CP electronics logoVITP7-EBDMR Vitesse Plus Ceiling Presence Detector
User GuideCP electronics VITP7-EBDMR Vitesse Plus Ceiling Presence DetectorCP electronics VITP7-EBDMR Vitesse Plus Ceiling Presence Detector - logoCP electronics VITP7-EBDMR Vitesse Plus Ceiling Presence Detector - icon 1 VITP7-EBDMR
Ceiling presence detector

VITP7-EBDMR Vitesse Plus Ceiling Presence Detector

Electric Shock Icon This device should be installed by a  qualified electrician in accordance with the latestedition of the IET wiring regulations. CP electronics VITP7-EBDMR Vitesse Plus Ceiling Presence Detector - fig 1This device is designed to be ceilingmounted.

  • Do not site the unit where direct sunlight might enter the sensor.
  • Do not site the sensor within 1m of any lighting, forced air heating or ventilation.
  • Do not fix the sensor to an unstable or vibrating surface.

INSTALLATION

Flush fixing

CP electronics VITP7-EBDMR Vitesse Plus Ceiling Presence Detector - fig 2Bend the springs up and push detector through hole in ceiling. When fully inserted the springs snap back to hold the device in place.
Surface fixing

CP electronics VITP7-EBDMR Vitesse Plus Ceiling Presence Detector - fig 3 Surface mounting box: part code DBB, sold separatelyCP electronics VITP7-EBDMR Vitesse Plus Ceiling Presence Detector - fig 4 Pull out the ends of both springs and bend them so that they do not stick out over the sensor head bezel.

AFTER INSTALLATION

CP electronics VITP7-EBDMR Vitesse Plus Ceiling Presence Detector - fig 5 Use the two RJ45 sockets with Cat5 patch leads to connect other Vitesse Plus components such as lighting control modules (LCMs) and detectors.CP electronics VITP7-EBDMR Vitesse Plus Ceiling Presence Detector - fig 6Use the UNLCDHS handset to send the required preset configuration to the LCM.

TESTING

CP electronics VITP7-EBDMR Vitesse Plus Ceiling Presence Detector - fig 7Plug the luminaires into the LCM.

CP electronics VITP7-EBDMR Vitesse Plus Ceiling Presence Detector - fig 8 If the preset configuration is for Presence detection, making a movement should turn the lights on. If the preset is for Absence, turn the light on at the switch and carry out the following additional steps…

CP electronics VITP7-EBDMR Vitesse Plus Ceiling Presence Detector - fig 9Use the UNLCDHS handset to program the detector to have a time-out period of 1 minute. CP electronics VITP7-EBDMR Vitesse Plus Ceiling Presence Detector - fig 10Vacate the room or remain very still and wait for the load to switch off (this should take 6 minutes).CP electronics VITP7-EBDMR Vitesse Plus Ceiling Presence Detector - fig 11 Enter the room and check that the load switches on.

TROUBLESHOOTING

What if the load does not come on?

  • Check that the LCM is powered up and the wiring is correct.
  • Disconnect both RJ45 connections on the Cat5 patch lead then reconnect, ensuring that they click into position.
  • Check that the Lux Hold Off setting is not keeping the lights off due to there being sufficient ambient light.
  • If detection range is smaller than expected, mount the detector higher.
  • If the LED is flashing at regular intervals, the detector is being overridden. Use the handset to cancel the override.

What if the load does not turn off?

  • Confirm that the area is being left unoccupied for longer than the timeout period.
  • Ensure that the sensor is not adjacent to circulating air, heaters or lamps.
  • If the LED is flashing at regular intervals, the detector is being overridden. Use the handset to cancel the override.

Technical data

Supply voltage DC 12 V
Max load See Vitesee Plus LCM documentation
Connections RJ45 sockets
Operational temp. ºC -10 to 35
Humidity 5 to 95% non-condensing
Material (casing) Flame retardant ABS and PC/ABS
Compliance EMC-2014/30/EU, LVD-2014/35/EU

CP electronics logoCP electronics VITP7-EBDMR Vitesse Plus Ceiling Presence Detector - icon 2CP electronicsac VITP7-EBDMR Vitesse Plus Ceiling Presence Detector - icon 3CP Electronics – a business unit of Legrand Electric Limited
Brent Crescent, London NW10 7XR Tel: +44 (0)333 900 0671
Fax: +44 (0)333 900 0674
CP electronics VITP7-EBDMR Vitesse Plus Ceiling Presence Detector - icon 4UK
www.cpelectronics.co.uk
enquiry@cpelectronics.co.uk
Due to our policy of continual product improvement, CP
Electronics reserves the right to alter the specification of this product without prior notice.
Ref WD877 issue 2