SINOTIMER STVP936-1-80A

User Manual: Three-Phase Adjustable Over/Under Voltage Chránič

Model: STVP936-1-80A

1. Úvod

The SINOTIMER STVP series automatic over-voltage a pod-zvtage protector is designed for three-phase 3*127V/220VAC power systems with a rated working current of 80A. This device provides essential protection for electrical equipment by instantaneously cutting off the power supply when over-voltage, pod-voltage, or over-current conditions are detected. Once the circuit voltage returns to normal, the protector automatically restores power, ensuring continuous operation and safeguarding your appliances from damage.

This protector integrates multiple protection functions including over-voltage, pod-voltage, over-current, three-phase current (voltage) imbalance, phase sequence (reverse phase), zero-break, and phase-break protection. It also features voltmeter and ammeter functions, and the ability to restore factory settings. The device offers comprehensive features, stable performance, and ease of operation.

Podrobný návod k použití ve formátu PDF je k dispozici ke stažení: Uživatelská příručka (PDF)

2. Klíčové vlastnosti

  • Voltage ochrana
  • Pod voltage ochrana
  • Nadproudová ochrana
  • Automatické obnovení
  • svtage display (separate ABC phase voltage měření)
  • Ampere display (separate ABC phase ampere measurement)
  • Třífázový ampere unbalance protection
  • Phase sequence protection (reverse phase protection)
  • Zero line break protection
  • Ochrana proti výpadku fáze
  • Fault inquiry function
  • Rotation display of voltage and current for each phase
  • Nastavitelný přetlaktage protection value and recovery value
  • Adjustable under-voltage protection value and recovery value
  • Adjustable over-current protection value and action time
  • Adjustable 3-phase ampere unbalance protection value and action time
  • Adjustable delay time after power-on
  • Adjustable fault recovery delay time
  • Factory data reset function

3. Specifikace produktu

AtributHodnota
Číslo modeluSTVP936-1-80A
Napájení3*127V/220VAC 60Hz
Jmenovitý objemtage220V
FázeTřífázové
Max. Zatěžovací proud1~80A Adjustable (default: 80A)
VoltagRozsah ochrany e121V-150V-OFF Adjustable (default: 140V)
VoltagRozsah zotavení e120V-149V (default: 135V)
Voltage Čas akce0.1~10 seconds (default: 0.2s)
Pod voltagRozsah ochrany e118V-80V-OFF Adjustable (default: 90V)
Pod voltagRozsah zotavení e118V-91V (default: 95V)
Pod voltage Čas akce0.1~10 seconds (default: 0.2s)
3-Phase Volt Unbalance Protection10%~50%~OFF (default: 20%)
3-Phase Volt Unbalance Action Time0.1~10 seconds (default: 1s)
Delay Time After Power-on2~255 seconds (default: 2s)
Fault Recovery Delay Time2~600 seconds (default: 60s)
Zobrazit modelLCD
Rozměry71.5 mm (Š) * 95.2 mm (V) * 65.7 mm (H)
Instalace35 mm DIN lišta
OsvědčeníCE, RoHS

4. Bezpečnostní informace

  • Instalaci a údržbu by měli provádět pouze kvalifikovaní elektrikáři.
  • Před jakoukoli instalací nebo elektroinstalačními pracemi se ujistěte, že je odpojeno napájení.
  • The device does not provide overload or short-circuit protection. It must be used in conjunction with appropriate external circuit breakers (e.g., C45, C65 mini circuit breakers) for comprehensive protection.
  • Před připojením napájení zkontrolujte, zda jsou všechna zapojení bezpečná a správná.
  • Do not operate the device in wet or hazardous environments.

5. Instalace

5.1 Fyzické rozměry

Dimensions of the STVP936-1-80A protector, showing width 71.5mm, height 95.2mm, and depth 65.7mm.
Obrázek 1: Rozměry produktu

5.2 Montáž

The protector is designed for 35mm DIN rail installation. Snap the device onto the DIN rail securely.

Strana view of the protector showing its compatibility with a DIN rail for mounting.
Obrázek 2: Montáž na DIN lištu

5.3 Schéma zapojení

Connect the input and output terminals as shown in the diagram below. Ensure correct phase (L1, L2, L3) and neutral (N) connections. The input terminals are located at the top, and output terminals at the bottom.

Přední view of the protector with input (N, L1, L2, L3) and output (N, L1, L2, L3) terminals clearly labeled with arrows.
Figure 3: Input/Output Terminal Labels
Detailed wiring diagram showing connections from a power switch to the voltage protector (IN terminals) and from the voltage protector (OUT terminals) to an air circuit breaker.
Obrázek 4: Obecné schéma zapojení

6. Nastavení a konfigurace

Chcete-li vstoupit do režimu nastavení, stiskněte a podržte tlačítko SOUBOR button for 3 seconds. Then, continuously press SOUBOR to cycle through the parameters. Use the a buttons to adjust the values. When "ENd" appears, press SOUBOR again to save the data and exit the setting mode.

If no operation is performed within 10 seconds after pressing SOUBOR, the device will automatically exit the setting mode, and any unsaved changes will be lost.

6.1 Parameter Settings Table

KrokObsahLCD displejDescription / Range (Default)
1Voltage ochranná hodnotaUvo 280V221V-300V-OFF (280V)
2Voltage hodnota výtěžnostiUvor 250V220V-299V (250V)
3Voltage protection action time0.2S0.1–10 s (0.2 s)
4Pod voltage ochranná hodnotaUve 160V219V-150V-OFF (160V)
5Pod voltage hodnota výtěžnostiUver 180V151V-220V (180V)
6Pod voltage protection action time0.2S0.1–10 s (0.2 s)
7Hodnota nadproudové ochrany>In 80A1-80A (80A)
8Over-current protection action time5S1–512 s (5 s)
93 fáze amp unbalance protection value>In %5%-90%-OFF (25%). Not active if current < 2A.
103 fáze amp unbalance protection action time1.0 S0.1–10 s (1 s)
11Ochrana sledu fázíON ABCON or OFF (ON)
12Doba zpoždění zapnutí2 S2–255 s (2 s)
13Fault recovery delay time60 S2–512 s (60 s)
14Fault inquiry codeE0Press ▲ to view last 5 fault records (E1-E5). >U for overvoltage, <U for undervoltage.
15KonecKonecPress SET to save and exit.

6.2 Obnovení továrního nastavení

To reset the device to factory settings, press and hold the a tlačítka současně po dobu 3 sekund.

7. Provoz

Once installed and configured, the device will continuously monitor the three-phase power supply. The LCD screen will automatically rotate to display the real-time voltage and current for each phase (L1, L2, L3).

V případě přeobjtage, pod-voltage, or over-current event, the protector will automatically trip and cut off the power supply to protect connected equipment. After the fault condition clears and the recovery delay time has passed, the device will automatically restore power.

8. Řešení problémů

8.1 Dotazování poruch

If a fault occurs, the device will display an error code (E0). You can press the button to query the last 5 fault records (E1-E5). The display will indicate:

  • ">U" for overvoltage události.
  • "<U" for undervoltage události.

8.2 Phase Sequence Error

If the LCD displays "ABC" character, it indicates a phase sequence error. To correct this, arbitrarily reverse any two of the three phase lines (L1, L2, L3) at the input.

9. Údržba

  • Udržujte zařízení čisté a bez prachu a vlhkosti.
  • Pravidelně kontrolujte těsnost kabelových spojů a známky opotřebení nebo poškození.
  • Do not attempt to repair the device yourself. Refer to qualified personnel for service.

10. Záruka a podpora

For technical support, inquiries, or warranty claims, please contact the distributor:

Distributor: XNY INTERNATIONAL LIMITED

Adresa: Room 20A, Kiu Fu Commercial Building, 300 Lockhart Road, Wanchai, Hong Kong.

tel: 0086

Fax: 0086 577 89736991

WhatsApp: 0086 1565857 3377

Wechat: sinotimer

Skype: sinotimer

Web: www.sinotimer.com

E-mail: info@sinotimer.com

Související dokumenty - STVP936-1-80A

Předview Uživatelská příručka SINOTIMER SVP719: Sv.tage Protector, měřič energie a monitor spotřeby energie
Komplexní uživatelská příručka pro SINOTIMER SVP719, která podrobně popisuje jeho funkce, jako je nastavitelný nad/pod objem.tagochrana proti přepětí, relé proti nadproudu a měřič energie ve wattech/kWh pro sledování spotřeby energie.
Předview Inteligentní přehřátí SVP-916tagNávod k obsluze proudového chrániče e Limit Current Protection Protector
Návod k obsluze inteligentního přepěťového senzoru SINOTIMER SVP-916tage, pod-voltaga nadproudová ochrana pro jednofázové systémy střídavého proudu 230 V. Podrobně popisuje vlastnosti, parametry a metody nastavení ochrany elektrických zařízení.
Předview SINOTIMER WiFi Smart Switch Instruction Manual
Comprehensive instruction manual for the SINOTIMER WiFi Smart Switch, detailing network setup via the Graffiti Smart APP, device unbinding and reset procedures, indicator light status, electricity consumption display, and configuration of overvoltage, podpaltage, and overcurrent protection settings.
Předview Sinotimer MT-S PID regulátor teploty: Vlastnosti, specifikace a návod k nastavení
Podrobné informace o inteligentním PID teplotním regulačním relé Sinotimer MT-S, včetně funkcí, technických specifikací, schémat zapojení a pokynů k nastavení PID a On-Off regulačních režimů.
Předview Návod k obsluze měřicího spínače vodicí lišty SINOTIMER DDS6619
Návod k obsluze pro měřicí spínače s vodicí lištou řady SINOTIMER DDS6619. Podrobné technické specifikace, zapojení, ovládání aplikací přes Smart Life/Tuya, návod k obsluze a bezpečnostní opatření pro inteligentní monitorování energie.
Předview SINOTIMER TM618s digitální programovatelný časovač - uživatelská příručka a specifikace
Komplexní průvodce digitálním programovatelným časovačem SINOTIMER TM618s, který zahrnuje funkce, specifikace, programování, zapojení a instalaci. Ideální pro ovládání elektrických zařízení s denními plány zapínání a vypínání.