CONTEMPORARY CONTROLS BASC-E36 36 Point Edge Controller Installation Guide

BASC-E36 36 Point Edge Controller

Specifications:

  • Product Name: BAScontrol-E36
  • Type: 36-point Edge Controller
  • Communication Protocol: BACnet
  • Control: Sedona
  • Platform: Linux
  • Features: Cloud connector to Azure IoT Central, JSON-node
    programmable dashboard, email alarms and notifications, online
    weather service access
  • Configuration: Webpage configurable, Sedona drag-and-drop
    programming, BAScontrol Toolset
  • Driver: Sedona N4 driver available for programming via N4
    Workbench
  • Design: Rugged, low profile, wide temperature operation for
    indoor or outdoor use

Product Usage Instructions:

Installation:

Ensure proper electrical connections using the specified power
requirements.

Power:

WARNING: Follow power source compatibility
guidelines to prevent damage.

Input/Output Connections:

Refer to the wiring diagram for proper connection of
input/output devices.

Termination:

To terminate the controller at an end-of-line location, insert
jumpers accordingly.

Web Page Configuration:

Access the BAScontrol-E36 factory settings using the default IP
address, subnet mask, username, and password provided in the
manual.

FAQ:

Q: How do I reset the device to factory settings?

A: To reset the device to factory settings, locate the reset
button on the device and hold it for 10 seconds until the device
restarts.

Q: Can I use the BAScontrol-E36 in extreme temperatures?

A: Yes, the BAScontrol-E36 is designed for wide temperature
operation and can be used in both indoor and outdoor
environments.

BAScontrol-E36
36-point Edge Controller
The BAScontrol-E36 is a 36-point edge controller which supports BACnet/IP client/server operation over its built-in 2-port Ethernet switch connection or BACnet MS/TP over its EIA-485 port. A wall setter port supports an optional wall setter device. The controller complies with the B-ASC device profile having a convenient mix of sixteen universal inputs, four binary inputs, eight analog outputs, and eight binary outputs. It is designed for the requirements of ASHRAE Guideline 36-2018 High-Performance Sequences of Operation for HVAC Systems (GL-36).
The controller has the necessary computing power and input/output (I/O) points to execute recommended advanced sequences published in GL-36. It utilizes BACnet for communication protocol and Sedona for control. The BAScontrol-E36 runs on a Linux platform and has edge-connected features, such as a cloud connector to Azure IoT Central, a JavaScript Object Notation (JSON)-node programable dashboard, email alarms and notifications, and access to an online weather service.
The device is fully webpage configurable and freely programmable using Sedona’s drag-and-drop programming methodology and can be programmed using Contemporary Controls’ free BAScontrol Toolset. A Sedona N4 driver is available for programming via N4 Workbench. Rugged design, low profile, and wide temperature operation make it suitable for indoor or outdoor use.

Installation Guide

BASC-E36

Electrical (Class 2 Circuits Only)

INPUT Voltage (±10%): Power: Frequency:

DC 24 V 15 W N/A

AC 24 V 22 VA 47-63 Hz

Environmental Operating temperature: Storage temperature: Relative humidity:

­40°C to +75°C ­40°C to +85°C 10­95%, non-condensing

Functional Ethernet
MS/TP

Physical Layer
10BASE-T 100BASE-TX
EIA-485

Wall Setter EIA-485

Cable length limit 100 m

Comments

1200 m (for 9.6-76.8 kbps) 1000 m (for115.2 kbps) Jumper selectable bias and termination.
100 m

Installation
Power
The power source for the internal supply is applied via the two terminals labelled HI and COM. COM is for the power source return and serves as the common ground connection. Primary 24 VAC/VDC (± 10%) power is applied to HI and COM. HI connects to a diode and accomplishes half-wave rectified power–while providing reverse input voltage protection. The recommended power conductor size is 16­18 AWG (solid or stranded). Ground is directly connected to zero volts. Input connections are reverse polarity protected. This device is intended for use with Class 2 circuits. A ground lug is provided to connect the device to either earth or control panel ground. Use a green 16-18 AWG for connection.
WARNING: Internally, this device utilizes a half-wave rectifier and therefore can only share the same AC power source with other half-wave rectified devices. Sharing a common DC power source is also possible. Sharing AC power with fullwave rectified devices is NOT recommended. Devices powered from a common AC source could be damaged if a mix of half-wave and full-wave rectified devices exists.

The dimensions are the same on all models. All units are in mm.
Ø 4.7

L

E

D

LED LED LED LED

UI UI UI UI UI 01 02 C 03 04
J6
ETH1

UI UI UI UI UI 05 06 C 07 08
J5

UI UI UI UI UI 09 10 C 11 12
J4

UI UI UI UI UI 13 14 C 15 16
J3

BI BI BI BI BI 12C34
J2

LEDs TX RX STAT PWR
BAScontrol-E36
24 VAC/VDC

SERVICE
Reset

24V
J1
V +D -D C J11

ETH2

J7

J8

J9

AO AO AO AO AO AO AO AO AO AO 12C34 56C78

BO1

BO2

BO3 BO4

J10
BO5 BO6 BO7 BO8

MS/TP EOL +S -S SC Term
TX RX

L

E

LED LED

D

120 mm 128 mm

25 mm

173 mm 181 mm

Input/Output Connections

Wiring diagram showing the wall setter and MS/TP wiring option.

T1

24 VAC

Line

COM

Line

L

E

D

LED LED LED LED

UI UI UI UI UI 01 02 C 03 04
J6
ETH1

UI UI UI UI UI 05 06 C 07 08
J5

UI UI UI UI UI 09 10 C 11 12
J4

UI UI UI UI UI 13 14 C 15 16
J3

BI BI BI BI BI 12C34
J2

LEDs TX RX STAT PWR
BAScontrol-E36
24 VAC/VDC

SERVICE
Reset

24V J1
V +D -D C J11

ETH2

J7

J8

J9

AO AO AO AO AO AO AO AO AO AO 12C34 56C78

BO1

BO2

BO3 BO4

J10
BO5 BO6 BO7 BO8

MS/TP EOL +S -S SC Term
TX RX

L

E

LED LED

D

Termination BTB: To terminate the controller at an end-of-line (EOL) location, insert the jumpers over the left 4 jumper pins (see installation guide).

To enable or disable bias/termination, install jumpers as shown.
Bias/Termination Enabled
Bias/Termination Disabled

Web Page Configuration

The BAScontrol-E36 contains an interactive web server accessible from any Internet-compatible PC on the local network with recent versions of most standard web browsers such as Microsoft Edge, Mozilla Firefox, Apple Safari, or Google Chrome. To configure the controller, connect it to your PC using an Ethernet cable and set the PC’s IP and subnet mask in Local Area Connection ­> Properties. In the Internet Protocol Version 4 (TCP/IPv4) settings of your PC, specify an IP address and a Subnet mask in the same subnet as the BAScontrol-E36 (e.g., 192.168.92.5 /24).

BAScontrol-E36 factory settings:

Default IP address is 192.168.92.68 and a Class C subnet mask of 255.255.255.0 (/24) User Name is admin and Password is admin

Reset IP switch is located on the front, underneath the metal case edge, and also indicated on label. Remove power, then press and hold the Reset IP switch.

Apply power again while holding down the Reset IP switch. I/O channels will alternately flash after startup. Log in to the default IP address and set new IP,

User ID, and Password. For complete datasheet and details on BAScontrol-E36, support, or compliance information, please visit our product page at:

https://www.ccontrols.com/basautomation/bascontrole36.php and click on the Support tab under More Information.

Contemporary Control Systems, Inc. reserves the right to make changes in the specifications of the product described within this manual at any time without notice and without obligation of Contemporary Control Systems, Inc. to notify any person of such revision or change.

TD210500-0IA