CSI Controls Speed-E Connect Float Connection System Instruction Manual

CSI Controls logoSpeed-E Connect™
Control Duty Extra Large
Float Switch & Sealing Plug
Installation Instructions

Speed-E Connect Float Connection System

CSI Controls Speed E Connect Float Connection System - Figure 1U.S. Patent Numbers 9,559,455 and 9,583,867CSI Controls Speed E Connect Float Connection System - U.S. Patent Numbers

Mechanically-activated, narrow-angle, internally weighted municipal float switch designed by the global manufacturing leader. The Speed-EConnect™ float is ideal for level control in municipal sewage pumping stations. The internal switching mechanism contains unique gold crosspoint contacts, providing precision and reliable control signals up to 1 Amp.

Electrical Warnings

Failure to follow these precautions could result in serious injury or death. Do not energize the Speed-E Connect™ system if all ports on the manifold are not properly connected to a float switch and/or a sealing plug. If any of the manifold ports were left open in the tank, have come in contact with water, or the manifold cable is damaged or severed, replace the manifold immediately. Do not attempt to dry the manifold ports or repair the Speed-E Connect™ system. Keep these instructions with the warranty after installation. This product must be installed in accordance with the National Electric Code, ANSI/NFPA 70, so as to prevent moisture from entering or accumulating within boxes, conduit bodies, fittings, float housing, or cable.

CSI Controls Speed E Connect Float Connection System - Symbol 1
ELECTRICAL SHOCK HAZARD
Disconnect power before installing or servicing this product. A qualified service person must install and service this product according to applicable electrical and plumbing codes.

CSI Controls Speed E Connect Float Connection System - Symbol 2
EXPLOSION OR FIRE HAZARD
Do not use with flammable liquids. Install in accordance with ANSI/NFPA 70. Suitable for use with intrinsically safe circuit extensions as defined by UL 698A.

Items Needed

Included with Speed-E Connect™ Control Duty Extra Large Float Switch

Black Boot – Normally Open (N.O.) CSI Controls Speed E Connect Float Connection System - Black Boot
Gray Boot – Normally Closed (N.C.) CSI Controls Speed E Connect Float Connection System - Gray Boot

Not included

CSI Controls Speed E Connect Float Connection System - Not included

Sealing Plug (Ordered Separately)
Used to seal any open ports.

CSI Controls Speed E Connect Float Connection System - Sealing Plug

C Speed-E Connect™ Manifold with Multi-Conductor Cable
D Sealing Plug

Specifications

CSA Certified

125/250 VAC
Maximum Electrical
Load: 1 amp
Minimum Electrical
Load: 1 milliamp.
30 VDC
Maximum Electrical
Load: 1 amp
Minimum Electrical
Load: 1 milliamp.
5 VDC
Minimum Electrical
Load: 1 milliamp.
CABLE
18 gauge,
2 conductor SJOW
FLOAT
polypropylene
BOOT MATERIAL
Chloroprene rubber
MAXIMUM WATER DEPTH
30 feet (9 meters), 13 PSI (90kPa)
MAXIMUM TEMPERATURE
140°F (60°C)
  1. To unplug the float switch or sealing plug from the manifold, twist the outer boot and slide. Press latch and pull down connector to release.CSI Controls Speed E Connect Float Connection System - Figure 2
  2. Determine tether length for each float switch and install float switches at desired activation level.CSI Controls Speed E Connect Float Connection System - Figure 3Suspension Mounting: Suspend float 11 inches below desired activation level as shown in figure.
    Tether Mounting: Minimum 12-inch tether length.
  3. Fully insert float switch connector until it clicks. Slide the rubber boot to seat against manifold flange.
    NOTE: Record which float switches are connected to R(red), B(blue), Y(yellow), and W(white) wire color for easy panel wiring.
    HORECAROMA La Doppia Espresso Coffee Machine - Symbol 1 WARNING: DO NOT install WITHOUT float switches and/ or sealing plugs installed on ALL connections.CSI Controls Speed E Connect Float Connection System - insert float switch connectorCSI CONTROLS® THREE-YEAR LIMITED WARRANTY
    Three-Year Limited Warranty. For complete terms and conditions, please visit www.csicontrols.com.
  4. Test float switches for operation according to panel installation instructions.CSI Controls Speed E Connect Float Connection System - Test float switches for operation according

HORECAROMA La Doppia Espresso Coffee Machine - Symbol 1 WARNING: DO NOT suspend float switches directly from manifold.

CSI Controls logoTechnical support: +1 800-746-6287
techsupport@sjeinc.com
www.csicontrols.com
Instl. Instr. PN 1059243B 06/26
© 2018 SJE, Inc. All Rights Reserved.
CSI CONTROLS is a trademark of SJE, Inc.

Documents / Resources

PDF thumbnailSpeed-E Connect Float Connection System
Instruction Manual · Speed-E Connect Float Connection System, Connect Float Connection System, Float Connection System, Connection System

References

Ask a Question

Use this section to ask about setup, compatibility, troubleshooting, or anything missing from this manual.

Ask a Question

Ask about setup, compatibility, troubleshooting, or anything missing from this manual. Name and email are optional.