CDP UPO11-3 Enterprise Level Monitoring Solutions AC Power Modular Datacenters User Guide
High performance double conversion for critical loads and corporate applications
Features
- Voltage range 60 – 150VAC. Double conversion technology.
- Frequency regulation at output.
- Pure sine wave output. Offers greater availability for your equipment, by correcting low and high voltages without using batteries.
- Zero transfer time.
- Eliminates 99% of electrical problems.
- Cold start.
- Allows fast recovery after overload events.
- Ideal for protection of medical equipment, laboratory, mission critical servers or telecommunications critical servers or telecommunications.
- Total isolation of the load from the commercial grid.
- Maximizes battery performance, life and reliability through intelligent, precision charging intelligent, precision charging.
- Protects the connected load against short or prolonged surges, lightning, other power irregularities and other power irregularities.
- Converts input power to direct current (DC) and then to alternating current (AC).
- Frequency conversion capability.
- Power factor 0.9 at output.
User friendly LCD Display
Shows input and output voltages, backup time and battery charge.
4 NEMA 5-15R or 5-20R output terminals
AC power cord NEMA 5-30P
Communication ports
Hard wire output
Option card: SNMP
Option card: EMD (Environmental Monitoring Device)
Task-critical solutions for corporate applications
Model | UPO11-3 | |
Capacity | 3000VA | |
Input | 120VAC nominal voltage | |
Voltage range | 60VAC – 150VAC | |
Frequency range | 40Hz- 70Hz | |
Power factor | >/=0.99 @nominal voltage (full load) | |
Output | ||
Output voltage | 110/115/120/ 127 VAC | |
ACvoltage regulation | +1% | |
Frequency range | Battery mode | 50 Hz +/-0.1 Hz 60 Hz +/-0.1 Hz |
Crest factor | 31 | |
Overload | 100% – 110: Alarm; 110/130: Battery mode: UPS shuts down in 30 seconds / Normal mode= UPS transfers to bypass mode when power is normal; >130%: Battery mode= UPS shuts down immediately / Normal mode= UPS transfers to bypass mode when power is normal | |
Harmonic distortion | </=3% THD (linear loads) </= 6% THD (non-linear loads) | |
Transfer time | AC mode to battery mode | zero |
Waveform | Pure sine wave | |
Eficiencia | ||
Modo AC | 90% | |
Modo Eco | 96% | |
Batteries | ||
Type/Quantity | 12v/9Ahx 6 | |
Recharge time | 4 hours to recover 90% of its capacity (typical) | |
Charge current | 1,0 Ah (max) | |
Charge voltage | 82,1VDC +/-1% | |
Backup time | Full charge 4 minutes / Half charge 9 minutes | |
Environment | ||
Dimensions | (length x height x depth) | 190335 x 421mm |
Net weight | 27.6Kg | |
Physical | ||
Humidity | 20-90% RH @ 0-45°C (non-condensing) | |
Noise level | Less than 50dBA @ 1 meter | |
Control | ||
Smart RS232 or USB | Supports Windows 2000/ 2003 / XP / Vista / 2008 / 7, 8,10, Linux and Mac | |
Optional SNMP | Control and command for SNMP and web browser (via internal SNMP or SNMPDBS) | |
Certifications | NOM, 1509001, 1SO14001, CIDET |
Product specifications are subject to change without notice
COP COLOMBIA
colombia@cdpups.com
CDP USA
usa@cdpups.com
COP CHINA
china@cdpups.com
Documents / Resources
![]() |
CDP UPO11-3 Enterprise Level Monitoring Solutions AC Power Modular Datacenters [pdf] User Guide UPO11-3 Enterprise Level Monitoring Solutions AC Power Modular Datacenters, UPO11-3, Enterprise Level Monitoring Solutions AC Power Modular Datacenters, Monitoring Solutions AC Power Modular Datacenters, AC Power Modular Datacenters, Modular Datacenters |