Carrier-logo

Carrier TM Series i-Vu Building Automation System Thermostats

Carrier-TM-Series-i-Vu-Building-Automation-System-Thermostats-fig-1

Product Information

The TB and TM Series Thermostats are designed to control temperature and humidity in various applications. Depending on the specific requirements, different models are available.

  • TB Series: Available in different configurations such as 24 V, Temp. Only or 110 – 220V, Temp, Humidity, Motion.
  • TM Series: Available in options like 24 V, Temp. Only or 110 – 220V, Temp. Only.

Usage Instructions

TB Series (BACnet) Thermostats:

  • Part# TB-24-C: 24 V, Temp. Only
  • Part# TB-24-HM-C: 24 V, Temp, Humidity, Motion
  • Part# TB-C: 110 – 220V, Temp. Only
  • Part# TB-24: TB-24-HM: TB
  • Communication: BACnet MS/TP (subordinate device) with baud rates up to 76.8 kbps
  • Power Requirements: Detected and set automatically by the thermostat

TM Series (MODBUS) Thermostats:

  • Part# TM-24: 24 V, Temp. Only
  • Communication: Modbus RTU (server) with baud rates up to 76.8 kbps
  • Power Requirements: Detected and set automatically by the thermostat

FAQ

Where can I find more information about the product?
For more information, contact your local Carrier Controls Expert. Visit the Controls Expert Locator at www.carrier.com/controls-experts.

INTRODUCTION

The Carrier TB and TM Series Thermostats are available in BACnet (TB series) or MODBUS (TM series) communication protocols and come with various options and features for a wide range of HVAC applications. The TB and TM Series thermostats offer either zone/room/building control or building management system (BMS) level control. Utilizing Carrier’s powerful i-Vu® building automation system’s platform, the user can be sure that each space has precision temperature control.

Key Features

  • Built-in temperature, humidity, and/or motion sensing for optimal control
  • Intuitive push-button interface with a clear LCD
  • BACnet or MODBUS communication protocol capable (depending on model) for flexible system integration
  • Configurable inputs and outputs to support a variety of HVAC applications
  • Real-time clock maintains accurate time for up to 7 days during power outages
  • Choice of 24VAC or 110-220V power supply for installation flexibility*

Applications

  • Fan (FCUs): Enhance occupant comfort by providing individual control over fan speed and temperature
  • Rooftop Units (RTUs): Optimize RTU operation for energy efficiency through precise temperature and airflow control
  • Heat Pumps: Maximize heat pump performance and efficiency with integrated control of heating and cooling modes
  • Variable Frequency Drives (VFDs): Seamlessly integrate with VFDs to fine-tune motor speeds and optimize energy consumption

Specifications

TB Series (BACnet) Part#
Options 24 V, Temp. Only 24 V, Temp, Humidity, Motion 110 – 220V, Temp. Only
Branded TB-24-C TB-24-HM-C TB-C
Unbranded TB-24 TB-24-HM TB
Communication BACnet MS/TP (subordinate device)

Baud rates up to 76.8 kbps are detected and set automatically by the thermostat.

TM Series (MODBUS) Part#
Options 24 V, Temp. Only 110 – 220V, Temp. Only
Unbranded TM-24 TM
Communication Modbus RTU (server)

Baud rates up to 76.8 kbps are detected and set automatically by the thermostat.

Power Requirements 24 VAC ± 15%

4VA no load, 76 VA Full Load

110-220 VAC
Display LCD
Sensing Element
Temperature Range: 41-95° (5-35°C), Accuracy: ± 1°F (0.5°C)
Humidity

Range: 10-90% Accuracy: ± 3% Typical

 

 

X

 

Motion

Sensor Type: PIR, quad, omnidirectional Distance: 16.4 ft. (5 m)

Detection Range: 90 x 30 (HxV)

Movement Speed:    2.62 – 3.94 ft/s (0.8 – 1.2 m/s)

Detection Object: 15.75 x 9.84 in. (400 x 250 mm)

 

 

 

 

X

 

 

Inputs T1, 0 – Normally Open (NO) or Normally Closed (NC) dry contract, or 0-10 Vdc AI, or 50 kOhm thermistor @ 77°F (25°C)

A, B – Communication +/- (RS485)

In1, 0 – NO or NC dry contract, or 0-10 Vdc AI, or 50 kOhm thermistor @ 77°F (25°C)

C, R – Power 24 VAC

Outputs 11, 12, 13 – DO, 3A

14 – DO 0.3A

15, 16 – DO 0.3A or AO 0-10 Vdc, 5 mA max., not isolated

Environmental Operating Range 50° to 122°F (10° to 50°C), 10 – 90% RH, non-condensing
Housing Square form factor, fire-retardant ABS plastic, UL94V-0
Mounting Installs to a standard wall box with mounting hardware included (consult technical instructions)
Compliance FCC CFR47, chapter 1, subchapter A, part 15, class B ICC, ICES-003, class B

CE Mark LVD, 2014/35/EU RoHS 2011/65/EU

C-Tick Mark, AS/NZS 61000-6-3

CA Prop. 65

Dimensions 3.62” W x 3.19” H x 0.91” D (9.2cm W x 8.1cm H x 2.3cm D)
Weight 4.8 oz (0.14 kg)

ABOUT COMPANY

  • For more information, contact your local Carrier Controls Expert. Controls Expert Locator: www.carrier.com/controls-experts
  • ©2025 Carrier. All Rights Reserved. Cat. No. 11-808-1163-01 Rev. 01/25
  • Manufacturer reserves the right to discontinue or change at any time, specifications, or designs, without notice and without incurring obligations. All trademarks and service marks referred to herein are the property of their respective owners.