SM040KAMFA 3 Phase Modular Smart
SCALABLE UPS TO GUARANTEE
ULTIMATE POWER PROTECTION
SM020KAMFA/SM040KAMFA MODULAR UPS (3-PHASE) SERIES
The 3-Phase Modular UPS with N+X redundancy design and hot-swappable modularity for mission-critical applications
Designed for server room and data center applications, the Modular UPS (3-Phase) Series adopts double-conversion topology to provide seamless Pure Sine Wave output. The modular UPSs support vertical addition of power modules, and horizontal expansion by paralleling multiple systems to achieve even higher capacity, allowing users to customize base on their business needs. The N+1 redundancy design and replaceable modularity enhances the system availability and avoids the risk of single point of failure.
SERIES FEATURES
- Three-phase Design
- Online (Double Conversion) UPS Topology
- ECO Mode
- High Density Design
- Vertical Scalability
- Flexible Installation Design
- Color LCD with Touch Panel
- UPS Parallel Expansion
- Dual Inputs
-
Generator Compatible
-
Pure Sine Wave Output
-
Overload Protection
-
Maintenance Bypass Switch
-
Smart Battery Management (SBM)
-
Emergency Power Off (EPO) Port
-
SNMP/HTTP Remote Management Capability
-
PowerPanel Management Software
PRODUCT CALLOUTS
- Emergency Power OFF (EPO) Button
- LED Status Indicator
- LCD Display Panel
- Function Buttons
- Manual Bypass Breaker
- RS232
- RS485
- SNMP/HTTP Network Slot
- Parallel Board Slot
- Dry Contact
TECHNICAL SPECIFICATIONS
Model Name | SM020KAMFA |
SM040KAMFA |
General | ||
Phase | Three Phase | |
Form Factor | Modular | |
Energy Saving Technology | Online ECO Mode Efficiency > 97.5% | |
Hot Swappable Bypass Module | Yes | |
Normal Mode Efficiency (%) | 93% | |
Battery Mode Efficiency (%) | 92.5% | |
Parallel Expansion (Max. Units) | 2 | |
Redundancy Design | Yes | |
Input | ||
Dual Power Inputs | Yes | |
Backfeed Protection | Yes | |
Default Input Voltage Range (Bypass) | -20% ~ 15% | |
Overload Protection (Bypass) | 110~130% Load for 5 min, 130~150% Load for 1 min, >150% Load for 300ms | |
Rated Input Current (Bypass) | 55.6A (208V) | 111A (208V) |
Default Frequency Tolerance (Bypass) | ± 5% | ± 10% |
Configurable Frequency Tolerance (Bypass) | ± 1 %, ± 3 %, ± 5 % | ± 2.5 %, ± 5 %, ± 10 %, ± 20 % |
Bypass to Inverter Switch Time (ms) | ≤1 | |
Current Rating of Neutral Cable (Bypass) (A) | 1.7 x Input Rated Current | |
Input Connector | L1, L2, L3, N, G | |
Input Frequency (Hz) | 50, 60 | |
Input Frequency Range (Hz) | 40 ~ 70 | |
Nominal Input Voltage (Vac) | Line to Neutral (L-N): 120, 127 Vac, Line to Line (L-L):208, 220 | |
Input Voltage Range (Vac) | Line to Line (L-L): 124.8 ~ 260 Vac | |
Synchronization Window (Nominal) (Hz) | ± 2 | |
Synchronization Window (Configurable) | ±0.5Hz ~ ±5Hz | |
THDI (%) | <4% (Full Linear Load) | |
Input Power Factor | 0.99 | |
Output | ||
Max Change Rate of Sync Frequency (Default) (Hz/sec) | 1 | |
Change Rate Range of Sync Frequency (Configurable) (Hz/sec) | 0.1~5 | |
Capacity (VA) | 20000 | 40000 |
Capacity (Watts) | 20000 | 40000 |
Neutral Current Capability (%) | 170 | |
Non-Linear Load Capability (%) | 100 | |
Output Connector | L1, L2, L3, N, G | |
Rated Output Voltage (Vac) | Line to Neutral (L-N):120, 127 Vac, Line to Line (L-L):208, 220 | |
Output Voltage Range (Vac) | ± 5% | |
Output Frequency (Hz ± %) | 50, 60 | |
Power Factor | 1 | |
Overload Protection (Line Mode) | 110% Load for 10 min, 125% Load for 1 min, 150% Load for 30 sec, >150% Load for 200ms | |
Crest Factor | 3 : 1 | |
Harmonic Distortion (Linear Load) | THD<1.5% | |
Harmonic Distortion (Non-linear Load) | THD<6% | |
Short Circuit Protection | 300% 200ms | |
Synchronization Window (Nominal) (Hz) | ± 2 | |
Synchronization Window (Configurable) | ±1Hz ~ ±5Hz | |
Battery | ||
Compatible Battery Types | VRLA, AGM, Gel | |
Charger Voltage Tolerance (%) | ≤ 1 % | |
Recharge Power (%) | Default 10 % (Selectable from 1~20 % x UPS Capacity) | |
Ripple Current | ≤5% C10 | |
Battery Solution | Extended Battery | |
Battery Voltage (V) | ±120 | |
Compatible Extended Battery Module (EBM) | Yes | |
External Battery Quantity | 12V X 20pcs | |
Management & Communications | ||
LCD Panel | Yes | |
LCD Types | Color LCD, LCD Touch Panel | |
LCD Information Display | Operation Type, Power Status, Battery Status, Load Status, Fault & Warning, Other Information, Event & Log | |
LCD Setting & Control | Input & Output, Battery Setting, Language | |
LED Indicators | Power On, Line Mode, Battery Mode, Bypass Mode, Low Battery, Overload, UPS Fault | |
Serial Port | RS232 x 1 + RS485 x 1 + Dry Contact x1 | |
Emergency Power Off (EPO) Port | Yes | |
Power Management Software | PowerPanel Business (Recommended) | |
SNMP/HTTP Remote Monitoring | Yes – RMCARD205 included | |
Physical | ||
Ingress Protection | IP20 |
Physical Size – UPS Module | ||
Dimensions (WxHxD) (mm.) | 485.1 x 607.1 x 774.7 | 485.1 x 942.3 x 774.7 |
Weight (kg.) | 60.69 | 80.6 |
Shipping Dimensions | ||
Dimensions (WxHxD) (mm.) | 632 x 784.4 x 1022.4 | 632 x 1124 x 988.1 |
Weight (kg.) | 91.97 | 121.97 |
Environmental | ||
Operating Temperature (°C) | 0 ~ 40 | |
Operating Temperature Note | Battery life is halved for every 50°F (10°C) increase above 68°F (20°C) | |
Operating Relative Humidity (Non-condensing) (%) | 0 ~ 95 | |
Maximum Air Exchange (m3/min) | 3.02 | |
Operating Elevation (feet/meters) | ≤1000, Load Derated 1% per 100m from 1000m and 2000m | |
Operating Elevation Note | At <=1,000m above sea level, de-rate power by 1% per 100m between 1,000m and 3,048m | |
Storage Temperature (°C) | -20 ~ 70 | |
Storage Relative Humidity (Non-condensing) (%) | 0 ~ 95 | |
Audible Noise at 1.0M from Surface of Unit (dBA) | 56 | |
Battery Temperature Compensation | -3mV/ °C | |
Certifications | ||
Certifications* | FCC Class A, UL1778, NOM, cTUVus, ICES-003 | |
RoHS | Yes |
*Certifications may vary according to different regions. Visit www.cyberpower.com for more information.
#All specifications are subject to change without notice.
CyberPower and the CyberPower logo are trademarks of Cyber Power Systems, Inc., and/or affliates, which are registered in many countries and regions.
All other trademarks are the property of their respective owners.
Copyright © 2022 Cyber Power Systems, Inc.
All rights reserved.
www.cyberpower.com
Documents / Resources
![]() |
CyberPower SM040KAMFA 3 Phase Modular Smart [pdf] Instruction Manual SM040KAMFA 3 Phase Modular Smart, SM040KAMFA, 3 Phase Modular Smart, Modular Smart, Smart |