ComfortStar CC-CPAL009-1S Variable Refrigerant Flow Systems
Specification
Comfortstar Model | CC-CPAL009-1S | ||
Power supply | 220-240V/1N/50Hz | ||
Capacity | Cooling | kW | 2.8 |
Heating | kW | 3.2 | |
Rated input | kW | 0.05 | |
Fan motor |
Model | DR-310-27F-8 | |
Type | DC | ||
Brand | Yongan | ||
Speed (Hi/Med/Low) | r/min | 850/640/550 | |
ESP | Pa | 30 | |
Indoor coil |
Number of rows | 2 | |
Fin type | Hydrophilic aluminum | ||
Tube diameter and type | mm | Ø7, Innergroove tube | |
Air flow (High speed) | m3/h | 450 | |
Sound pressure level | dB(A) | 24~29 | |
Body |
Dimension (W×H×D) | mm | 814×210×467 |
Packing (W×H×D) | mm | 910×240×510 | |
Net/Gross weight | kg | 16/18.5 | |
Refrigerant type | R410A | ||
Throttle type | EXV | ||
Design pressure | MPa | 4.5 | |
Liquid pipe / Gas pipe | mm | Ø6.35/ Ø9.53 | |
Connecting wire |
Power wire | mm2 | 2.5*2+2.5(L≤20m) |
4*2+2.5(20m<L≤50m) | |||
Signal wire | mm2 | 0.75*2 shield | |
Drainage water pipe | mm | Ø25 | |
Controller | Standard | Wired controller | |
Optional | Remote controller | ||
Operation temp | ˚C | 16~32 |
Note: Graphics in this document are for representation only.The actual model may differ in appearance.
Unit dimension

- 12201 N W 107th Avenue
- Miami, FL 33178
- 1.866.524.9898 Toll Free
- 305.500.9898 Office
- 305.500.9896 Fax
- http://www.comfortstarusa.com
The AHRI mark indicates Comfortstar’s participation in the AHRI Certification program. Visit ahridirectory.org for verification of individual certified products. Comfortstar reserves the right to change design and specs without notice. Comfortstar has a policy of updating the data continuously. We are committed to using environmentally conscious print practices.
Product Usage Instructions
Assembly and Parts Replacement
- Refer to the exploded view diagram to identify different parts of the product.
- When replacing parts, ensure compatibility with the model number mentioned in the manual.
- Follow the provided part codes for accurate replacement.
Cleaning and Maintenance
- Regularly clean filter baffles and cotton attachments to maintain optimal performance.
- Inspect motor assembly components for any debris or blockages that may affect functioning.
- Ensure proper drainage by checking the water pump assembly and related parts.
FAQs
How often should I clean the filter?
It is recommended to clean the filter baffles at least once a month to ensure efficient air circulation.
Can I replace spare parts myself?
Yes, you can replace spare parts following the instructions provided in the user manual. Ensure to power off the unit before any maintenance work.
What should I do if the water pump is not functioning?
Check for any clogs in the drainage system and ensure the water pump filter seat is clean. If issues persist, contact customer support for assistance.