Installer setting – RC settings – Indoor unit settings
X Auto draft prevention Set the auto draft prevention function to enable/disable.
22
Manual setting mode
– Installer setting – RC settings – Indoor unit settings
Sensor settings
Main
Set the sensing sensor low mode function, which controls power consumption by gradually changing the internal set temperature after it detects that no people are present, or set the sensing sensor stop mode function, which stops operation of the air conditioner after it detects that no people are present and a fixed amount of time has elapsed. After all settings are complete, press the “Send to RC” button.
23
Manual setting mode
– Installer setting – RC settings – Indoor unit settings
X Sensing sensor low mode Set the sensing sensor low mode function to enable/disable.
24
Manual setting mode
– Installer setting
– RC settings
– Indoor unit settings
X Cool/Heat
Setpoint increment or decrement Set the setpoint increase or decrease of the cool/heat temperature. Increment or Decrement time Set the number of minutes after which the sensing sensor low mode function will begin if no people are detected and the air conditioner is in Cool/Heat mode. Setpoint high or low limit Set limits on the correction value (a setpoint high limit for cool and a setpoint low limit for heat).
X Sensing sensor stop mode Set the sensing sensor stop mode function to enable/disable.
25
Manual setting mode
– Installer setting – RC settings – Indoor unit settings
X Unoccupied stop time Set the number of hours after which the sensing sensor stop mode function will turn off the indoor unit if no people are detected.
26
Manual setting mode
– Installer setting – RC settings – RC settings
Setpoint configuration
Main
Setpoint mode and differential can be set when changeover is available. After all settings are complete, press the “Send to RC” button.
27
Manual setting mode
– Installer setting
– RC settings
– RC settings
X Setpoint mode Set the setpoint mode. · Single The cool setpoint and heat setpoint will be made the same, and the room temperature will be kept close to this setpoint. · Dual The cool setpoint and heat setpoint will be made different, and the room temperature will be kept between the cool or heat setpoints.
28
Manual setting mode
– Installer setting – RC settings – RC settings
· None Set the cool temperature and heat temperature so that they do not restrict each other. When set to None, automatic cooling/heating changeover (Changeover) is unavailable.
X Setpoint minimum differential Set the setpoint minimum differential between the cool and heat setpoints.
29
Manual setting mode
– Installer setting – RC settings – RC settings
Setpoint range limitation
Main
Limit the range of setpoints which can be set from the remote controller. After all settings are complete, press the “Send to RC” button.
30
Manual setting mode
– Installer setting
– RC settings
– RC settings
X Cool setpoint range Set the cool setpoint range.
* The displayed upper and lower limit values are values from the connected MAIN indoor unit.
X Heat setpoint range Set the heat setpoint range.
* The displayed upper and lower limit values are values from the connected MAIN indoor unit.
31
Manual setting mode
– Installer setting – RC settings – RC settings
Setback
Main
To prevent the room temperature from becoming extremely high or low while the air conditioner operation is turned off, if the room temperature exceeds the setback setpoint or falls below it, operation is set to start automatically. After all settings are complete, press the “Send to RC” button.
example: setpoint range: 10 – 27°C heat/cool recovery differential: 1°C therefore heating setback temperature: 10°C1°C=9°C and cooling setback temperature: 27°C+1°C=28°C
heating setback temperature cooling setback temperature
(10°C1°C=9°C)
(27°C+1°C=28°C)
9
28
example setpoint range
5 10
27 35
available setpoint range (5 – 35°C)
0 5 10 15 20 25 30 35 40
°C
32
Manual setting mode
– Installer setting – RC settings – RC settings
X Setback Set the setback function to enable/ disable.
33
Manual setting mode
– Installer setting – RC settings – RC settings
X Cool setback Set the cool setback to enable/ disable.
X Cool setback setpoint Set the cool setback setpoint.
X Cool recovery differential Set the cool recovery differential.
X Heat setback Set the heat setback to enable/ disable.
X Heat setback setpoint Set the heat setback setpoint.
X Heat recovery differential Set the heat recovery differential.
34
Manual setting mode
– Installer setting – RC settings – RC settings
Function lock
Main Sub
Partially limit the operation from the remote controller. After all settings are complete, press the “Send to RC” button.
35
Manual setting mode
– Installer setting – RC settings – RC settings
36
Manual setting mode
– Installer setting
– RC settings
– RC settings
X RC button Set the remote controller button operation to enable/disable.
X User menu item
Operation mode Set the ability to change operation modes to enable/disable. Fan speed Set the ability to change Fan speed to enable/disable. Airflow direction Set the ability to change airflow direction to enable/disable. Ventilation rate Set the ability to change ventilation rate to enable/disable.
37
Manual setting mode
– Installer setting
– RC settings
– RC settings
Ventilation mode Set the ability to change ventilation rate mode to enable/disable. Change setpoint Set the ability to change the setpoint to enable/disable. X Operation mode
Auto Set operation mode Auto to enable/ disable. Cool Set operation mode Cool to enable/ disable. Heat Set operation mode Heat to enable/ disable.
38
Manual setting mode
– Installer setting
– RC settings
– RC settings
Fan Set operation mode Fan to enable/ disable. Dry Set operation mode Dry to enable/ disable. Ventilation/Purify Set operation mode Ventilation/Purify to enable/disable. Dry Cool Set operation mode Dry Cool to enable/disable. Dry Level Setting Set operation mode Dry Level Setting to enable/disable.
39
Manual setting mode
– Installer setting – RC settings – RC settings
External input interlock
Main
Set the external input linkage function to automatically start/stop the indoor unit if it is determined that a card key has been inserted (for example, at a hotel). After all settings are complete, press the “Send to RC” button.
40
Manual setting mode
– Installer setting – RC settings – RC settings
X Timer settings Card key delay timer Set the time interval after which the indoor unit will automatically stop once a card key has been removed.
41
Manual setting mode
– Installer setting
– RC settings
– RC settings
Card key reset timer Set the time interval after which it will be reset to the value set in Reset settings once a card key has been removed.
X Reset setting
Reset on/off Set which indoor unit state to use (operating or stopped) at time of reset. Reset mode Set which operation mode to use at time of reset. Reset cool setpoint Set what temperature to set the cool setpoint at time of reset.
42
Manual setting mode
– Installer setting – RC settings – RC settings
Reset heat setpoint Set what temperature to set the heat setpoint at time of reset.
43
Manual setting mode
– Installer setting – RC settings – RC settings
Schedule menu *BRC1H63 and above only
Main
Set the schedule function to enable/ disable. To confirm the settings, press
the “Send to RC” button.
* This function cannot be used when a group address is set for the indoor unit.
* This function cannot be used unless the clock is set on the remote controller.
44
Manual setting mode
– Installer setting – RC settings – RC settings
45
Manual setting mode
– Installer setting
– RC settings
– RC settings
X Schedule function enable/disable Enabled: Enables the schedule function and displays the buttons for pattern setting and screen transition buttons. Disabled: Disables the schedule function.
X Pattern selection Select the pattern to be used for the schedule function.
X Holiday setting Opens the holiday setting screen.
X Schedule setting Opens the schedule setting screen.
46
Manual setting mode
– Installer setting – RC settings – RC settings – Schedule menu
Holiday setting *BRC1H63 and above only
Main
Set each day of the week to be either a workday or holiday. To confirm the settings, press the “Send to RC” button.
47
Manual setting mode
– Installer setting – RC settings – RC settings – Schedule menu
X Day of the week enable/disable Enabled: Holiday Disabled: Workday
48
Manual setting mode
– Installer setting – RC settings – RC settings – Schedule menu
Schedule setting *BRC1H63 and above only
Main
Configure settings for a schedule.
pattern/day/number
Control settings for each can be configured individually. To confirm the
settings, press the “Send to RC” button.
* If the connected indoor unit does not have a cooling (heating) mode, the cooling (heating) temperature cannot be set. When dual setpoint is set (default), note that the heating set temperature is lower than the cooling set temperature.
49
Manual setting mode
– Installer setting – RC settings – RC settings – Schedule menu
50
Manual setting mode
– Installer setting
– RC settings
– RC settings
– Schedule menu
X Pattern Patterns 1 to 3 can represent summer, winter, and intermediate periods. Switches to the pattern selected.
X Day of the week Select the day of the week to configure. Switches to the selected day of the week.
X Number 5 variations (No. 1 to No. 5) can be configured. Switches to the selected number.
51
Manual setting mode
– Installer setting
– RC settings
– RC settings
– Schedule menu
X Holiday If the day of the week is set to enable (holiday), the holiday settings are displayed.
X Schedule setting Enable/disable schedule setting.
X Execution time Set the time.
X Start and stop Set the operation to be performed at the time set. If set to ON, the unit will operate normally. If set to OFF, the setback function is enabled.
52
Manual setting mode
– Installer setting – RC settings – RC settings – Schedule menu
X Cooling set temperature Set cooling mode operation settings. If enabled, a cooling temperature range can be set.
X Heating set temperature Set heating mode operation settings. If enabled, a heating temperature range can be set.
53
Manual setting mode
– Installer setting – RC settings – RC settings
Hotel mode *BRC1H63 and above only
Main Sub
Set the hotel mode function to enable/ disable. Changing the hotel mode setting changes the remote controller screen display. For details on the screen display, refer to the installation manual included with the remote controller. To confirm the settings, press the “Send to RC” button.
54
Manual setting mode
– Installer setting – RC settings – RC settings
X Hotel mode enable/disable Enabled: Hotel mode is enabled. Disabled: Hotel mode is disabled.
55
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
Temperature sensor *BRC1H63 and above only Main
Set up the Temperature sensor interlocking.
Set the upper and lower temperature limits, and set the control (start/stop) when the upper limit is reached/when the lower limit is reached. Also set the duration time.
* It is possible to disable the entire Temperature interlocking control or only a part of it (e.g. upper limit control).
56
Manual setting mode
– Installer setting
– RC settings
– Sensor interlocking control
* Sensor interlocking controls can be set in priority order, and if two or more Sensor interlocking controls are set to have contrary controls, the control with the higher priority is executed. (Priority: 1>2>3>4) Depending on sensor priority, intended control may not be achieved, so please be careful when configuring settings with several sensors.
57
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
X Interlocking control Set the interlocking control function to enable/disable.
X Sensor priority Set the priority order number for the control.
X Upper and lower limit settings Set the lower and upper limits of the setting range.
X Upper limit control Set the upper limit control to enable/ disable.
X Start and stop Set the control response at the upper limit value.
58
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
X Duration Set the duration of the setting.
X Lower limit control Set the lower limit control to enable/ disable.
X Start and stop Set the control response at the lower limit value.
X Duration Set the duration of the setting.
59
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
CO2 sensor *BRC1H63 and above only
Main
Set up the CO2 sensor interlocking.
Set the upper and lower limits of CO2 concentration and set the ventilation volume when the upper limit is reached/ when the lower limit is reached/when the intermediate value is reached. For higher and lower limit control, also set the duration time.
* It is possible to disable the entire CO2 interlocking control or only a part of it (e.g. upper limit control).
60
Manual setting mode
– Installer setting
– RC settings
– Sensor interlocking control
* Sensor interlocking controls can be set in priority order, and if two or more Sensor interlocking controls are set to have contrary controls, the control with the higher priority is executed. (Priority: 1>2>3>4) Depending on sensor priority, intended control may not be achieved, so please be careful when configuring settings with several sensors.
61
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
X Interlocking control Set the interlocking control function to enable/disable.
X Sensor priority Set the priority order number for the control.
X Upper and lower limit settings Set the lower and upper limits of the setting range.
X Upper limit control Set the upper limit control to enable/ disable.
X Ventilation volume Set the ventilation control response.
62
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
X Duration Set the duration of the setting.
X Intermediate value control Set the intermediate value control to enable/disable.
X Ventilation volume Set the ventilation control response.
63
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
X Lower limit control Set the lower limit control to enable/ disable.
X Ventilation volume Set the ventilation control response.
X Duration Set the duration of the setting.
64
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
Door/Window sensor *BRC1H63 and above only Main
Set up the Door/Window sensor interlocking.
Set up the control (start/stop) when the door (window) is open/when the door (window) is closed. Also set the duration time.
* It is possible to disable the entire Door/ Window sensor interlocking control or only a part of it (e.g. control when doors/windows are open).
65
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
* Sensor interlocking controls can be set in priority order, and if two or more Sensor interlocking controls are set to have contrary controls, the control with the higher priority is executed. (Priority: 1>2>3>4) Depending on sensor priority, intended control may not be achieved, so please be careful when configuring settings with several sensors.
X Interlocking control Set the interlocking control function to enable/disable.
66
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
X Sensor priority Set the priority order number for the control.
X Control in opening Set the control in opening to enable/ disable.
X Start and stop Set the control response at the upper limit value.
X Duration Set the duration of the setting.
67
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
X Control in closing Set the control in closing to enable/ disable.
X Start and stop Set the control response at the lower limit value.
X Duration Set the duration of the setting.
68
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
Motion sensor *BRC1H63 and above only
Main
Set up the Motion sensor interlocking control.
Set up the control (start/stop) when a person is in the room/when a person is not in the room. Also set the duration time.
* It is possible to disable the entire Motion sensor interlocking control or only a part of it (e.g. control when a person is in the room).
69
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
* Sensor interlocking controls can be set in priority order, and if two or more sensor interlocking controls are set to have contrary controls, the control with the higher priority is executed. (Priority: 1>2>3>4) Depending on sensor priority, intended control may not be achieved, so please be careful when configuring settings with several sensors.
X Interlocking control Set the interlocking control function to enable/disable.
70
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
X Sensor priority Set the priority order number for the control.
X Control in detecting Set the Control in detecting to enable/disable.
X Start and stop Set the control response at the upper limit value.
X Duration Set the duration of the setting.
71
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
X Control in no detecting Set the Control in no detecting to enable/disable.
X Start and stop Set the control response at the lower limit value.
X Duration Set the duration of the setting.
72
Manual setting mode
– Installer setting
– RC settings
– Sensor interlocking control
NOTICE About priority settings when using multiple sensors
Interlocking control is performed starting from the sensor with the highest priority. When interlocking control is being performed by a sensor with a higher priority, the sensor with a lower priority will not make interlocking control decisions. (Even if operation conditions for interlocking control are satisfied, interlocking control is not performed.)
73
Manual setting mode
– Installer setting
– RC settings
– Sensor interlocking control
· Example of sensor interlocking settings
X Example of inappropriate settings · Door/Window sensor (Priority No. 1) OPEN (function enabled): Air conditioner OFF CLOSE (function disabled): · Motion sensor (Priority No. 2) Motion detected (function enabled): Air conditioner ON Motion not detected (function disabled): Air conditioner OFF
74
Manual setting mode
– Installer setting
– RC settings
– Sensor interlocking control
· CO2 sensor (Priority No. 3) Greater than 1000 ppm (function enabled): Ventilation High Less than 600 ppm (function enabled): Ventilation Low Greater than or equal to 600 ppm and less than 1000 ppm (function disabled): –
· Temperature sensor (Priority No. 4) Over 25°C (function enabled): Air conditioner ON Below 20°C (function enabled): Air conditioner OFF
75
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
Sensor priority No.1 Door/Window sensor
interlocking control
CLOSE
OPEN
Sensor priority No.2 Motion sensor
interlocking control
Case 1 Air conditioner
OFF
Motion not detected
Motion detected
Air conditioner OFF
Case 2 Air conditioner
ON
Sensor priority No.3 CO2 sensor
interlocking control
1000 ppm or less, 600 ppm or more
Less than 600 ppm More than 1000 ppm
Sensor priority No.4 Temperature sensor interlocking control
Case 4 Ventilation Low
Less than 20°C
More than 25°C
Case 6 Air conditioner
OFF
Case 5 Air conditioner
ON
Case 3 Ventilation High
76
Manual setting mode
– Installer setting
– RC settings
– Sensor interlocking control
Since the Motion sensor is always set to be enabled, the CO2 sensor and Temperature sensor will not operate concurrently.
X Example of appropriate settings · Door/Window sensor (Priority No. 1) OPEN (function enabled): Air conditioner OFF CLOSE (function disabled): · Motion sensor (Priority No. 2) Motion detected (function enabled): Air conditioner ON Motion not detected (function disabled): –
77
Manual setting mode
– Installer setting
– RC settings
– Sensor interlocking control
· CO2 sensor (Priority No. 3) Greater than 1000 ppm (function enabled): Ventilation High Less than 600 ppm (function enabled): Ventilation Low Greater than or equal to 600 ppm and less than 1000 ppm (function disabled): –
· Temperature sensor (Priority No. 4) Over 25°C (function enabled): Air conditioner ON Below 20°C (function enabled): Air conditioner OFF
78
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
Sensor priority No.1 Door/Window sensor
interlocking control
CLOSE
OPEN
Sensor priority No.2 Motion sensor
interlocking control
Case 1 Air conditioner
OFF
Motion not detected
Motion detected
Sensor priority No.3 CO2 sensor
interlocking control
Case 2 Air conditioner
ON
1000 ppm or less, 600 ppm or more
Less than 600 ppm More than 1000 ppm
Sensor priority No.4 Temperature sensor interlocking control
Case 4 Ventilation Low
Case 3 Ventilation High
More than 25°C
Less than 20°C
Case 6 Air conditioner
OFF
Case 5 Air conditioner
ON
79
Manual setting mode
– Installer setting
– RC settings
– Sensor interlocking control
In some cases, all sensors from No.1 to No.4 will be engaged in interlocking control concurrently.
Response Case 1
Door/Window sensor : OPEN Air conditioner OFF
Case 2
and Door/Window sensor : CLOSE
Motion sensor
: Motion detected
Air conditioner ON
Case 3
and Door/Window sensor : CLOSE
Motion sensor
: Motion not detected
CO2 sensor
: More than 1000 ppm
Ventilation High
80
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
Case 4
and Door/Window sensor : CLOSE
Motion sensor
: Motion not detected
CO2 sensor
: Less than 600 ppm
Ventilation Low
Case 5
and Door/Window sensor : CLOSE
Motion sensor
: Motion not detected
CO2 sensor
: 1000 ppm or less
600 ppm or more
Temperature sensor: More than 25°C
Air conditioner ON
81
Manual setting mode
– Installer setting – RC settings – Sensor interlocking control
Case 6
and Door/Window sensor : CLOSE
Motion sensor
: Motion not detected
CO2 sensor
: 1000 ppm or less
600 ppm or more
Temperature sensor: Less than 20°C
Air conditioner OFF
82
Manual setting mode
– Installer setting – RC settings – RC display settings
Date and time/DST
Main Sub
Set the remote controller clock and daylight saving time. After all settings are complete, press the “Send to RC” button.
* The app screen displays different items depending on the field setting (daylight saving time setting) of the remote controller. For details on how to change the daylight saving time setting, refer to the installation manual included with the remote controller.
83
Manual setting mode
– Installer setting – RC settings – RC display settings
When there is no daylight saving time setting
84
Manual setting mode
– Installer setting – RC settings – RC display settings
When there is a daylight saving time setting
85
Manual setting mode
– Installer setting
– RC settings
– RC display settings
X Automatic clock setting Set automatic clock setting to enable/ disable. Not displayed when daylight saving time is displayed, or when connected to a centralized device. Not displayed and function not available if the daylight saving time setting is able to be changed.
X Date and time Manually set the day and time.
* If automatic clock setting is set to unavailable, this setting is possible.
X Daylight saving time Set the ability to change the daylight saving time setting to enable/disable.
86
Manual setting mode
– Installer setting – RC settings – RC display settings
X DST start Set the date and time at which daylight saving time will start.
X DST end Set the date and time at which daylight saving time will finish.
87
Manual setting mode
– Installer setting – RC settings – RC display settings
Celsius/Fahrenheit
Main Sub
Set the unit type with which the temperature is displayed on the app screen. After all settings are complete, press the “Send to RC” button.
88
Manual setting mode
– Installer setting – RC settings – RC display settings
X Celsius/Fahrenheit Set the Celsius/Fahrenheit display.
89
Manual setting mode
– Installer setting – RC settings – RC display settings
Brightness control
Main Sub
Set the brightness level of the status indicator and remote controller LCD backlight. When you return to the previous screen, the settings are sent to the remote controller.
90
Manual setting mode
– Installer setting – RC settings – RC display settings
X Back light brightness Set the remote controller LCD brightness level.
91
Manual setting mode
– Installer setting – RC settings – RC display settings
X Status indicator brightness (Back light on) Set the status indicator brightness level when the backlight is ON.
X Status indicator brightness (Back light off) Set the status indicator brightness level when the backlight is OFF.
92
Manual setting mode
– Service menu
X Error code reset After resolving the error, tap “Reset” to clear it from the error history display of the remote controller.
93
Manual setting mode
– Service menu
– Error history
Main
Display the error history saved in the remote controller and indoor unit. By selecting from the menu in the upper portion of the screen, you can switch between displaying the error history of the remote controller and indoor unit. By specifying the unit number of an indoor unit, you can confirm the error history of each indoor unit.
* For indoor unit error history, a maximum of 5 issues are displayed.
* For remote controller error history, a maximum of 10 issues are displayed.
94
Manual setting mode
– Service menu – Error history
95
Manual setting mode
– Service menu – Error history
96
Manual setting mode
– RC security
– Owner password
Main Sub
Set the password for the owner/ administrator. It is possible to make password entry required if the user wants to change functions that can be changed with owner/administrator authority.
[When password input is unavailable] If the toggle switch is available, the password setting screen will be displayed, so enter a 4 digit password.* Be sure to make a memo of your password and keep it in a safe place. Please understand that, in case you forget your password, there is a possibility that we may not be able to help you.
97
Manual setting mode
– RC security
– Owner password
Main Sub
98
Manual setting mode
– RC security
– Owner password
Main Sub
[When password input is available] If “Change Password” is tapped, the password setting screen will be displayed, so enter a 4 digit password.99
Manual setting mode
– RC security
– Owner password
Main Sub
* After changing your password, be sure to make a memo of your new password and keep it in a safe place. Please understand that, in case you forget your password, there is a possibility that we may not be able to help you.
100
Manual setting mode
– RC security
– Owner password
Main Sub
101
Work history
Setting log confirmation procedure
You can confirm the setting log of the remote controller on which setting has been done. Date information is also displayed.
* A maximum of 50 historical data items are stored.
* It is not possible to re-edit historical data. * Items other than those upon which setting
had been carried out cannot be viewed.
102
Work history
103
App menu
Application version
You can confirm the software version of this app.
104
App menu
Terms of use
You can confirm the terms of use of this app.
105
App menu
Open source licenses
You can confirm the open-source software license which this app uses.
106
App menu
Application language
You can change the language displayed by this app.
107
App menu
Application time
You can change whether this app displays time in 24-hour or 12-hour style.
108
App menu
User mode
You can change the user mode to Administrator or Installer. The app will restart when a change is made.
109
Troubleshooting
The app cannot be found
· Is the Android device you are using equipped with Bluetooth and a rearfacing camera? X Unequipped Android devices will not display the app in the Google Play store list of apps.
· Is the OS version of the Android device you are using correct? X If using an Android device with an OS older than 12.0, the app may not be displayed in the Google Play store list of apps.
110
Troubleshooting
Communication with the remote controller is not possible
· Are you carrying out settings in a location close to the remote controller? X Though Bluetooth low energy communication is possible even from distant locations, as a basic rule, please carry out work close to the operating remote controller.
· Are the Bluetooth function and camera function of the device set to ON? X Set the device Bluetooth function and camera function to ON.
111
Troubleshooting
· Is the Bluetooth setting screen displayed within the installer menu screen? X On the remote controller, display the Bluetooth setting screen within the installer screen.
· Is the clock on the device correct? X Set the clock on the device correctly to the current time.
112
Troubleshooting
· Is the Bluetooth prohibition setting in the remote controller set to “Allow”? X Set to “Allow” in the Bluetooth prohibition setting area of the remote controller field setting menu.
· Are you trying to establish a Bluetooth connection without using the app? X Even if you establish a connection from the smartphone setting screen, without using the app, the app will not have a connection.
113
Troubleshooting
· Is the device you are using charged? X Please charge it. If the battery power is insufficient, there is a possibility that communication cannot be carried out well.
· Connection to the remote controller was possible before, but now connection is not possible. X Unregister the device from the Bluetooth device list in the smartphone’s settings.
114
Troubleshooting
Zigbee icon does not appear on the remote controller screen
· Has interlocking been configured correctly? X Be sure to not only perform sensor registration but to also configure interlocking for the registered sensor.
· Are you displaying the remote controller information screen? X The Zigbee icon displays on the remote controller information screen. For details, refer to the installation manual included with the remote controller.
115
Troubleshooting
· Are Bluetooth connections with the DAIKIN APP disconnected? X The Zigbee icon will not be displayed while there is a Bluetooth connection, so please disconnect Bluetooth.
116
Troubleshooting
Zigbee icon is blinking
· Is the Zigbee sensor battery depleted? X Please replace the battery. Please refer to the Zigbee sensor manual for instructions on replacement.
· Has the Zigbee sensor been installed in a location where its signals would be obstructed? X Check for obstructions and the positioning of the Zigbee sensor.
· Are you using any device that could interfere with the signal of the Zigbee sensor? X Check for the presence of such devices and their positioning.
117
Troubleshooting
· Is the Zigbee sensor positioned far from the remote controller unit? X Position within approx. 10 m with no obstructions.
· Did you turn off the remote controller just before? X The Zigbee icon may blink for a while after the power supply of the remote controller is restored. The following operations on the registered sensor may resolve the problem.
· Temperature/Humidity sensor or CO2 sensor: Pressing the button on the main unit.
· Door/Window sensor: Opening and closing the door, window, etc., on which the sensor is installed.
· Motion sensor: Holding your hand in front of the sensor.
118
Troubleshooting
Air conditioner is not interlocking
· Has interlocking been configured correctly? X Configure interlocking settings correctly. For details on the interlocking settings for each Zigbee sensor, refer to the respective sections “Temperature sensor”, “CO2 sensor”, “Door/ Window sensor” and “Motion sensor” in this manual.
· Did the operating state of the air conditioner change just before? X When the operation of the air conditioner is changed, it can take up to 30 minutes for interlocking control to start working.
119
Troubleshooting
· Has interlocking been set for multiple sensors? X When setting up interlocking control with multiple Zigbee sensors, interlocking control may not function as intended depending on control response and priority settings. Please check interlocking control settings. For details, refer to “NOTICE (About priority settings when using multiple sensors)” in “Sensor interlocking control”.
120
Troubleshooting
The sensor value is displayed as “-” on the remote controller screen
· Have sensor interlocking settings been configured correctly? X Just registering the sensor will not change the sensor value. Be sure to set up sensor interlocking as well.
· Did you turn off the remote controller just before? X Communication with the Zigbee sensor may fail for a while after the power supply of the remote controller is restored. Pressing the button on the body of the registered Temperature/ Humidity sensor or CO2 sensor may restore the display.
121
About display messages
App screen (dialog displayed when writing to the remote controller)
Contents X Device error
Error code
Message
Correction method
The Bluetooth function of the device is OFF
A-0001
The Bluetooth
From the setting
function of the device screen of the device,
is unavailable.
please make the
Bluetooth function
available.
The app is prohibited from giving its location information (Android only)
A-0002
To use this app, access to location information needs to be granted.
Please grant access to location information from the app information.
This device does not A-0004 This device does not Please use a
support Bluetooth
support Bluetooth. recommended device.
This device does
A-0005
not support camera
usage.
X Communication error
This device does not support camera usage.
Please use a recommended device.
Communication timed out
B-0001
Communication timed Move close to the
out.
remote controller
and perform settings
again.
The length of the frame is not within range
B-0002 Communication failed.
Move close to the remote controller and perform settings again.
A nonexistent command was received
B-0003 Communication failed.
Move close to the remote controller and perform settings again.
Inconsistent frame number
B-0004 Communication failed.
Move close to the remote controller and perform settings again.
Cannot receive due to communication volume exceeding the allotted memory area
B-0005
Communication failed.
Move close to the remote controller and perform settings again.
Pairing was interrupted
B-0006
Communication with the remote controller was interrupted.
Make the advertisement function on the remote controller available, perform pairing again, and then perform settings.
122
About display messages
Contents
Error code
Message
Correction method
There was a failure at B-0007 Communication
CRC check
failed.
Move close to the remote controller and perform settings again.
Received data is missing
B-0008 Reception failed.
Move close to the remote controller and perform settings again.
Connected to a nonsupported device
B-0009
It is a non-supported device.
This app can only connect to the Daikin Industries, Ltd. “BRC1H6” wired remote controller series.
The amount of
B-0010 The amount of data is
schedule data is
in error.
—
excessive
An error occurred in B-0011 Communication
part of the header
failed.
This app can only connect to the Daikin Industries, Ltd. “BRC1H6” wired remote controller series.
Processing sequence B-0012 Communication
error
failed.
—
X Setting failure
There was a setting failure due to an error on the device side
C-0001
Some kind of error Move close to the
occurred between the remote controller
remote controller and and perform settings
the indoor unit.
again.
If the same message is displayed, confirm the contents of the setting.
123
About display messages
Contents
Error code
Message
Correction method
Setting failed
C-0002 Contains a value that Confirm the contents
because the batch
cannot be set. Check of the setting.
sending function sent
the settings for the
a value that cannot
following functions.
be set on the device
· Field setting
side.
· Setpoint range
limitation
Enumerates functions that tried to set values which cannot be set, such as above.
1 If this app is not updated to the latest version, this app cannot be used. Also, if the app is being used in an environment where internet connection is not possible and the app has been started more than 31 times since the last version check, the app cannot be used until a version check is performed again.
2 Though Bluetooth low energy communication is possible even from distant locations, as a basic rule, please carry out work close to the operating remote controller.
124
About trademarks and copyright
· “QR Code” is a trademark or registered trademark of DENSO WAVE INCORPORATED.
· “iOS” and “Apple Store” are trademarks or registered trademarks of Apple Inc.
· “Android” and “Google Play Store” are trademarks or registered trademarks of Google Inc.
· The Bluetooth® and ZigbeeTM word mark and logos are registered trademarks owned by the Bluetooth SIG, Inc and Zigbee Alliance, respectively, and the use of such marks by Daikin Industries LTD. is under license. Other trademarks and trade names are those of their respective owners.
· The contents of this manual are subject to change without prior notice.
125
About trademarks and copyright
· Other company names, product names, etc. noted here are trademarks or registered trademarks of other companies, or trademarks of this company. It should be noted that ® and TM marks are not specified in the text.
EM19A039G (2507) HT
Documents / Resources
![]() |
DAIKIN BRC1H Series Wired Remote Controller [pdf] User Guide BRC1H Series Wired Remote Controller, BRC1H Series, Wired Remote Controller, Remote Controller |