Danfoss 034L0097

Brugsanvisning til Danfoss KVR15 trykregulator

Model: 034L0097

1. Introduktion

This manual provides essential information for the safe and efficient installation, operation, and maintenance of the Danfoss KVR15 Pressure Regulator. The KVR15 is designed to maintain a constant evaporating pressure in refrigeration and air conditioning systems. It features a 5/8 inch ODF connection and an access port for pressure measurement.

Læs venligst denne manual grundigt, inden du installerer eller bruger enheden. Gem denne manual til senere brug.

2. Sikkerhedsoplysninger

WARNING: Improper installation, operation, or maintenance can result in serious injury or equipment damage.

3. Pakkens indhold

Kontroller, at alle komponenter er til stede og ubeskadigede ved udpakning:

Danfoss KVR15 Pressure Regulator with 5/8 inch ODF connections and an access port

Image: Danfoss KVR15 Pressure Regulator. This image shows the compact design of the regulator, highlighting its 5/8 inch ODF connections on both ends and a small access port located on the side for pressure monitoring.

4. Opsætning og installation

Follow these steps for proper installation of the KVR15 Pressure Regulator:

  1. Systemforberedelse: Ensure the refrigeration system is depressurized and isolated before beginning installation.
  2. Beliggenhed: Install the regulator in the suction line, upstream of the compressor, and preferably in a horizontal pipe run. Ensure there is sufficient space for service and adjustment.
  3. Forbindelse: The KVR15 features 5/8 inch ODF (Outside Diameter Flare) connections. Use appropriate brazing techniques for copper tubing. Ensure the regulator is clean and free of debris before brazing. Protect the valve body from excessive heat during brazing by wrapping it with a wet cloth or using a heat sink compound.
  4. Strømningsretning: Observe the arrow on the regulator body, which indicates the correct flow direction. Install the regulator so that the refrigerant flows in the direction of the arrow.
  5. Adgangsport: The access port allows for pressure measurement. Ensure the cap is securely tightened after use to prevent leaks.
  6. Lækagetest: After installation, perform a thorough leak test on all connections using an appropriate leak detection method.
  7. Evakuering: Evacuate the system to the required vacuum level before charging with refrigerant.

Anbefalede værktøjer: Brazing torch, nitrogen for purging, leak detector, vacuum pump, manifold gauge set, pipe cutters, deburring tool, wet rags or heat sink compound.

5. Betjeningsvejledning

The KVR15 regulator is designed to maintain a constant evaporating pressure. Adjustment is typically performed during system commissioning.

  1. Indledende indstilling: The regulator is factory set to a nominal pressure. For specific system requirements, adjustment may be necessary.
  2. Justering af tryk:
    • Remove the protective cap from the adjustment spindle.
    • Turn the adjustment spindle clockwise to increase the evaporating pressure.
    • Turn the adjustment spindle counter-clockwise to decrease the evaporating pressure.
    • Use a pressure gauge connected to the access port or elsewhere in the suction line to monitor the pressure while adjusting.
    • Make small adjustments and allow the system to stabilize before making further changes.
    • Once the desired pressure is achieved, replace and tighten the protective cap to secure the setting and prevent leaks.
  3. Access Port Usage: The access port allows for temporary connection of a pressure gauge to verify the regulated pressure. Always ensure the port cap is securely tightened when not in use.

6. Vedligeholdelse

The Danfoss KVR15 Pressure Regulator is designed for long-term, reliable operation with minimal maintenance. However, periodic checks are recommended.

Note: Internal components of the KVR15 are not user-serviceable. If the regulator malfunctions, it should be replaced by a qualified technician.

7. Fejlfinding

This section provides solutions to common issues that may arise with the KVR15 Pressure Regulator.

ProblemMulig årsagLøsning
Regulated pressure is too high/low.Incorrect adjustment setting.Adjust the regulator setting as described in the "Operating Instructions" section.
Pressure fluctuates significantly.System instability; debris in regulator; incorrect sizing.Check for system issues (e.g., TXV operation). If debris is suspected, the regulator may need replacement. Verify regulator sizing for the application.
Refrigerant leak at connections.Improper brazing; loose access port cap.Re-braze connections if necessary. Ensure access port cap is securely tightened.
No pressure regulation.Internal failure; completely clogged.The regulator may need to be replaced. Consult a qualified technician.

If troubleshooting steps do not resolve the issue, contact a qualified HVAC/R technician or Danfoss technical support.

8. Specifikationer

FeatureDetalje
MærkeDanfoss
Modelnummer034L0097
TypeEvaporating Pressure Regulator (KVR15)
Tilslutningsstørrelse5/8 inch ODF (Outside Diameter Flare)
Målesystemtomme
FunktionerAdgangsport
FabrikantDanfoss
ASINB0085POK2G
Dato først tilgængelig27. december 2017

9. Garantioplysninger

Danfoss products are manufactured to high-quality standards. This product is covered by Danfoss's standard manufacturer's warranty. Specific warranty terms and conditions, including duration and coverage details, can be found on the official Danfoss website or by contacting Danfoss customer service. Please retain your proof of purchase for warranty claims.

Note: The warranty may be voided by improper installation, unauthorized modifications, or use outside of specified operating conditions.

10. Kundesupport

For technical assistance, spare parts, or further information regarding the Danfoss KVR15 Pressure Regulator, please visit the official Danfoss webwebstedet eller kontakt deres kundesupportafdeling.

Danfoss-officielle Webwebsted: www.danfoss.com

When contacting support, please have your product model number (034L0097) and serial number (if applicable) ready.

Relaterede dokumenter - 034L0097

Preview Danfoss ERC 214 Digital Regulator Installationsvejledning
Omfattende installationsvejledning til Danfoss ERC 214 digital regulator med detaljerede oplysninger om dens funktioner, brugergrænseflade, hurtigstartkonfiguration, grundlæggende funktioner, tekniske data og parameterindstillinger til køle- og afrimningsapplikationer.
Preview Danfoss RT Series Pressure Switch Installationsvejledning
Denne vejledning indeholder installationsvejledning til Danfoss RT-serien af ​​pressostater, inklusive modellerne RT 6W, RT 6B, RT 6S, RT 6AW, RT 6AB, RT 6AS, RT 30AW, RT 30AB og RT 30AS. Den dækker produktfunktioner, tekniske specifikationer, monteringsprocedurer, elektriske tilslutninger og justeringer, med godkendelser fra EN 12263 og CE-mærkning.
Preview Danfoss trykafbryder KPI 34, 35, 36, 38 installationsvejledning
Installationsvejledning til Danfoss KPI-serien af ​​pressostater (KPI 34, 35, 36, 38), der beskriver specifikationer, temperaturgrænser, trykområder, differensindstillinger, elektriske klassificeringer og ledningsføringsinstruktioner.
Preview Installationsvejledning til Danfoss MP 54, MP 55, MP 55A differenstrykafbryder
Installationsvejledning til Danfoss MP 54, MP 55 og MP 55A differenstrykafbrydere, med detaljer om kølemiddelkompatibilitet, tekniske specifikationer og installationsprocedurer.
Preview Danfoss ERC 213 Electronic Refrigeration Control Installationsvejledning
Installationsvejledning til Danfoss ERC 213 elektronisk kølestyring, med detaljer om dens tekniske højdepunkter, brugergrænseflade, dimensioner, elektriske tilslutninger og parameterindstillinger til kommercielle køleapplikationer.
Preview Danfoss HFI Float Valve (High Pressure) - Installation and Maintenance Guide
Comprehensive guide for installing and maintaining the Danfoss HFI Float Valve (High Pressure). Covers refrigerant compatibility, temperature and pressure specifications, detailed installation steps including welding and assembly, tightening procedures, and maintenance tasks like purging and float assembly replacement. Includes safety notes and technical specifications.