CyberPower-LOGO

CyberPower CP850AVRLCD Intelligent LCD UPS System

CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-PRODUCT

Product Information

  • Specifications
    • Model: K01-0000524-00

Product Usage Instructions

  • Power On
    • Press and hold the POWER button.
    • You will hear a constant tone for 1 second, followed by a short beep.
    • Release the button after the short beep.
  • Power Off
    • Press and hold the POWER button.
    • You will hear a constant tone for 1 second, followed by two short beeps.
    • Release the button after the two short beeps.
  • Display
    • Press the DISPLAY button for 3 seconds to change the current LCD screen status between Auto Off and Always On.
    • LCD Auto Off: In Line Mode, the LCD screen will automatically turn off after 1 minute of inactivity; in Battery Mode, the LCD screen is always on.
    • LCD Always On: The LCD screen will be always on.
  • Select
    • Short press the SELECT button to view information about the UPS or to scroll down the function/option menu.
  • Mute
    • Press the MUTE button for 3 seconds to enable the audible alarm (beeps once) or disable it (beeps twice).
  • Enter
    • Short press the ENTER button to confirm settings or enter into functions. (For more information about this button, please refer to the following Setup Mode section).
  • Enter into Setup Mode
    • Press both the SELECT and ENTER buttons at the same time for approximately 3 seconds to access the setup mode’s 11 functions:
  • Utility Power
    • MAX O/P Voltage
    • MIN O/P Voltage
  • Sensitivity
    • Low Battery Warning
  • Self Test
    • Audible Alarm
  • LCD Auto Off
    • Last Fault Reason
    • Back to Default Settings
    • Back to Status Display
  • Select Function
    • Short press the SELECT button to scroll down the function/option menu.
  • Confirm Option
    • When an option is selected, short press the ENTER button. After the setting has been confirmed, the LCD screen will stop flashing.
  • Frequently Asked Questions (FAQ)
    • Q: What are the options for Function Utility Power?
    • A: The options are Poor (97V~142V), Normal (100V~139V), and Good (103V~136V).
    • Q: How do I enter Self Test mode?
    • A: In Line Mode, select YES for Self Test (Battery Test) in the Audible Alarm function.
    • Q: What does Last Fault Reason display?
    • A: Last Fault Reason displays error codes for various faults, such as Charger fault (Over Charge), Charger fault (No Charge), Battery Fault, Output short, and Overload.
    • Q: How can I restore the UPS to factory default settings?
    • A: Select Yes for the Back to Default Settings function.

FUNCTION SETUP GUIDE

CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (1)

Function LCD Display Options Default Description
Utility Power CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (2) Poor (97V~142V)CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (3)

 

 

Normal (100V~139V)CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (4)

 

Good (103V~136V)CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (5)

 

 

 

Escape to Function MenuCyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (6)

 

 

 

 

Normal This function determines how the UPS will switch to Battery Mode.

3 different output voltage ranges can be chosen

according to the quality of the

      AC utility service in your
      location. If your utility service is not stable, you can select Poor (97V~142V). The UPS will go to Battery Mode less often to tolerate the utility power
  (CUSt)*   fluctuations.
  * Only when   If your utility service is stable,
  MIN or MAX O/P Voltage is   you can select Good
  configured.   (103V~136V). The unit will go
      to Battery Mode more often.
MAX O/P Voltage CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (7)

 

H136V ~ H142V H139V In Utility Power settings, only
      3 types of fixed voltage
  Escape to Function

Menu

  ranges can be chosen.

However, you can fine tune

  CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (8)   the MAX O/P voltage in this function.

If the utility voltage is usually

high, and the connected

      equipment can work in this
      condition, you can set the
      output voltage range higher to
      reduce the UPS from going to
      Battery Mode as often.
MIN O/P Voltage CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (9) L97V ~ L103V

Escape to Function MenuCyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (10)

L100V In Utility Power settings, only 3 types of voltage ranges can be chosen. However, you can fine tune the MIN O/P voltage in this function. If the utility voltage is usually low, and the connected equipment can work in this condition, you can set the output voltage range lower to reduce the UPS from going to AVR Mode or Battery Mode as often.
Function LCD Display Options Default Description
Sensitivity CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (11) Low          CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (3) Medium If the connected equipment can tolerate more power events (Example: unstable power often associated with stormy weather), select Low Sensitivity. The UPS will go to Battery Mode less often. If the connected equipment is more sensitive to power events, select High Sensitivity. The UPS will go to Battery Mode

more often.

  MediumCyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (4)  
  HighCyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (5)  
     
     
  Escape to Function MenuCyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (6)  
Low Battery Warning CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (12) 5~8 mins Escape to Function Menu 5 mins The audible alarm will sound when the remaining runtime is less than the value selected.
Self Test (Battery Test) CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (14) YESCyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (15) No Action In Line Mode, select YES to perform a Self Test on the battery.
  Escape toCyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (16)    
  FunctionCyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (17)    
  Menu    
Audible Alarm CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (17)

 

b.onCyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (19) b.on “b.on” is buzzer enable; “b.oFF” is buzzer disable.

If b.oFF is selected, the unit will mute all alarms except for

fault or overload condition.

  b.off    
      You can also set the audible alarm with the MUTE button mentioned before.
  Escape to Function MenuCyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (20)    
Function LCD Display Options Default Description
LCD Auto Off CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (21) L.on (Auto Off is on)CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (22) L.on “L.on” (Auto Off is on): In Line
    Mode, LCD screen will off automatically after 1 min of inactivity; in Battery Mode, LCD screen is always on.
  L.oFF (Auto Off is off)CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (23)    
      “L.oFF” (Auto Off is off): LCD

screen is always on.

  Escape to    
  Function    
  MenuCyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (24)    
Last Fault Reason CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (25)     There is no setting in this page. This page will only show the error code for last fault reason.

E01 : Charger fault (Over Charge).

E02 : Charger fault (No Charge)

E11 : Battery Fault

E21 : Output short. E22 : Over load.

Back to Default Settings CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (26) YES CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (27)Escape to Function MenuCyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (28) No Action Select Yes to restore the UPS factory default settings.
Return to Status Display CyberPower-CP850AVRLCD-Intelligent-LCD-UPS-System-FIG-1 (28)   Press the ENTER Button to leave setup mode and go back to the Status Display.

All rights reserved. Reproduction without permission is prohibited.

Documents / Resources

CyberPower CP850AVRLCD Intelligent LCD UPS System [pdf] User Guide
CP850AVRLCD, CP850AVRLCD Intelligent LCD UPS System, CP850AVRLCD, Intelligent LCD UPS System, LCD UPS System, UPS System, System

References

Leave a comment

Your email address will not be published. Required fields are marked *