1.1 Outline and mounting dimensions

Model Wiring
Method
modulus Dimensions
(L*W*H) mm
Suttle(kg)  Rail dimension
DDSU666
Series
Direct
connection
1 100×18×65.5 About 0.08 DIN35 standard
guide rails

CHNT DDSU666 Series Single Phase Smart Meter - Product Description 1

CHNT DDSU666 Series Single Phase Smart Meter - icon 13 NOTE
The unnoted tolerance is ±1mm;
The appearance, size and information are subject to actual objects.

1.2 Product performance specifications 

Model DDSU666
Current specification 0.25-5(80)A
Access method Direct connection
Nominal voltage 220V…240V
Frequency 50/60Hz
Current measuring range 0~80A
Voltage measuring range 176V~253V
Accuracy class Class B(Class 1)
Power grid system single phase
Baud rate 1200bps/2400bps/4800bps/9600bps(default 9600bps)/19200bps/115200bps
Temperature -25℃~+55℃(nominal),-40℃~+70℃(ultimate)
Way to install Rail mounting
Authentication CE,RCM,MID

Install DDSU666

CHNT DDSU666 Series Single Phase Smart Meter - Install DDSU666 1

Installing cables

3.1 Prepare Cables

  • 0.25~5(80)A wiring – Direct connection
Cables Port Port
number
Type Conductor
Cross-sectional
Area Range
Outer
Diameter
Source
Voltage and
Current
Cable
N/UN 3 Multi-core
Outdoor
Copper
0.25mm2-1.5 mm2 4mm-1 1 mm Prepared by the
customer
‘JUL. I* 1 25mm2 10mm
I 2 Cable
  • Communications cable
Cables Port Port
number
Type Conductor
Cross-sectional
Area Range
Outer
Diameter
Source
Voltage and
Current
Cable
N/UN 3 Multi-core
Outdoor
Copper
Cable
0.25mm2-1.5mm2 4mm-1 I mm Prepared by the
customer
L/UL, I* 1 25mm2 lOmm
I 2

CHNT DDSU666 Series Single Phase Smart Meter - icon 13 NOTE
The maximum torque for terminal screws 1, 2 ,3is 1.7 N·m, and the recommended torque is 0.9 N·m to 1.1
N·m. The maximum torque for terminal screws 24 and 25 is 0.4 N·m, and the recommended torque is 0.15
N·m to 0.25 N·m.

3.2 Wiring Diagram

  • Direct connection

CHNT DDSU666 Series Single Phase Smart Meter - Installing cables 1

Displays project and parameter Settings

4.1 Display
When the meter is powered on, it will display the software version number and CRC check code.
Software Version:V104,CRC check code:0x55d7. The key is used to switch the display interface.

No. Display Interface Instruction
Display when power on
1 CHNT DDSU666 Series Single Phase Smart Meter - icon 1 Software version:V104
2 CHNT DDSU666 Series Single Phase Smart Meter - icon 2 CRC check code:0x55d7
Auto display
3 CHNT DDSU666 Series Single Phase Smart Meter - icon 3 Means the combined active total electrical
energy, the unit is “kWh”, the left picture is
2.200kWh.
4 CHNT DDSU666 Series Single Phase Smart Meter - icon 4 the current display voltage is U, the unit is “
V”, the left picture is U=220.0V.
5 CHNT DDSU666 Series Single Phase Smart Meter - icon 5 the current display current is I, the unit is “A
”, the left picture is I=5.000A.
6 CHNT DDSU666 Series Single Phase Smart Meter - icon 6 the current display is the active power P,
the unit is “kW” ,the left picture is
P=1.100kW.
7 CHNT DDSU666 Series Single Phase Smart Meter - icon 7 the current display is the power factor Ft,
the left picture is Ft=1.000.
8 CHNT DDSU666 Series Single Phase Smart Meter - icon 8 the current display is frequency F, the left
picture is  F=50.00Hz.
9 CHNT DDSU666 Series Single Phase Smart Meter - icon 9 the current communication protocol is
Modbus.
10 CHNT DDSU666 Series Single Phase Smart Meter - icon 10 the current communication address of
Modbus is 1.
11 CHNT DDSU666 Series Single Phase Smart Meter - icon 11 Represents 8 data bits, no effect bit and one
stop bit of the current communication
protocol.
12 CHNT DDSU666 Series Single Phase Smart Meter - icon 12 the current communication baud rate is 9600.

4.2 Parameter setting operation example
Description of pressing key:As shown in the following flowchart, long press the button and lift it to display the screen to enter the Setting ModBus address screen. Press the button again to modify the ModBus address. The address range of the button can be set to 1-247.

CHNT DDSU666 Series Single Phase Smart Meter - Installing cables 2

CHNT DDSU666 Series Single Phase Smart Meter - icon 13 NOTE
Communication parameters are configured for the smart power sensor prior to delivery. If the communication is abnormal, check and set parameters.

Diagnosis, analysis and troubleshooting of common faults

Fault phenomenon Reason analysis Elimination
No display after the
instrument being
powered on
Incorrect wiring mode; Abnormal voltage supplied for theinstrument 1.If the wiring mode is incorrect, please connect based on the correct wiring mode (see the wiring diagram).
2.If the supplied voltage is abnormal, please supply the
voltage on the instrument specification.
If this is not the problem above, contact your local supplier

Warranty and Service

The manufacturer implements three guarantees for product quality. Within 18 months from the date of delivery, if the user fully complies with the provisions of this manual and the factory seal is still intact, the
instrument is found damaged during use, and the company is responsible for free repair or replacement.

Environmental

Dear customer :
Please help us do one thing, when this product at the end of its life, in order to protect our environment, please do a good job of recycling the product or its parts and materials. Please also dispose of materials that cannot be recycled. Thank you very much for your cooperation and support.

Statement

  1. The products, services or features purchased by you are subject to the commercial contracts and terms signed with the Company, and all or part of the products, services or features described in this manual may not be included in the products purchased by you.
  2. Except as otherwise agreed in the contract, the Company makes no representations or warranties, express or implied, about the contents of this specification.
  3. The information in this brochure is subject to change without prior notice.
  4. The Company shall not be liable for indirect losses arising from the provision, display or use of this material.

Manufacturer Information

Manufacturer Zhejiang Chint IoT Technology Co.,Ltd.
Address Wenzhou Bridge Industrial Park, Beibaixiang Town, Yueqing City, Wenzhou City,
Zhejiang Province, China.
Tel. +86-577-62877777
Postcode 325603
FAX +86-400-8177777
Service Hotline +86-577-62789987
Website http://aiot.chint.com
E-mail ztwl@chint.com

Documents / Resources

CHNT DDSU666 Series Single Phase Smart Meter [pdf] User Guide
666-110, DDSU666 Series Single Phase Smart Meter, DDSU666 Series, Single Phase Smart Meter, Smart Meter, Meter

References

Leave a comment

Your email address will not be published. Required fields are marked *