CLIveT T D63 Compact 4 Way Cassette
Product Information
Specifications
- Model: Q4AN-3-XY D15 – D63
- Power Supply: 1-phase, 220-240V, 50Hz
- Refrigerant Type: R-410A
- Cooling Capacity: 1.5 kW – 6.3 kW
- Heating Capacity: 1.8 kW – 7.1 kW
- Fan Motor Type: DC
- Main Body Weight: 13.0 kg – 16.0 kg
- Panel Weight: 2.3 kg – 3.0 kg
- Liquid/Gas Pipe: 6.35 mm / 12.7 mm
Product Usage Instructions
Installation
Ensure the maintenance hole centerline aligns with the indoor unit centerline.
Unit Placement
Follow the provided unit placement considerations to ensure proper installation.
Piping Diagram
Refer to the piping diagram legend for proper connections.
Wiring Diagram
Follow the wiring diagram for correct electrical connections.
Group Control
For group control, connect indoor units in a daisy chain and set the group controller to group control mode.
FAQs
- Q: What should I do if the unit is not cooling/heating properly?
A: Check the power supply, air filters, and ensure proper installation for efficient cooling/heating. - Q: How often should the unit be serviced?
A: It is recommended to service the unit annually to maintain optimal performance. - Q: Can this unit be used in commercial spaces?
A: Yes, this unit is suitable for both residential and commercial applications.
FEATURES
SIZE | D15 | D22 | D28 | D36 | D45 | D56 | D63 | ||||||||
COOLING CAPACITY kW | 1,5 | 2,2 | 2,8 | 3,6 | 4,5 | 5,6 | 6,3 | ||||||||
HEATING CAPACITY kW | 1,8 | 2,4 | 3,2 | 4,0 | 5,0 | 6,3 | 7,1 |
General technical data
Model | Q4AN-3-XY D15 | Q4AN-3-XY D22 | Q4AN-3-XY D28 | Q4AN-3-XY D36 | ||||||||
Power supply | 1-phase, 220-240V, 50Hz | |||||||||||
Cooling1 |
Capacity | kW | 1.5 | 2.2 | 2.8 | 3.6 | ||||||
kBtu/h | 5.1 | 7.5 | 9.6 | 12.3 | ||||||||
Power input | W | 14 | 14 | 16 | 18 | |||||||
Heating2 |
Capacity | kW | 1.8 | 2.4 | 3.2 | 4.0 | ||||||
kBtu/h | 6.1 | 8.2 | 10.9 | 13.7 | ||||||||
Power input | W | 14 | 14 | 16 | 18 | |||||||
Fan motor type | DC | |||||||||||
Indoor coil |
Number of rows | 1 | 1 | 1 | 2 | |||||||
Tube pitch × row pitch | mm | 18×10,72 | ||||||||||
Fin spacing and type | mm | 1,2 Hydrophilic aluminum | ||||||||||
Tube OD and type | mm | Ф5 Inner-groove | ||||||||||
Dimensions (L×H×W) | mm | 436×180×436 | ||||||||||
Number of circuits | 1 | 1 | 1 | 2 | ||||||||
Air flow rate3 | m3/h | 450/425/400/370/345/320/295 | 510/480/455/425/ 395/370/340 | 530/500/470/440/ 405/375/345 | ||||||||
Sound pressure level4 | dB(A) | 29/28/27/27/26/26/25 | 30/29/28/27/26/26/25 | 31/30/29/28/27/26/25.5 | ||||||||
Sound power level5 | dB(A) | 40/39/39/39/38/38/38 | 42/41/40/39/39/38/38 | 42/40/39/38/38/38/38 | ||||||||
Main body |
Net dimensions6 (W×H×D) | mm | 575×235×638 | |||||||||
Packed dimensions (W×H×D) | mm | 690×285×690 | ||||||||||
Net/Gross weight | kg | 13.0/15.0 | 14.0/16.0 | |||||||||
Panel |
Net dimensions7 (W×H×D) | mm | 620×65×620 | |||||||||
Packed dimensions (W×H×D) | mm | 680×80×665 | ||||||||||
Net/Gross weight | kg | 2.3/3.0 | ||||||||||
Refrigerant type | R410A/R32 | |||||||||||
Design pressure (H/L) | MPa | 4.4/2.6 | ||||||||||
Pipe connections | Liquid/Gas pipe | mm | Ф6.35/Ф12.7 | |||||||||
Drain pipe | mm | OD Ф25 |
Model | Q4AN-3-XY D45 | Q4AN-3-XY D56 | Q4AN-3-XY D63 | ||||||||
Power supply | 1-phase, 220-240V, 50Hz | ||||||||||
Cooling1 |
Capacity | kW | 4.5 | 5.6 | 6.3 | ||||||
kBtu/h | 15.4 | 19.1 | 21.5 | ||||||||
Power input | W | 25 | 35 | 50 | |||||||
Heating2 |
Capacity | kW | 5.0 | 6.3 | 7.1 | ||||||
kBtu/h | 17.1 | 21.5 | 24.2 | ||||||||
Power input | W | 25 | 35 | 50 | |||||||
Fan motor type | DC | ||||||||||
Indoor coil |
Number of rows | 2 | 3 | 3 | |||||||
Tube pitch × row pitch | mm | 18×10,72 | |||||||||
Fin spacing and type | mm | 1,2 Hydrophilic aluminum | |||||||||
Tube OD and type | mm | Ф5 Inner-groove | |||||||||
Dimensions (L×H×W) | mm | 436×180×436 | |||||||||
Number of circuits | 2 | 3 | 3 | ||||||||
Air flow rate3 | m3/h | 640/605/570/530/ 495/460/425 | 810/765/720/670/ 625/580/535 | 905/855/805/755/ 705/655/605 | |||||||
Sound pressure level4 | dB(A) | 36.5/35/33/31/29/28/26.5 | 39/38/37/36/35/34/32 | 43/42/40/38/36/35/33.5 | |||||||
Sound power level5 | dB(A) | 44/44/43/42/41/41/41 | 48/46/45/43/42/42/41 | 51/50/48/46/45/44/42 | |||||||
Main body |
Net dimensions6 (W×H×D) | mm | 575×235×638 | ||||||||
Packed dimensions (W×H×D) | mm | 690×285×690 | |||||||||
Net/Gross weight | kg | 14.0/16.0 | 15.0/17.0 | ||||||||
Panel |
Net dimensions7 (W×H×D) | mm | 620×65×620 | ||||||||
Packed dimensions (W×H×D) | mm | 680×80×665 | |||||||||
Net/Gross weight | kg | 2.3/3.0 | |||||||||
Refrigerant type | R410A/R32 | ||||||||||
Design pressure (H/L) | MPa | 4.4/2.6 | |||||||||
Pipe connections | Liquid/Gas pipe | mm | Ф6.35/Ф12.7 | Ф9.52/Ф15.9 | |||||||
Drain pipe | mm | OD Ф25 |
Notes:
- Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
- Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
- Air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.
- Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.4m below the unit in a semi- anechoic chamber.
- Sound power level is from highest level to lowest level, total 7 levels for each model.
- The dimension is only the body size, excluding the size of the installation lug, connecting copper pipe, etc. For detailed dimensions, please refer to the installation manual.
- Exposed height of the panel after being installed on the ceiling.
Dimensions
Dimensions (unit: mm)
Unit placement
Placement Considerations
Unit placement should take account of the following considerations:
- Units should not be installed in the following locations:
- A place filled with mineral oil, fumes or mist, like a kitchen.
- A place where there are corrosive gases, such as acid or alkaline gases.
- A place exposed to combustible gases and using volatile combustible gases such as diluent or gasoline.
- A place where there is equipment emitting electromagnetic radiation.
- A place where there is a high salt content in the air like a coast.
- Do not use the air conditioner in an environment where an explosion may occur.
- Places like in vehicles or cabin rooms.
- Factories with major voltage fluctuations in the power supplies.
- Other special environmental conditions.
- Units should be installed in positions where:
- Ensure that the airflow in and out of the IDU is reasonably organized to form an air circulation in the room.
- Ensure IDU maintenance space.
- The nearer the drainage pipe and copper pipe are to the ODU, the lower the pipe cost is.
- Prevent the air conditioner from blowing directly to the human body.
- The closer the wiring to the power cabinet, the lower the wiring cost is.
- Keep the air-conditioning return air away from the setting sun of the room.
- Be careful not to interfere with the light tank, fire pipe, gas pipe and other facilities.
- The IDU should not be lifted in the places like load-bearing beam and columns that affect the structural safety of the house.
- The wired controller and the IDU should be in the same installation space; otherwise, the sampling point setting of the wired con-troller need to be changed.
Space Requirements (unit: mm)
- The centerline of the maintenance hole should be in the same position as the centerline of the indoor unit.
MODEL | A | B | ||
D15÷D56 | Φ6.35 | Φ12.7 | ||
D63 | Φ9.52 | Φ15.9 |
Piping Diagram
LEGEND | ||||
1 | T1 | Inlet Air Temp. Sensor | ||
2 | T2A | Liquid Pipe Temp. Sensor | ||
3 | T2 | Middle Pipe Temp. Sensor | ||
4 | T2B | Gas Pipe Temp. Sensor |
Wiring Diagram
Notes for installers and service engineers
- Caution
- All installation, servicing and maintenance must be carried out by competent and suitably qualified, certified and accredited profes-sionals and in accordance with all applicable legislation.
- Units should be grounded in accordance with all applicable legislation. Metal and other conductive components should be insula-ted in accordance with all applicable legislation.
- Power supply wiring should be securely fastened at the power supply terminals loose power supply wiring would represent a fire risk.
- After installation, servicing or maintenance, the electric control box cover should be closed. Failing to close the electric control box cover risks fire or electric shock.
- The dotted lines indicate the field wiring or optional function
- D1D2 communication ports are used for group control communication. When connecting the group controller, the D1D2 port of the indoor units that are to be group controlled must be connected in daisy chain, and the group controller must be connected to the X1X2 port of one of the indoor units in the group control, and set to group control mode. In addition, D1D2 communication ports can also be connected to the central controller.
Capacity Tables
Cooling Capacity Table
MODEL | Indoor air temperature (°C WB/DB) | |||||||||||||||||||||||||||
14/20 | 16/23 | 18/26 | 19/27 | 20/28 | 22/30 | 24/32 | ||||||||||||||||||||||
TC | SC | TC | SC | TC | SC | TC | SC | TC | SC | TC | SC | TC | SC | |||||||||||||||
Q4AN-3-XY D15 | 1.4 | 1.3 | 1.5 | 1.4 | 1.5 | 1.3 | 1.5 | 1.3 | 1.6 | 1.3 | 1.6 | 1.2 | 1.6 | 1.1 | ||||||||||||||
Q4AN-3-XY D22 | 2.0 | 1.9 | 2.1 | 1.9 | 2.2 | 1.9 | 2.2 | 1.8 | 2.3 | 1.8 | 2.3 | 1.7 | 2.4 | 1.7 | ||||||||||||||
Q4AN-3-XY D28 | 2.5 | 2.3 | 2.7 | 2.4 | 2.8 | 2.4 | 2.8 | 2.3 | 2.9 | 2.3 | 2.9 | 2.2 | 3.0 | 2.1 | ||||||||||||||
Q4AN-3-XY D36 | 3.2 | 2.9 | 3.4 | 3.0 | 3.6 | 3.0 | 3.6 | 2.9 | 3.7 | 2.9 | 3.8 | 2.8 | 3.9 | 2.7 | ||||||||||||||
Q4AN-3-XY D45 | 4.0 | 3.6 | 4.3 | 3.7 | 4.5 | 3.8 | 4.5 | 3.7 | 4.6 | 3.6 | 4.7 | 3.4 | 4.8 | 3.3 | ||||||||||||||
Q4AN-3-XY D56 | 5.0 | 4.6 | 5.3 | 4.7 | 5.6 | 4.8 | 5.6 | 4.6 | 5.7 | 4.5 | 5.8 | 4.2 | 6.0 | 4.1 | ||||||||||||||
Q4AN-3-XY D63 | 5.6 | 5.2 | 6.0 | 5.3 | 6.3 | 5.4 | 6.3 | 5.2 | 6.4 | 5.1 | 6.5 | 4.7 | 6.8 | 4.6 |
- Abbreviations:
- TC: Total capacity (kW)
- SC: Sensible capacity(kW)
Notes: Shaded cells indicate rating condition.
Heating Capacity Table
MODEL | 16 | 18 | 20 | 21 | 22 | 24 | |||
TC | TC | TC | TC | TC | TC | ||||
Q4AN-3-XY D15 | 1.9 | 1.9 | 1.8 | 1.7 | 1.7 | 1.6 | |||
Q4AN-3-XY D22 | 2.6 | 2.6 | 2.4 | 2.3 | 2.3 | 2.1 | |||
Q4AN-3-XY D28 | 3.4 | 3.4 | 3.2 | 3.1 | 3.0 | 2.8 | |||
Q4AN-3-XY D36 | 4.2 | 4.2 | 4.0 | 3.8 | 3.8 | 3.5 | |||
Q4AN-3-XY D45 | 5.3 | 5.3 | 5.0 | 4.8 | 4.7 | 4.4 | |||
Q4AN-3-XY D56 | 6.7 | 6.6 | 6.3 | 6.1 | 5.9 | 5.5 | |||
Q4AN-3-XY D63 | 7.5 | 7.5 | 7.1 | 6.9 | 6.7 | 6.2 |
- Abbreviations:
- TC: Total capacity (kW)
Notes: Shaded cells indicate rating condition.
- TC: Total capacity (kW)
Electrical characteristics
MODEL | Power supply | Indoor fan motors | |||||||
Hz | Volts | Min. volts | Max. volts | MCA | MFA | Rated motor output (kW) | FLA | ||
Q4AN-3-XY D15 | 50 | 220-240 | 198 | 264 | 0.46 | 15 | 0.045 | 0.37 | |
Q4AN-3-XY D22 | 50 | 220-240 | 198 | 264 | 0.46 | 15 | 0.045 | 0.37 | |
Q4AN-3-XY D28 | 50 | 220-240 | 198 | 264 | 0.54 | 15 | 0.045 | 0.43 | |
Q4AN-3-XY D36 | 50 | 220-240 | 198 | 264 | 0.54 | 15 | 0.045 | 0.43 | |
Q4AN-3-XY D45 | 50 | 220-240 | 198 | 264 | 0.61 | 15 | 0.045 | 0.49 | |
Q4AN-3-XY D56 | 50 | 220-240 | 198 | 264 | 0.65 | 15 | 0.045 | 0.52 | |
Q4AN-3-XY D63 | 50 | 220-240 | 198 | 264 | 0.81 | 15 | 0.045 | 0.65 |
- Abbreviations:
- MCA: Minimum Circuit Amps MFA: Maximum Fuse Amps FLA: Full Load Amps
- Voltage range: Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. Maximum allowable voltage variation between phases is 2%.
Selection wire size based on the value of MCA.
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth circuit breaker).
Overall
MODEL | Sound pressure levels dB | |||||||
SSH | SH | H | M | L | SL | SSL | ||
Q4AN-3-XY D15 | 29 | 28 | 27 | 27 | 26 | 26 | 25 | |
Q4AN-3-XY D22 | 29 | 28 | 27 | 27 | 26 | 26 | 25 | |
Q4AN-3-XY D28 | 30 | 29 | 28 | 27 | 26 | 26 | 25 | |
Q4AN-3-XY D36 | 31 | 30 | 29 | 28 | 27 | 26 | 25.5 | |
Q4AN-3-XY D45 | 36.5 | 35 | 33 | 31 | 29 | 28 | 26.5 | |
Q4AN-3-XY D56 | 39 | 38 | 37 | 36 | 35 | 34 | 32 | |
Q4AN-3-XY D63 | 43 | 42 | 40 | 38 | 36 | 35 | 33.5 |
Notes: Sound pressure levels are measured 1.4m below the unit in a semi-anechoic chamber at 0 Pa static pressure. During in-situ operation, sound pressure levels may be higher as a result of ambient noise.
Octave Band Levels
Sound Level
Temperature and Airflow Distributions
Simulate condition
MODEL NAME | Room size (m) | Ceiling height (m) | Flow angle (Cooling/Heating) | Placing | |
Q4AN-3-XY D15 | 5*5 | 2.7 | 40°/70° | Center | |
Q4AN-3-XY D22 | 5*5 | 2.7 | 40°/70° | Center | |
Q4AN-3-XY D28 | 6*6 | 2.7 | 40°/70° | Center | |
Q4AN-3-XY D36 | 6*6 | 2.7 | 40°/70° | Center | |
Q4AN-3-XY D45 | 6*6 | 2.7 | 40°/70° | Center | |
Q4AN-3-XY D56 | 6*6 | 2.7 | 40°/70° | Center | |
Q4AN-3-XY D63 | 6*6 | 2.7 | 40°/70° | Center |
Note: These figures and videos are based on software simulation. They show typical temperature and airflow distributions in the conditions above. In the actual installation, they may differ from these figures and videos under the influence of air temperature conditions, ceiling height, cooling/heating load, obstacles, etc.
Airflow distributions – Cooling (after 300s)
Airflow distributions – Heating (after 300s)
Temperature distributions – Cooling (after 300s)
Temperature distributions – Heating (after 300s)
FOR 30 YEARS WE HAVE BEEN OFFERING SOLUTIONS FOR SUSTAINABLE COMFORT AND THE WELL-BEING OF PEOPLE AND THE ENVIRONMENT.
CLIVET S.p.A
Via Camp Lonc 25, Z.I. Villapaiera 32032 – Feltre (BL) – Italy
Tel. +39 0439 3131
info@clivet.it
CLIVET GMBH
Hummelsbütteler Steindamm 84,
22851 Norderstedt, Germany
Tel. +49 40 325957-0
info.de@clivet.com
Clivet Group UK LTD
Units F5 & F6 Railway Triangle, Portsmouth, Hampshire PO6 1TG
Tel. +44 02392 381235 –
Enquiries@Clivetgroup.co.uk
CLIVET LLC
Office 508-511, Elektozavodskaya st. 24, Moscow, Russian Federation, 107023
Tel. +7495 6462009
info.ru@clivet.com
CLIVET MIDEAST FZCO
Dubai Silicon Oasis (DSO) Headquarter Building, Office EG-05, P.O Box-342009, Dubai, UAE
Tel. +9714 3208499
info@clivet.ae
Clivet South East Europe
Jaruščica 9b
10000, Zagreb, Croatia
Tel. +3851 222 8784
info.see@clivet.com
CLIVET France
10, rue du Fort de Saint Cyr – 78180 Montigny le Bretonneux, France
info.fr@clivet.com
Clivet Airconditioning Systems Pvt Ltd
Office No.501 & 502,5th Floor, Commercial –I, Kohinoor City, Old Premier Compound, Off LBS Marg, Kirol Road, Kurla West, Mumbai Maharashtra 400070, India
Tel. +91 22 30930200
sales.india@clivet.com
Documents / Resources
![]() |
CLIveT T D63 Compact 4 Way Cassette [pdf] Owner's Manual T D63 Compact 4 Way Cassette, T D63, Compact 4 Way Cassette, 4 Way Cassette, Cassette |