ComfortStar CC-CPAL009-1S Variable Refrigerant Flow Systems

ComfortStar-CC-CPAL009-1S-Variable-Refrigerant-Flow-Systems-product

Specification

Comfortstar Model CC-CPAL009-1S
Power supply 220-240V/1N/50Hz
Capacity Cooling kW 2.8
Heating kW 3.2
Rated input kW 0.05
 

 

Fan motor

Model   DR-310-27F-8
Type   DC
Brand   Yongan
Speed (Hi/Med/Low) r/min 850/640/550
ESP Pa 30
 

Indoor coil

Number of rows   2
Fin type   Hydrophilic aluminum
Tube diameter and type mm Ø7, Innergroove tube
Air flow (High speed) m3/h 450
Sound pressure level dB(A) 24~29
 

Body

Dimension (W×H×D) mm 814×210×467
Packing (W×H×D) mm 910×240×510
Net/Gross weight kg 16/18.5
Refrigerant type   R410A
Throttle type   EXV
Design pressure MPa 4.5
Liquid pipe / Gas pipe mm Ø6.35/ Ø9.53
 

Connecting wire

Power wire mm2 2.5*2+2.5(L≤20m)
  4*2+2.5(20m<L≤50m)
Signal wire mm2 0.75*2 shield
Drainage water pipe   mm Ø25
Controller Standard   Wired controller
Optional   Remote controller
Operation temp   ˚C 16~32

Note: Graphics in this document are for representation only.The actual model may differ in appearance.

Unit dimensionComfortStar-CC-CPAL009-1S-Variable-Refrigerant-Flow-Systems-fig1 ComfortStar-CC-CPAL009-1S-Variable-Refrigerant-Flow-Systems-fig2 ComfortStar-CC-CPAL009-1S-Variable-Refrigerant-Flow-Systems-fig3

ComfortStar-CC-CPAL009-1S-Variable-Refrigerant-Flow-Systems-fig4

The AHRI mark indicates Comfortstar’s participation in the AHRI Certification program. Visit ahridirectory.org for verification of individual certified products. Comfortstar reserves the right to change design and specs without notice. Comfortstar has a policy of updating the data continuously. We are committed to using environmentally conscious print practices.

Product Usage Instructions

Assembly and Parts Replacement

  1. Refer to the exploded view diagram to identify different parts of the product.
  2. When replacing parts, ensure compatibility with the model number mentioned in the manual.
  3. Follow the provided part codes for accurate replacement.

Cleaning and Maintenance

  1. Regularly clean filter baffles and cotton attachments to maintain optimal performance.
  2. Inspect motor assembly components for any debris or blockages that may affect functioning.
  3. Ensure proper drainage by checking the water pump assembly and related parts.

FAQs

How often should I clean the filter?

It is recommended to clean the filter baffles at least once a month to ensure efficient air circulation.

Can I replace spare parts myself?

Yes, you can replace spare parts following the instructions provided in the user manual. Ensure to power off the unit before any maintenance work.

What should I do if the water pump is not functioning?

Check for any clogs in the drainage system and ensure the water pump filter seat is clean. If issues persist, contact customer support for assistance.