Carrier MPW017-080 Multi Chiller Controller Accessory
Specifications
- Model: MPW017-080
- Part Number: 30MP70001401
- Chiller Capacity: 2 to 8 chillers
- Controller Type: TruVu controller board
- Energy Efficiency: Reduces system energy consumption at part-load operating conditions
Installation
Installation of the 30MP multi-chiller controller accessory should only be performed by trained, qualified installers and service technicians. Follow the safety precautions provided in the literature and labels attached to the equipment.
Configuring the Controller
To configure the controller, follow the instructions provided in the manual for setting up points, properties, and scheduling. This will ensure efficient operation of the chiller plant.
Sequence of Operation
The sequence of operation includes scheduling and condenser water temperature control. Ensure proper settings for optimal performance.
Troubleshooting
If any issues arise, refer to the troubleshooting section in the manual. Pay attention to LEDs for indications and follow guidelines for obtaining serial numbers.
FAQs
Q: Can untrained individuals install the controller accessory?
A: No, installation should only be done by trained, qualified installers and service technicians due to safety considerations.
Q: How many chillers can the 30MP multi-chiller controller control?
A: The controller can control 2 to 8 chillers as a single chiller plant.
Q: How does the controller improve energy efficiency?
A: The controller stages each chiller independently, reducing system energy consumption at part-load operating conditions.
“`
30MPA, MPW017-080 Multi-Chiller Controller Accessory
Installation Instructions
Part No. 30MP70001401
Installation of this accessory can be hazardous due to system pressures, electrical components, and equipment location (such as a roof or elevated structure). Only trained, qualified installers and service technicians should install, start-up, and service this equipment.
When installing this accessory, observe precautions in the literature, labels attached to the equipment, and any other safety precautions that apply:
· Follow all safety codes
· Wear safety glasses and work gloves
· Use care in handling and installing this accessory
It is important to recognize safety information. This is the safetyalert symbol: . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and service. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300273-01
Printed in U.S.A.
Form No. 30MP-6ASI
Pg 1
10-24
Replaces: 30MP-27SI
FCC Compliance
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
CAUTION
Changes or modifications not expressly approved by the responsible party for compliance could void the user’s authority to operate the equipment.
CE Compliance
This is a Class A product. In a domestic environment, this product may cause radio interference in which case the user may be required to take adequate measures.
BACnet1 Compliance
BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test products for compliance with ASHRAE standards. Compliance of listed products to requirements of ASHRAE Standard 135 is the responsibility of BACnet International.
GENERAL
The 30MP multi-chiller controller is a field-installed accessory kit that is used to control 2 to 8 chillers as a single chiller plant. The units are controlled by the TruVu controller board inside the accessory panel. The 30MP multi-chiller controller allows for efficient operation by staging each chiller independently. This reduces system energy consumption at part-load operating conditions.
1. Third-party trademarks and logos are the property of their respective owners.
The multi-chiller controller accessory includes Carrier’s TruVu ET® display, which is an integrated component of the i-Vu BAS (Building Automation System).
The multi-chiller controller accessory also contains a power converter and terminal strip in a NEMA type 1 enclosure, which can be wall mounted. The kit requires field-supplied 120 vac, 100 va incoming power. The enclosure has multiple knockouts sized from 1/2 to 1-1/2 in. which allows for wiring to the terminal strip.
The following field-supplied items are required for installation:
· Varnish cloth
· Wire (22 AWG [American Wire Gauge], low capacitance, twisted, stranded, and shielded copper wire). Length should be up to 2000 ft to daisy chain all 30MP chillers to the multi-chiller controller panel from their desired location.
All field wiring should be connected to the terminal strip supplied in the 30MP multi-chiller controller accessory panel.
The TruVu controller board communicates to each legacy 30MP chiller via the UPC Open BACnet Communication Module. The TruVu controller communicates with the new 30MP chillers through a PIC6.1 controller which uses network points over an MS/TP network.
It is necessary to connect the 30MP multi-chiller controller accessory panel and each UPC Open module or PIC6.1 module on an MS/TP network segment. The PIC6.1 chiller can also communicate over IP with the TruVu controller. All wiring is field supplied.
For a description of LEDs, switches, jumpers, connection ports, and terminators on the UPC Open Interface, see Fig. 1.
For an example of how to wire the 30MP multi-chiller accessory panel (UPC Open module and PIC6.1 controller) to the BACnet Communication Module on each 30MP chiller, see Fig. 2 and 3.
If the TruVu controller is at either end of the network segment, set the End of Net to YES (which applies network termination and bias).
The UPC Open module is located behind the low voltage terminal block (LVT) in each 30MP chiller control panel. See Fig. 4. For PIC6.1 controller with the J10 connector see Fig. 5.
BT485 Terminator
MS/TP Communication Wiring
Tx1 LED Rx1 LED
Tx2 LED Rx2 LED
EIA-485 Jumpers
Power LED
45 45
BACnet
Baud Rate
6 789
Dip Switches
01 01
6 789
Address Rotary
Switches
23 23
Run LED Error LED
Fig. 1 — UPC Open Interface Details 2
Terminal Block, TB1 on 30MP Multi-Chiller Controller Accessory Panel BACnet Communication Modules Located In Each 30MP Chiller
Port S1 NET + 21 NET – 22 Shield 23
TB1
BT485 NET + NET Shield
BT485 NET + NET Shield
BT485 NET + NET Shield
Fig. 2 — MS/TP Network Daisy Chain Configuration (UPC)
Terminal Block, TB1 on 30MP Multi-Chiller Controller Accessory Panel BACnet Communication Modules Located In Each 30MP Chiller
Port S1 NET+ 21 NET- 22 Shield 23
TB1
J10 J10 J10
+ c –
+ c –
+ c –
NOTE: Ground (G) represents C.
Fig. 3 — MS/TP Network Daisy Chain Configuration (PIC6.1)
3
UPC Open Module
30MP Control Panel
Fig. 4 — Location of the UPC Open Module Within the 30MP Control Panel
J10 Connector
Fig. 5 — PIC6.1 Controller (J10 Connector) Within 30MP Control Panel 4
INSTALLATION
Prerequisites
Prior to installation ensure that:
· Each legacy 30MP chiller is equipped with a UPC Open module. Legacy chillers are unit sizes 016, 020, 030, 032, 040, 045, 050, 055, 060, 065, and 070.
· New 30MP chillers are equipped with a PIC6.1 controller. Unit sizes 017, 021, 031, 033, 041, 046, 051, 056, 066, and 080 use the PIC6.1 controller.
· All 30MP chiller units must be the same type (air-cooled or water-cooled). If one unit is air-cooled, all other units must be air-cooled and vice versa.
Step 1 — Inspect Shipment
Inspect the contents of the accessory package before installing. File a claim with the shipper if shipping damage is found or contact your Carrier representative if any parts are missing. See Table 1 for accessory kit package contents.
Table 1 — Package Contents
DESCRIPTION Control Box Assembly Thermistor Well
QUANTITY 1 1 1
PART NUMBER —
HH79NZ029 10HB50106802
Step 2 — Position and Mount the Panel
The 30MP multi-chiller controller accessory panel can be wall mounted using (4) 1/4 in. screws. Select the proper location for the 30MP multi-chiller controller accessory panel. Ensure the location provides access to the required power wiring, wiring to the common water manifold temperature thermistor, and is able to be wired to the MS/TP network in a daisy chain with the 30MP chillers. The panel requires 120 vac (100 va) single phase incoming power.
NOTE: The maximum terminal strip torque is 7.52 in-lb. The terminal strip accepts incoming wire size 12 to 22 AWG.
Step 3 — Make Electrical Connections
To wire for power:
1. Open fuse block (FB1) to remove power from the power supply.
2. Select the appropriate knockout for incoming power wiring, and connect line side power wiring to the L1 terminal on the fuse block (FB1) and the neutral terminal (NEU) on the terminal block (TB1). Connect the ground wire to the ground terminal (GND) on terminal block TB1. See 30MP multichiller controller wiring diagram provided inside the accessory panel.
3. Restore power to the power supply and verify that the Power LED is on (in the controller module). See Fig. 6 for Power LED location.
Step 4 — Address Controllers
For PIC6.1 controller and UPC Open module:
· Equal sized chillers: There are no special staging or addressing guidelines.
· Unequal sized chillers: Carefully implement the following staging and addressing instructions for optimal water temperature control and part-load efficiency. See Tables 2 and 3 for correct unit ordering.
Table 2 — Chiller Addressing
CHILLER ORDER
CH-1 CH-2 CH-3 CH-4 CH-5 CH-6 CH-7 CH-8
UPC OPEN ADDRESS
01 02 03 04 05 06 07 08
PIC6.1 ADDRESS
01 02 03 04 05 06 07 08
Table 3 — Chiller Size Ordering
CHILLER ORDER
First Chiller
Last Chiller
30MP MODEL SIZES
017 021 041 046 031 033 051 056 066 — 080
30MP LEGACY MODEL SIZES
016 020 030 032 040 045 050 055 060 065 070
Power
MUC Board
5
Fig. 6 — LED Locations
SETUP PIC6.1 CONTROLLERS
1. Login as Factory in order to see Configuration in the Main Menu. See Table 4 for factory configurations.
2. Press the home button to get back to the main screen. Login as Factory in the Main Menu. See Table 5 for PIC6.1 BACnet configuration.
3. Once all BACnet parameters are set press the Unit Start/Stop button, then select Network. When this is complete the
TruVu controller is ready to control the chillers. See Fig. 7.
Fig. 7 — Unit Start/Stop Screen
Table 4 — PIC6.1 Configuration — Factory Parameters
(Factory Main Menu Configuration Factory Parameters)
SCREEN 4
Enable Liquid Line Valve
[No]/YesEnable Head Press Act A
[No]/YesEnable Evap Isolator Rel
[No]/YesLeakage Charge Detection
[No]/YesEnable BACNet Option
No/[Yes]a
NOTE(S):
a. Item requires configuration.
ADDRESS THE UPC OPEN MODULES
Address and configure the chiller system before starting the multichiller controller, which supports a maximum of 8 chillers. These steps enable the controller to communicate with each individual chiller through their corresponding UPC Open module.
Once the system is powered and operating, the TruVu controller reads the type and size of each chiller and automatically configures any additional features (such as hot gas bypass) that could impact machine staging or sequencing.
Chillers should be addressed with MAC address 01 to 08. To address a UPC controller use the rotary switches (see Fig. 8):
Perform the following procedure to assign an address:
1. Set the Tens (10’s) switch to the tens digit of the address.
2. Set the Ones (1’s) switch to the ones digit.
For example, if the controller’s address is 25, point the arrow on the Tens (10’s) switch to 2 and the arrow on the Ones (1’s) switch to 5 as shown in Fig. 8.
Table 5 — PIC6.1 Configuration — BACnet Parametersa
(Factory Main Menu Configuration Network Menu BACnet Parameters)
Screen 1
BACnet Enable Option
2b
0 — Disabled
1 — BACnet IP
2 — BACnet MSTP
Metric Units?
[No]/YesScreen 2
Network
16101b
UDP Port Numbers
47808
Device ID Manual
161010xb
Device ID Auto Option
[Disable]/ EnablebAlarm Reporting
Disable/ [Enable]
Screen 3
BACnet Manage Occupancy
[No]/YesIP Port Interface Name
0
0=J5/J15
1=J16
BACnet MS/TP MAC Address
xb
Screen 4
BACnet MS/TP Baud Rate
4b
0=9600
1=19200
2=38400
3=57600
Screen 5
3=57600
4=76800
5=115200
BACnet MS/TP Max Master
127
MS/TP Max Info Frames
10
NOTE(S):
a. X represents chiller number. Example: Chiller1 x would be 1, Chiller2, x would be 2.
b. Item requires configuration.
6
BT485 TERMINATOR
BACNET CONNECTION (BAS PORT)
Tx1 LED Rx1 LED
Tx2 LED Rx2 LED
EIA-485 JUMPERS
45
POWER LED
ON
OFF
8
7
6 5 4
3 2
1
6 789
45
6 789
01
BACNET BAUD RATE DIP SWITCHES
ON
8
7 6 5 4 3 2
1
OFF
Address Dip Switches
6 78 9 10’s
45
01
01
RUN LED ERROR LED
6 789
1’s
23
23
23 23
45
01
Address Rotary Switches
Fig. 8 — Setting the Address Rotary Switches on the UPC Open Module (Inside 30MP Chiller)
Step 5 — Wire the MS/TP Network
When wiring the MS/TP network follow the procedure below:
1. The TruVu controller communicates with each chiller using BACnet communication on an MS/TP network. The factory default setting for the controller, UPC Open module and, PIC6.1 controller are 76.8 kbps. It is recommended to use the default baud rate.
NOTE: The TruVu controller, UPC Open modules (located in each 30MP chiller), and PIC6.1 controllers must be set to the same baud rate. For BACnet baud rate dip switch locations refer to Fig. 8. Switches 1,2, and 4 must be set to the ON position. Switches 3,5,6,7, and 8 should be set to the OFF position. Refer to Table 5 for setting the baud rate of the PIC6.1 controllers. The TruVu controller will already be configured for 76.8 kbps.
NOTE: The CCN (Carrier Comfort Network®) baud rate on each 30MP chiller must also be set to the same baud rate as the TruVu controller and all UPC Open modules in each chiller or PIC6.1 controller.
2. Wire the multi-chiller controller accessory panel, with the UPC Open module or, PIC6.1 controller in each 30MP chiller on an MS/TP network segment in a daisy-chain configuration (refer to Fig. 2 and 3). A BT485 terminator in the UPC module is a signal biaser that adds bias and prevents signal distortions due to echoing.
3. In the multi-chiller controller panel, connect the MS/TP communication wires to terminals 21, 22, and 23 on the terminal block. See “Typical Wiring Schematic” on page 9.
Step 6 — Wire the TruVu Controller to the Network
To wire the TruVu controller to the network:
1. Open the fuse block (FB1) to remove power to the controller.
2. Check the communications wiring for shorts and grounds.
3. Connect the communications wiring to terminals 21, 22, and 23 on the terminal block (if not already done). See “Typical Wiring Schematic” on page 9.
4. Verify that the end of the Net switch is in the up position (YES) on the TruVu controller.
When installation is complete, restore power to the power supply, in the 30MP multi-chiller controller accessory panel.
Step 7 — Wire the Inputs and Outputs
The multi-chiller controller requires a 5k ohm common leaving water temperature thermistor. Included in the accessory package is the 5k ohm thermistor (P/N HH79NZ029) with a 4 in. immersion well (P/N 10HB50106802). See Fig. 9 for dimensions.
A B
0.505/0.495
0.61 DIA
1/4 N.P.T.
PART NUMBER 10HB50106802
6″ Minimum Clearance For
Thermistor Removal
DIMENSIONS — in. (mm)
A
B
4.10 (104.1)
1.28 (32.5)
Fig. 9 — Thermistor Well Dimensions
7
Install the thermistor well on the chilled and /or hot water supply, downstream of the last chiller as shown in Fig. 10. Water flows to the evaporator for cooling and to the condenser for heating.
Connect the thermistor leads to terminals 13 and 14 for chilled water on the terminal block (TB1) in the multi-chiller controller accessory panel.
Connect the thermistor leads to terminals 7 and 8 for hot water on the terminal block (TB1) in the multi-chiller controller accessory panel.
Tables 6 and 7 show each available output and input. All connections are made at the terminal block (TB1) in the 30MP multichiller controller accessory panel. See Fig. 11.
T
Common Leaving Water Temperature
30MP Multi-Unit Control Panel
30MP Chiller
STRAINER
Control Box
Control Box
MS/TP Network Wiring
30MP Chiller
Control Box
30MP Chiller
Fig. 10 — Common Leaving Water Temp Sensor Location
To wire inputs and outputs, connect to the appropriate landings on the terminal block (TB1) in the 30MP multi-chiller controller accessory panel. See Fig. 11 for the typical wiring schematic and Table 8 for input wiring specifications. Each output is a dry contact rated at 1 A, 24-v maximum and is normally open. To size output wiring, consider the following: · Total loop distance from the power supply to the control-
ler, and then to the controlled device. NOTE: Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length. · Acceptable voltage drop in the wire from the controller to the controlled device. · Resistance (ohms) of the chosen wire gauge. · Maximum current (amps) the controlled device requires to operate.
Table 6 — Available Outputs
AVAILABLE OUTPUT
Tower Fan Speed
Alarm Lamp
OUTPUT TERMINAL
(TB1)
4
5
GND TERMINAL
(TB1)
HARDWARE / SIGNAL
3
0-10 vdc
6
Relay
NOTE
Optional Optional
Table 7 — Available Inputs
AVAILABLE INPUT
Relative Humidity Sensor
External Analog Setpoint
Outdoor Air Temperature Sensora
Leaving Chilled Water Header Temperature
Leaving Hot Water Header Temperature
External Demand Limit
Remote Occupancy Contact
INPUT TERMINAL
(TB1) 20 17 16
13
7
12 9
GND TERMINAL
(TB1) 19 18 15
14
8
11 10
HARDWARE SIGNAL 0-5 vdc 0-5 vdc 10k
Thermistor
5k Thermistor
5k Thermistor
Dry Contact Dry Contact
NOTE
Optional
Optional
Optional
Required (if making chilled water)
Required (if making hot
water)
Optional
Optional
NOTE(S):
a. Use this input to reset leaving chilled or hot water temperature based on outdoor air temperature.
Table 8 — Input Shielded Wiring Specifications
INPUT
0-5 vdc 0-10 vdc
Thermistor Dry Contact Pulse Counter (TLO)
TruVu ET Device
MAXIMUM LENGTH (ft) 1000
1000
500
MINIMUM GAUGE (AWG) 26
22
22
LEGEND
AWG — American Wire Gauge TLO — Timed Local Override
IMPORTANT: Connect the shield wire to the terminal with the ground wire. Do not connect the shield wire at the other end of cable as this will cause a ground loop error.
8
9
Fig. 11 — Typical Wiring Schematic
Step 8 — Wire Sensors to the 30MP Multi-Chiller Controller Accessory Panel
Connect the following sensors: · Leaving chilled water header temperature (required if
making chiller water) · Leaving hot water header temperature (required if making
hot water) · Outdoor air temperature (optional) · Relative humidity (optional) NOTE: This document gives instructions for wiring the sensors to the controller. Table 8 shows the type and gauge of wire to use when wiring sensors to the controller. For mounting and wiring the sensors, see the Carrier Sensors Installation Guide.
WARNING
Disconnect electrical power to the controller before wiring it. Failure to follow this warning could cause electrical shock, personal injury, or damage to the controller.
CAUTION
Do not run sensor or relay wires in the same conduit or raceway with Class 1 AC or DC service wiring. Do not abrade, cut, or nick the outer jacket of the cable. Do not pull or draw cable with a force that may harm the physical or electrical properties. Avoid splices in any control wiring. Failure to follow these cautions may result in damage to the controller.
WIRING THE LEAVING CHILLED WATER HEADER TEMPERATURE SENSOR TO THE CONTROLLER 1. Strip the outer jacket from the cable for at least 4 in.
(10.2 cm). Strip .25 in. (.6 cm) of insulation from each wire. 2. Wire the sensor to the 30MP multi-chiller controller acces-
sory panel. Refer to Fig. 11. Sensor must be terminated at Terminals 13 and 14 of TB1. 3. Apply power and verify sensor readings.
WIRING THE LEAVING HOT WATER HEADER TEMPERATURE SENSOR TO THE CONTROLLER 1. Strip the outer jacket from the cable for at least 4 in.
(10.2 cm). Strip .25 in. (.6 cm) of insulation from each wire. 2. Wire the sensor to the 30MP multi-chiller controller acces-
sory panel. Refer to Fig. 11. Sensor must be terminated at Terminals 7 and 8 of TB1. 3. Apply power and verify sensor readings.
WIRING AN OUTDOOR AIR TEMPERATURE SENSOR (PART NO. 33ZCSENOAT) An optional outdoor air temperature (OAT) sensor may be used to provide a reset of the chilled and/or hot water setpoint adjustment based on the OAT reset. To wire an outdoor air temperature sensor to the controller: 1. Strip the outer jacket from the cable for at least 4 in. Strip
.25 in. (.6 cm) of insulation from each wire. 2. Wire the sensor to the controller. Refer to Fig. 11. Sensor
must be terminated at terminals 15 and 16. 3. Apply power and verify sensor readings.
WIRING A RELATIVE HUMIDITY SENSOR — WALL AND DUCT SENSOR (PART NO. 33ZCSENSRH-02)
Use the optional relative humidity (RH) sensor to override the OAT reset in order to provide better humidity control.
NOTE: The RH override requires that the OAT sensor is installed and OAT reset function is enabled and active. Otherwise, there is only the RH sensor monitoring and alarming.
To wire the RH sensor to the controller:
1. Strip the outer jacket from the cable for at least 4 in. (10.2 cm). Strip .25 in. (.6 cm) of insulation from each wire.
2. Wire the sensor (P/N 33ZCSENSRH-02). Refer to Fig. 11. It must be terminated at terminals 19 and 20. Use terminal 2 on TB1 to connect the 24vdc+ to the sensor.
3. Apply power and verify sensor readings.
CONFIGURING THE CONTROLLER
Configuring Points and Properties
To start up the controller, it is necessary to configure certain points and properties. See Appendix C “30MP MULTI-CHILLER POINTS/PROPERTIES” on page 17 for a list of points and properties, with descriptions, defaults, and ranges. These properties affect the unit operation and/or control. Review and understand the meaning and purpose of each property before changing it. NOTE: The controller does not support metric units of measure.
To start up the controller, configure necessary points and properties in the following order:
1. Set the Unit Configuration.
2. Set the Chilled Water or Hot Water Setpoint.
3. Set the Control Point for entering or leaving water temperature.
4. Set the controller for all chillers (either UPC Open module or PIC6.1 controller).
5. To start the plant, set the Occupancy Status to Occupied.
SEQUENCE OF OPERATION
The multi-chiller controller sequences chillers in order to maintain the desired water temperature setpoint. The controller can be configured to maintain supply or return water temperature.
Whenever the controller is in an occupied mode, the water temperature sensor is compared to the desired setpoint. If the water temperature sensor value is above the setpoint (for chilled water), then a PID will calculate how much additional capacity is required. If the water temperature sensor value is below the setpoint (for hot water), then a PID will calculate how much additional capacity is required. The minimum amount of chillers is defined by the parameter Minimum Number of Chillers to Run. See Appendix C, Table F “Service Configuration” on page 22 for number of chillers required. If the current number of chillers is less than the minimum number, then the chillers are started every 30 seconds until the minimum number is reached. Thereafter, additional stages are added subject to the configured ACR Timer delay time.
As each chiller is started, it is limited to its first stage of capacity until all available chillers are operating. Once all machines are operating at minimum capacity, if additional capacity is required, any 3-stage machine is loaded to 2 stages next, until all 3-stage machines are loaded to that capacity. If that level is reached and still further capacity is needed, then all machines are sequentially loaded until every machine is operating at 100% capacity. This sequence provides the most efficient operation of multiple chillers.
As the load decreases and the required capacity is reduced, the reverse cycle occurs. All machines are reduced by one stage to either 50% or 67%, depending on the number of machine stages.
10
As a further capacity reduction is needed, the second stage of any 3-stage machine is dropped until only one stage is operating per machine. As further reduction is needed, the first stage is dropped on each machine in the opposite order of the chiller sequence. NOTE: Dropping any stage is subject to the RCR Timer delay time between stages.
Additionally, if only one stage is operating per machine and any machines are equipped with hot gas bypass, the hot gas is used to maintain the desired water temperature, while waiting for the RCR Timer delay to expire, in order to further reduce capacity. Hot gas bypass provides improved water temperature control under light load conditions and prevents excessive chiller start/stop cycles.
The controlling setpoint for chilled water is calculated based on the following settings:
1. Configure Chilled Water Setpoint for the desired water temperature.
2. Use Cooling Setpoint OAT Reset to increase the water temperature setpoint as a function of the outdoor air temperature. NOTE: An OAT sensor is required to use this feature.
3. Use RH Cooling Setpoint Reset to reduce any calculated OA reset if a high humidity condition occurs.This usually happens under light load at lower OAT. NOTE: An RH sensor is required to use this feature.
The controlling setpoint for hot water is calculated based on the following settings:
1. Configure Hot Water Setpoint for the desired water temperature.
2. Use Heating Setpoint OAT Reset to decrease the water temperature setpoint as a function of the outdoor air temperature. NOTE: An OAT sensor is required to use this feature.
Scheduling
To use an occupancy schedule, configure time periods to schedule the transitions from occupied to unoccupied operation. The controller maintains the desired water setpoint when occupied and disables the chiller when unoccupied. The controller defaults to using the BAS (Building Automation System) On/Off point, which is factory set to Inactive. The unit will stay unoccupied until a Time Schedule is configured or a third-party control system Enables/Disables the BAS On/Off point. Set the local time and date for these functions to operate properly.
It is possible to change the occupancy source to one of the following:
OCCUPANCY SCHEDULES
The controller is occupied 24/7 until the time schedule is configured using the TruVu ET Display, Field Assistant, the i-Vu® application, or until a third-party control system Enables/Disables the BAS On/Off point. Disable this by going to (Configuration Unit Configuration Occupancy Schedules) and changing the point from Enable to Disable and clicking OK.
NOTE: Enable this point in order for the TruVu ET Display, Field Assistant, or the i-Vu® application to assign a time schedule to the controller.
SCHEDULE
The unit operates according to the schedule configured and stored in the unit. The schedule is accessible in the TruVu ET Display, Field Assistant, or the i-Vu application. The daily schedule consists of a start and stop time (standard or 24 hour mode) and seven days of the week, starting with Monday and ending on Sunday.
OCCUPANCY INPUT CONTACT (OPTIONAL)
If configured for remote occupancy control (default), the controller can use an external dry contact closure connected to terminals 9 and 10 on TB1, to determine the occupancy status of the unit. Disable the Occupancy Schedules to use the occupancy contact input.
NOTE: Scheduling can only be controlled from one source.
BAS (BUILDING AUTOMATION SYSTEM) ON/OFF
For use with a Building Automation System that supports network scheduling, disable the Occupancy Schedules so the BAS can control the unit through a network communication and the BAS scheduling function.
NOTE: Scheduling can either be controlled from the unit or the BAS, but not both.
SYSTEM OCCUPANCY
Uses the network to obtain an occupancy status value from another controller, which is read over the network and used by this controller. Occupancy Schedules MUST be set to Disable to use this function.
NOTE: Scheduling can only be controlled from one source.
Demand Limiting
The multi-chiller controller can provide up to 3 stages of demand limiting, if connected to an electric metering program indicating that demand limiting is required.
Demand limiting works using 2 different methods. The first connects the BACnet network input point System Cool/Heat Demand Level to the electric metering program, to send a value for the demand level. The second method is a binary input point IN-5 Extended Demand Limit that sets the demand level to 2 when the input is active.
CHILLED WATER
Demand Level 1, called the red line limit, sets the maximum chiller capacity to the current operating capacity, so that no additional capacity can be added. This prevents further increase in demand, although it will not prevent any necessary capacity reduction.
Demand levels 2 and 3 provide an adjustment to the operating setpoint. Demand level 2 occurs when System Cool Demand Level is set to 2 or the Extended Demand Limit input is active. This increases the chilled water setpoint by the configured Demand Level 2 Cool Adjustment amount. Demand Level 3 occurs when System Cool Demand Level is set to 3. This increases the chilled water setpoint by the configured Demand Level 3 Cool Adjustment amount. If the System Cool Demand Level is set to 0 and the IN-5 Extended Demand Limit is inactive, then there is no demand limiting.
HOT WATER
Demand Level 1, called the red line limit, sets the maximum chiller capacity to the current operating capacity, so that no additional capacity can be added. This prevents further increase in demand, although it will not prevent any necessary capacity reduction.
Demand levels 2 and 3 provide an adjustment to the operating setpoint. Demand level 2 occurs when System Heat Demand Level is set to 2 or the Extended Demand Limit input is active. This decreases the hot water setpoint by the configured Demand Level 2 Heat Adjustment amount. Demand Level 3 occurs when System Heat Demand Level is set to 3. This decreases the hot water setpoint by the configured Demand Level 3 Heat Adjustment amount. If the System Heat Demand Level is set to 0 and the IN-5 Extended Demand Limit is inactive, then there is no demand limiting.
11
OA (Outdoor Air) Reset
CHILLED WATER
It is possible to raise the water temperature setpoint as a function of the outdoor air temperature. Set the Cooling Setpoint OA Reset to Enable, then as the OA temperature drops below the OAT CHW Supply Reset High Limit, the water temperature setpoint increases proportionally between OAT CHW Supply Reset High Limit and OAT CHW Supply Reset Low Limit. At OAT CHW Supply Reset Low Limit, the maximum reset amount and maximum OA CHW Reset, is added to the configured water temperature setpoint.
If Cooling Setpoint OA Reset is set to Disable, then the configured water temperature setpoint is used.
HOT WATER
It is possible to lower the water temperature setpoint as a function of the outdoor air temperature. Set the Heating Setpoint OA Reset to Enable, then as the OA temperature rises above the OAT HW Supply Reset Low Limit, the water temperature setpoint decreases proportionally between OAT HW Supply Reset Low Limit and OAT HW Supply Reset High Limit. At OAT HW Supply Reset Low Limit, the maximum reset amount and maximum OA HW Reset, is added to the configured water temperature setpoint.
If Heating Setpoint OA Reset is set to Disable, then the configured water temperature setpoint is used.
RH (Relative Humidity) Cooling Reset
The multi-chiller controller can reduce any calculated OA reset, if the sensed relative humidity is above the control setpoint. Set the RH Cooling Setpoint Reset to Enable, as the RH increases above the Occupied Relative Humidity Setpoint, a PID (Proportional Integral Derivative Loop) calculates the amount of reduction in the OA reset value. RH Cooling Setpoint Reset is only applicable if the OA reset is active, since it can only reduce what is calculated by that algorithm. RH Cooling Setpoint Reset will NOT lower the water temperature setpoint below the user-defined Chilled Water Setpoint value.
If the RH Cooling Setpoint Reset is set to Disable, then the configured Chilled Water Setpoint, plus any calculated OA reset, is the controlling setpoint.
Power Failure Recovery
The controller has a Power Fail Restart Delay for after a power loss. The amount of time can be configured in seconds, up to 600. When the power returns, the controller prevents operating and starting any chillers for that amount of time.
The controller can also immediately restart the prior number of operating chillers in their previous capacity, if the duration of a power outage was less than the configured Immediate Restart Time in minutes. The plant returns to capacity quickly if there is a short outage and prevents waiting to load the plant at the ACR (Additional Capacity Required) rate. This feature adds stages every 30 seconds until the previously operating plant capacity is reached.
Cool Enable
The controller can prevent chiller operation if the OAT is below an adjustable OA temperature. If Cool Enable is set to Enable and there is a valid OA temperature and if the OA temperature is greater than the Cooling Lockout Temperature, the controller actively controls the chillers as required. If the OA temperature falls below the configured lockout value of 45°F, then all chillers are disabled.
Heat Enable
The controller can prevent chiller operation if the OAT is above an adjustable OA temperature. If Heat Enable is set to Enable and there is a valid OA temperature and if the OA temperature is less than the Heating Lockout Temperature, the controller actively controls the chillers as required. If the OA temperature rises above the configured lockout value of 65°F, then all chillers are disabled.
Rotation Method
The multi-chiller controller can rotate chillers based on several different methods. Rotation is only available with equal sized units. Set the rotation method using Rotation Method Sequence, and selecting Never, Daily, Weekly, Monthly, Manual, Runtime, or Runtime Equalization. The default and preferred method is Runtime Equalization, as it rotates the least-used machine to the lead position, but only when machines are started, so that no additional start/stop cycles are incurred.
For unequal-sized chillers, the staging sequence is dependent on the actual machine size and should not be altered, in order to provide the best water temperature control. For unequal-sized machines no rotation method is available, see Appendix C, Table C on page 19.
Analog Setpoint Input
The controller has an analog input channel used for an external setpoint input. The external setpoint input range depends on whether the connected chillers are brine or water. Channel IN-2 is used for external setpoint input and the range is 1 to 5 vdc.
· For water chillers, the range is proportional from 1 to 5 volts where 1 volt = 40°F and 5 volts = 65°F.
· For brine chillers, the range is proportional from 1 to 5 volts where 1 volt = 20°F and 5 volts = 45°F.
· For hot water chillers, the range is proportional from 1 to 5 volts where 1 volt=80°F and 5 volts=140°F.
NOTE: The lowest allowable setpoint is determined by the highest freeze setpoint of any machine connected to the controller.
Condenser Water Temperature Control (Tower Fan)
The controller has an analog output channel used to operate a cooling tower fan. The control reads the condenser water temperature from the 30MP chiller UPC Open or PIC6.1 controller. To accomplish this, the first chiller (CH1) must have the condenser water temperature sensor option and must have a valid status (Off and Available or CCN Mode and Running). If that chiller status is invalid, the control will check sequentially for the next available chiller (CH2-CH8). Installing the CWT option on at least the first two chillers is strongly recommended. It is possible to configure channel AO-2 to provide a 2 to 10 vdc or 0 to 10 vdc signal to control a tower fan VFD (variable frequency drive).
If an external control system is available, it can be used with the multi-chiller controller to provide the optimum tower setpoint value to the external control. A network-accessible analog value point or condenser water setpoint, can provide the desired condenser water temperature setpoint in degrees Fahrenheit.
12
30MP UPC Open Chiller Linkage
The multi-chiller controller receives and sends information to UPC through 30MP chiller linkage. It reads the following from each machine, as applicable:
· Alarm state
· Compressor relay state
· Compressor sizes
· Evaporator entering water temperature
· Evaporator leaving water temperature
· Machine runtime
· Mode
· Freeze setpoint
· Hot gas bypass
· Type of chiller (air-cooled or water-cooled, brine or water)
The display is automatically updated to reflect the actual machine type and the proper setpoint range, if the external analog input is used.
The chiller linkage sends each chiller a control setpoint, enable command, and demand limit value. By transferring data between the multi-chiller controller and each chiller, the controller automatically configures each machine and then sends and receives data. This operates the system properly and meets the desired chilled water setpoint by commanding each individual 30MP chiller to run as necessary. The operating mode, hot gas valve status, and entering and leaving water temperatures are displayed on the graphic, along with other information.
30MP PIC6.1 System Points
The multi-chiller controller receives and sends information to the PIC6.1 controller through System Points. It reads the following from each machine, as applicable:
· Alarm state
· Compressor relay state
· Compressor sizes
· Condenser entering water temperature
· Condenser leaving water temperature
· Condenser water temperature
· Entering water temperature
· Freeze setpoint
· Hot gas bypass
· Heat/Cool status
· Leaving water temperature
· Machine runtime
· Mode
· Type of chiller (air-cooled or water-cooled, brine or water)
The display is automatically updated to reflect the actual machine type and the proper setpoint range, if the external analog input is used.
The System Points send each chiller a heat/cool mode, control setpoint, enable command, and demand limit values. By transferring data between the multi-chiller controller and each chiller, the controller automatically configures each machine and then sends and receives data. This operates the system properly and meets the desired chilled water setpoint by commanding each individual 30MP chiller to run as necessary. The operating mode, hot gas valve status, and entering and leaving water temperatures are displayed on the graphic, along with other information.
TROUBLESHOOTING
LEDs
The LEDs indicate if the controller is speaking to the devices on the network. The LEDs should reflect communication traffic based on the baud rate set. The higher the baud rate the more solid the LEDs become.
Verify the LED patterns by cycling power to the controller and noting the lights and flashes. Tables 9 and 10 show the LED description and the error status. See Fig. 12 for indicator status.
See Tables 9 and 10
Fig. 12 — LED Indicator
Table 9 — LED Description
LEDs
STATUS
Lights when power is being supplied to the controller.
NOTE: The controller is protected by internal solid-state
Power
Polyswitches on the incoming power and network connections. These Polyswitches are not replaceable, but they will reset
themselves if the condition that caused the fault returns to
normal.
Rx
Lights when the controller receives data from the network segment; there is an Rx LED for Ports S1, ETH0, and ETH1.
Lights when the controller transmits data to the network
Tx
segment; there is an Rx LED for Ports S1 and 2, ETH0, and
ETH1.
Net LED to show Network status.
Sys LED to show Controller status.
Output Indicates status of each output.
Prog LED is customizable.
LEGEND
Prog — Rx — Sys — Tx —
Programmable Indicator Receiving Data System Status Transmitting
13
How to Obtain Serial Number (TV-UC683T)
The controller’s serial number is on a sticker on the back of the main controller board. If you need the controller’s serial number when troubleshooting, the number is on:
· A Module Status report (Modstat) under Core or Main board Hardware. See Fig. 13.
· A QR code, serial number, and MAC address printed on a sticker on the cover.
· A laser-etched number and QR code on the inside circuit board.
Fig. 13 — Serial Number Sticker
Table 10 — LED Error Status Troubleshooting
COLOR
RED
RED
BLUE
BLUE BLUE BLUE
BLUE GREEN MAGENTA
WHITE
RED RED RED GREEN GREEN GREEN GREEN BLUE BLUE BLUE
MAGENTA
WHITE
PATTERN
On
1 blink
On
1 blink 2 blink 3 blink
4 blink On
1 blink every second for 15 s
2 blink 4 blink Fast blink 1 blink 2 blink 3 blink Fast blink
On Slow blink Fast blink
1 blink every second for 15 s
CONDITION
MESSAGE IN MODULE STATUS
POSSIBLE SOLUTIONS
NET (Network Status) Tricolor LED
Ethernet connection problem.
No Ethernet Link.
Connect Ethernet Cable. Check other network components.
One of the following BACnet/IP (Ethernet) DLL reporting issue: Unable to create tasks. Unable to open socket for BACnet port.
BACnet/IP error.
Cycle power.
One of the following issues: Port communication firmware did not load properly. Port communication firmware is not running. Invalid protocol selected.
MSTP firmware error.
Change protocol using USB Service Port. Cycle power.
Invalid address selected for protocol.
Invalid address selection for MS/TP.
Change MAC address to unique address using USB Service Port.
Controller has same MAC address as another connected device.
Duplicate address on MS/TP.
Change MAC address to a unique value using USB Service Port to valid address.
Controller is the only device on the network.
No other devices detected on MS/TP.
Check that network cable is connected properly. Check that baud rate is correct.
Check that network cable is connected Excessive errors detected over 3 second period. Excessive communication errors on MS/TP. properly.
Check that baud rate is correct.
All enabled networks are functioning properly. No errors.
No action required.
Operating system changes are downloading.
WARNING: This process could take several minutes. Do NOT power off the controller during
N/A
the download.
No action required.
The Blink button on the controller setup Local Network tab has been pressed.
N/A
No action required.
SYS (System Status) LED
Restarting after an abnormal exit.
Auto restart delay due to system error on After 5 minute delay has expired, if
startup.
condition occurs again then cycle power.
Firmware image is corrupt.
Firmware error.
Download driver again.
Firmware error has caused the firmware to exit and restart.
Fatal error detected.
No action required.
No errors.
Operational.
No action required.
Download of driver is in progress.
Download in progress.
No action required.
BACnet Device ID is not set.
Download required.
Download the controller.
Installation of recently downloaded driver is occurring.
N/A
No action required.
Controller is starting up.
N/A
No action required.
Linux (operating system) is starting up.
N/A
No action required.
Linux is running but it could not start the firmware application.
N/A
Download driver.
Operating system changes are downloading.
WARNING: This process could take several minutes. Do NOT power off the controller during
N/A
the download.
No action required.
The Blink button on the controller setup Local Network tab has been pressed.
N/A
No action required.
14
APPENDIX A — MULTI-CHILLER WIRE LIST
Project Name: Location:
Point/ Cable Inputs (+)
IN-1
Terminal (TB1)
20
IN-2
17
IN-3
16
IN-4
13
IN-5
12
IN-6
9
IN-7
7
IN-8 Point/ Cable Outputs (+)
UO-1
Terminal (TB1)
AO-2
4
AO-3
BO-2
5
BO-3
BO-4
BO-5
BO-6
LEGEND
AO — Analog Output BO — Binary Output UO — Universal Output
SYSTEM NETWORK – 30MP MULTI-CHILLER
Controller: Network Number: MAC Address:
(G)
Terminal (TB1)
Input Type Sensor Code Equipment Name
Gnd
19
0-5 vdc
RH Sensor
Point Name
Gnd Gnd Gnd Gnd Gnd Gnd Gnd COM Gnd
18
0-5 vdc
AI Setpoint
15
10K OHM Therm.
14
5K OHM Therm.
OAT Sensor
Leaving Chilled Water Header Temperature
11
Dry Contact
Ext. Demand Limit
10
Dry Contact
8
5K OHM Therm.
Remote Occupancy Contact
Leaving Hot Water Header Temperature
Unused
Terminal (TB1)
Output Type
Sensor Code
Equipment Name
Point Name
Unused
Gnd
3
0-10 vdc
Tower Fan Speed
Gnd
Unused
Bus
6
24 vac
Alarm Lamp
Bus
Unused
Bus
Unused
Bus
Unused
Bus
Unused
15
APPENDIX B — DEVICE ADDRESS BINDING
Device Address Binding (DAB) allows the controller to receive data from other Open controllers when they are connected by a network. The controller receives data from other Open or BACnet controllers when they are installed as part of an i-Vu® control system. The data transfer takes the form of DAB, which must be configured.
Currently, the controller implements DAB for the following variables:
· System Outdoor Air Temperature
· System Occupancy
· System Leaving Load Water Temperature
· System Leaving Condenser Water Temperature
· System Control Setpoint · System Cool Demand Level
· System Heat Demand Level
· System Space RH (Relative Humidity) DAB can be implemented on network points with an undefined BACnet address, displayed in Field Assistant and the i-Vu® interface in Properties Network Points. See Fig. A.
Fig. A — DAB (Device Address Binding) Using Field Assistant and i-Vu® Interface
16
APPENDIX C — 30MP MULTI-CHILLER POINTS/PROPERTIES
Tables A-K describe all of the possible settings for the controller on the i-Vu® or Field Assistant Properties tab.
NOTE: Some of the properties are available only when other settings have been enabled. See Appendix D on page 30 for the points and properties available on the touchscreen interface.
NOTE: Engineering units shown in this document in the defaults and ranges are strictly for reference. Only integers may be used.
NOTE: Point Names are in the order which coincides with the Properties Page Menu.
Table A — Status
Navigation: i-Vu® / Field Assistant: Properties Control Program Status
POINT NAME
DESCRIPTION
DEFAULT (D) / RANGE (R)
Plant Run Status
The plant run status value states:
· Stop: The plant is commanded to stop.
· Delay: The plant is in a start-up delay.
R: Stop
· Ready: The plant is commanded to run, and no compressors are
Delay
required. The lead chiller is enabled to open isolation valves and
Ready
start pumps.
Run
· Run: The plant is commanded to run, and compressors are staged Shutdown
to satisfy the control setpoint.
· Shutdown: The plant shutdown is active.
Plant Run Command
The plant’s current run command.
R: Stop/Run
Plant Status
The plant’s current run status.
R: Off/Running
Equipment Alarm
Indicates the controller has an active alarm. See Service Configuration for causes.
R: Normal/Alarm
Chiller Plant MBH
Displays the current MBtu/hr of heating from the plant.
R: __Mbtu/hr
Chiller Plant Tons
Displays the current tons of cooling from the chiller plant.
R: __ tons
Chiller Plant Capacity
Displays the current percent loaded capacity of the chiller plant.
R: 0 to 100%
Chiller Control Temp
Displays the water temperature used to control the chiller plant.
R: __ °F
Chiller Control Setpoint
Displays the current setpoint used to control the chiller plant.
R: __ °F
Tower Fan Output
Displays the tower fan’s speed.
R: 0 to 100%
Tower Fan Control Temp
Displays the condenser water temperature used to control the cooling tower fan.
R: __ °F
Tower Fan Control Setpoint
Displays the current setpoint used to control the cooling tower fan. R: __ °F
Outdoor Air Temperature
The outdoor air temperature used for control.
R: 56° to 245°F
Space Relative Humidity
Displays the current value of relative humidity sensor, if present. Applicable if Relative Humidity Source is not set to N/A.
R: 0 to 100%
Shutdown
When Active, provides a means to stop the chiller plant in an orderly manner. All alarms are reset and only currently active alarms are displayed.
D: Inactive R: Inactive/Active
17
APPENDIX C — 30MP MULTI-CHILLER POINTS/PROPERTIES (cont)
Table B — Chiller Status
Navigation: i-Vu® / Field Assistant: Properties Control Program StatusChiller Status
POINT NAME
DESCRIPTION
CHILLER #1
Chiller #1 Size
Chiller #1’s capacity model.
Chiller #1 Stages
Chiller #1’s available number of stages.
Chiller #1 Enable
Chiller #1’s start/stop command.
Chiller #1 Demand
The percentage of demand of Chiller #1.
Chiller #1 EWT
Chiller #1’s entering water temperature.
Chiller #1 LWT
Chiller #1’s leaving water temperature.
Chiller #1 ECWT
Chiller #1’s entering condenser water temperature.
Chiller #1 Status
Chiller #1’s status read from UPC controller.
Chiller #1 Linkage Status Chiller #1 LCWT
Chiller #1 Heat/Cool Status
Chiller #1’s linkage connection status. Chiller #1’s leaving condenser water temperature.
Chiller #1’s heat/cool mode status.
Chiller #1 Status
Chiller #1’s status read from PIC6.1 controller.
Chiller #1 Network Status Chiller #2 to 8
Chiller #1’s System Point binding status. Same information is available for CH-2 to CH-8.
RANGE (R)
R: __
R: 1 to 3
R: Stop/Start
R: 0 to 100%
R: __ °F
R: __ °F
R: __ °F
R: Linkage Not Available Off and Available CCN Mode and Running Low Load Recycle Local Mode or Wait Power Fail Restart Fault Shutdown Communication Failure
R: Not Active/Active
R: __ °F
R: No Comm Cool Heat Auto
R: Comm Not Available Off Running Stopping Delay Tripout Ready Override Defrost Run Test Test Local Network Remote Free Cool Comm Failure
R: Not Active/Active
18
APPENDIX C — 30MP MULTI-CHILLER POINTS/PROPERTIES (cont)
Table C — Unit Configuration
Navigation: i-Vu® / Field Assistant: Properties Control Program Configuration Unit Configuration
POINT NAME
DESCRIPTION
DEFAULT (D) / RANGE (R)
Heat Enable
Enables or disables heating operation.
D: Enable R: Disable/Enable
Heating Lockout Temperature
Heating is inhibited above this outdoor air temperature.
D: 65°F R: 30° to 120°F
Heating Setpoint OA Reset
Enables OA reset of the heating water supply temperature’s setpoint.
D: Disable R: Disable/Enable
OAT HW Supply Reset Low Limit
The lowest outdoor air temperature which resets the heating water D: 30°F
supply temperature.
R: __°F
OAT HW Supply Limit High Limit
The highest outdoor air temperature which resets the heating water supply temp. Must be set above the configured OAT HW Supply Reset Low Limit.
D: 60°F R: __°F
Maximum OA HW Reset
The highest heating water supply temp setpoint reset allowed by the D: 20°F
OAT.
R: 0° to 40°F
Cool Enable
Enables or disables cooling operation.
D: Enable R: Disable/Enable
Cooling Lockout Temperature
Cooling is inhibited below this outdoor air temperature.
D: 45°F R: 65° to 80°F
Cooling Setpoint OA Reset
Enables OA reset of the cooling water supply temp’s setpoint.
D: Disable R: Disable/Enable
OAT CHW Supply Reset Low Limit
The lowest outdoor air temperature which resets the cooling water D: 70°F
supply temp.
R: __°F
OAT CHW Supply Reset High Limit
The highest outdoor air temperature which resets the cooling water supply temp. Must be set above the configured OAT CHW Supply Reset Low Limit.
D: 90°F R: __°F
Maximum OA CHW Reset
The highest cooling water supply temp. setpoint reset allowed by the D: 10°F
OAT.
R: 0° to 25°F
RH Cooling Setpoint Reset
Enables or disables reset of the cooling water supply temp. setpoint, D: Disable
based on relative humidity.
R: Disable/Enable
Occupancy Schedules
Enables or disables the occupancy schedule function.
D: Disable R: Disable/Enable
Alarm Lamp for Chiller Alerts
Enable to use the Alarm Lamp relay for alarms AND chiller alerts.
D: Disable R: Disable/Enable
POWER FAILURE RECOVERY
Power Fail Restart Delay
On initial power up or after recovery from a power failure, the controller delays starting any equipment for the configured value of this delay in seconds. Max delay time is 600 sec.
D: 120 seconds R: 0 to 600 seconds
Immediate Restart Time
For a power failure less than this value (in minutes), the control restarts all previous running chiller stages at 30 second intervals. Maximum restart delay time is 720 min.
D: 20 minutes R: 0 to 720 minutes
SENSOR CALIBRATION
Leaving Cond. Water Temperature The current leaving condenser water temperature.
R: __°F
Leaving Cond. Water Temperature Sensor Calibration
A calibration offset value that allows adjusting of the local leaving condenser water temperature sensor to match a calibrated standard that is measuring the temperature in the same location.
D: 0°F R: 9.9° to 10°F
Leaving Load Water Temperature
The current leaving load water temperature.
R: __ °F
Leaving Load Water Temp Sensor Calibration
A calibration offset value that allows adjusting of the local leaving load water temperature sensor to match a calibrated standard that is measuring the temperature in the same location.
D: 0°F R: 9.9° to 10°F
Outdoor Air Temperature
The current outdoor air temperature.
R: __ °F
A calibration offset value that can be adjusted so the outdoor air Outdoor Air Temp Sensor Calibration temperature sensor matches a calibrated standard that measures
the temperature in the same location.
D: 0°F R: 9.9° to 10°F
Space Relative Humidity
Displays the current value of relative humidity sensor, if present. Applicable if Relative Humidity Source is not set to N/A.
R: __%rh
Space RH Sensor Calibration
A calibration offset value that allows adjusting of the space relative humidity sensor to match a calibrated standard that is measuring the humidity in the same location.
D: 0%rh R: 15 to 15%rh
19
APPENDIX C — 30MP MULTI-CHILLER POINTS/PROPERTIES (cont)
Table C — Unit Configuration (cont)
Navigation: i-Vu® / Field Assistant: Properties Control Program Configuration Unit Configuration
POINT NAME
DESCRIPTION
DEFAULT (D) / RANGE (R)
CHILLER ROTATION
Rotation Method Selector — Equal Size
Daily: Rotates the lead chiller daily at a specified time period.
Weekly: Rotates the lead chiller weekly on a specified day and time
period.
D: Runtime Equalization
Monthly: Rotates the lead chiller monthly on a specified day and time R: Daily
period.
Weekly
Manual Rotation: Manually rotates the lead chiller when the operator Monthly
commands it.
Manual Rotation
Runtime: Rotates the lead chiller after it reaches a specified number Runtime
of runtime hours.
Runtime Equalization
Runtime Equalization: Rotates the lead chiller when all chillers are on
and lead chiller runtime > lag chiller runtime.
SPECIFY DETAILS OF THE SELECTED ROTATION METHOD
Method
Enter…
Daily
Time of day to rotate the lead chiller NOTE: Enter the time of day below in “Defined Time for Rotation”.
Weekly
Day of the week to rotate the lead chiller.
D: Wednesday R: Monday to Sunday
Monthly
Day of the month to rotate the lead chiller monthly.
D: 1 R: 1 to 31
Manual Rotation
Manually rotates the lead chiller.
D: Do not rotate R: Rotate
Runtime
Number of runtime hours before rotating the lead chiller.
D: 360 hrs R: 200 to 9999 hrs
Runtime Equalization
Rotates the lead chiller when all chillers are on and lead chiller runtime > lag chiller runtime.
Defined Time for Rotation
Specify the time of day (24 hour format) for automatic rotation based on the method and schedule selected. (Not applicable to Runtime Equalization).
D: 8:00 R: 1:00 to 24:00
Runtime Since Last Rotation
Chiller CH-1 CH-2
Runtime 0.0 hr 0.0 hr
R: __ hrs
Chiller Order
Chiller CH-1 CH-2
Position 1 0
R: 1 to 8 0 = Not Available
Table D — Setpoints
Navigation: i-Vu® / Field Assistant: Properties Control Program Configuration Setpoints
POINT NAME
DESCRIPTION
DEFAULT (D) / RANGE (R)
Hot Water Setpoint
The hot water temperature setpoint maintained by the chiller plant. D: 120°F
The setpoint is internally clamped so it will not exceed 140°F.
R: 80°F to 140°F
Chilled Water Setpoint
The chilled water temperature setpoint maintained by the chiller plant. The setpoint is internally clamped so it will not exceed the highest freeze point configured in any chiller.
D: 44°F R: 40 to 65°F for water
20 to 45°F for brine
CONDENSER WATER TEMPERATURE
CW Min Load Setpoint
The condenser water temperature setpoint at minimum load for tower fan control.
D: 65°F R: 50° to 85°F
CW Part-Load Setpoint
The condenser water temperature setpoint at partial load for tower D: 70°F
fan control.
R: 50° to 85°F
CW Full-Load Setpoint
The condenser water temperature setpoint at full load for tower fan D: 76°F
control.
R: 50 to 85°F
RELATIVE HUMIDITY
Occ Relative Humidity Setpoint
The control setpoint used during occupied periods.
D: 60%rh R: 0 to 100%rh
HEATING DEMAND LIMIT
Demand Level 1 Heat
Enables Demand Level 1 to limit the maximum stage capacity to the D: Disable
current operating capacity.
R: Disable/Enable
Demand Level 2 Heat Adj.
The hot water setpoint is decreased by this number of degrees when D: 3°F
receiving a Demand Level 2 signal.
R: 0 to 10°F
Demand Level 3 Heat Adj.
The hot water setpoint is decreased by this number of degrees when D: 5°F
receiving a Demand Level 3 signal.
R: 0 to 10°F
COOLING DEMAND LIMIT
Demand Level 1 Cool
Enables Demand Level 1 to limit the maximum stage capacity to the D: Disable
current operating capacity.
R: Disable/Enable
Demand Level 2 Cool Adj.
The chilled water setpoint is increased by this number of degrees D: 2°F
when receiving a Demand Level 2 signal.
R: 0°F to 10°F
Demand Level 3 Cool Adj.
The chilled water setpoint is further increased by this number of degrees when receiving a Demand Level 3 signal.
D: 3°F R: 0 to 10°F
20
APPENDIX C — 30MP MULTI-CHILLER POINTS/PROPERTIES (cont)
Table E — Alarm Configuration
Navigation: i-Vu® / Field Assistant: Properties Control Program Configuration Alarm Configuration
POINT NAME
DESCRIPTION
DEFAULT (D) / RANGE (R)
LEAVING CONDENSER WATER TEMPERATURE ALARM
Low Leaving Cond. Water Temp. Alarm Limit
The Leaving Condenser Water Temp. must drop below this value to
generate a Leaving Condenser Water Temperature Alarm. There is a fixed hysteresis of 2°F for return to normal. NOTE: This value should be set to at least 10°F below the
D: 100°F R: 80 to 200°F
configured heating setpoint.
High Leaving Cond. Water Temp. Alarm Limit
The Leaving Condenser Water Temp. must exceed this value to
generate a Leaving Condenser Water Temperature Alarm. There is a fixed hysteresis of 2°F for return to normal. NOTE: This value should be set to at least 4°F above the configured
D: 200°F R: 90 to 200°F
heating setpoint.
ENTERING CONDENSER WATER TEMPERATURE ALARM
Low Entering Cond. Water Temp. Alarm Limit
The Entering Condenser Water Temp. must drop below this value to generate an Entering Condenser Water Temperature Alarm. There is a fixed hysteresis of 2°F for return to normal.
D: 100°F R: 80 to 200°F
High Entering Cond. Water Temp Alarm Limit
The Entering Condenser Water Temp. must exceed this value to generate an Entering Condenser Water Temperature Alarm. There is a fixed hysteresis of 2°F for return to normal.
D: 200°F R: 80 to 200°F
LEAVING LOAD WATER TEMPERATURE ALARM
Low Leaving Load Water Temp. Alarm Limit
The Leaving Load Water Temp. must drop below this value to
generate a Leaving Load Water Temperature Alarm. There is a fixed hysteresis of 2°F for return to normal. NOTE: This value should be set to at least 4°F below the configured
D: 42°F R: 45 to 45°F
cooling setpoint.
High Leaving Load Water Temp. Alarm Limit
The Leaving Load Water Temp. must exceed this value to generate a Leaving Load Water Temperature Alarm. There is a fixed hysteresis of 2°F for return to normal. NOTE: This value should be set to at least 10°F above the configured cooling setpoint.
D:125°F R: 20 to 150°F
ENTERING LOAD WATER TEMPERATURE ALARM
Low Entering Load Water Temp. Alarm Limit
The Entering Load Water Temp. must drop below this value to generate an Entering Load Water Temperature Alarm. There is a fixed hysteresis of 2°F for return to normal.
D: 42°F R: 45 to 45°F
High Entering Load Water Temp. Alarm Limit
The Entering Load Water Temp. must exceed this value to generate an Entering Load Water Temperature Alarm. There is a fixed hysteresis of 2°F for return to normal.
D: 125°F R: 90 to 150°F
OUTDOOR AIR TEMPERATURE ALARM
Low OAT Alarm Limit
The Outdoor Air Temperature must drop below this value to generate an Outdoor Air Temp Alarm. There is a fixed hysteresis of 1°F for return to normal.
D: 65°F R: 65 to 40°F
High OAT Alarm Limit
The Outdoor Air Temperature must exceed this value to generate an Outdoor Air Temp. Alarm. There is a fixed hysteresis of 1°F for return to normal.
D: 245°F R: 100 to 245°F
SPACE HUMIDITY ALARM
Occupied High RH Alarm Limit
The relative humidity sensor must exceed this value to generate a Space Relative Humidity alarm in the occupied mode if RH Cooling D: 100%rh Setpoint Reset (Unit Configuration) is set to Enable. There is a fixed R; 45 to 100%rh hysteresis of 5%rh for return to normal.
Alarm Delay (min./%RH)
Determines the amount of delay before an occupied RH alarm is generated when the controller transitions to the occupied mode. The D: 5 minutes delay time equals this value multiplied by the difference between the R: 0 to 30 minutes sensor RH value and the occupied RH setpoint plus 15 minutes.
Unoccupied High RH Alarm Limit
The value that the relative humidity sensor must exceed to generate a Space Humidity Alarm in the unoccupied mode if RH Control is set to Enable. There is a fixed hysteresis of 5%rh for return to normal.
D: 100%rh R: 45 to 100%rh
21
APPENDIX C — 30MP MULTI-CHILLER POINTS/PROPERTIES (cont)
Table F — Service Configuration
Navigation: i-Vu® / Field Assistant: Properties Control Program Configuration Service Configuration
POINT NAME
DESCRIPTION
DEFAULT (D) / RANGE (R)
Control Mode Selection
Defines whether to control this equipment to make hot water or chilled water.
D: Cool Mode R: Heat Mode
Cool Mode
Control Point
Defines whether the control monitors and uses Leaving Water Temp. or Entering Water Temp. to control this equipment.
D: Leaving Water Temp R: Leaving Water Temp
Entering Water Temp
Minimum No. of Chillers to Run
The least number of chillers that can run at the same time.
D: 0 R: 0 to 8
ACR Timer
ACR (Additional Capacity Required) Determines the time delay before an D: 5:00 minutes
additional compressor stage can be added.
R: 2:00 to 20:00 minutes
RCR Timer
RCR (Reduced Capacity Required) Determines the time delay before an D: 3:00 minutes
additional compressor stage can be removed.
R: 1:00 to 5:00 minutes
This BACnet Object calculates the amount of capacity required to satisfy the Hot Water Setpoint and allows access to the control loop’s tuning parameters. NOTE: The following default values should be changed only by a technician trained in PID Loop algorithms.
Heat PID
Heat PID Output Hot Water Control Offset
ACTION Update Interval Proportional Integral Derivative Deadband Bias
REVERSE 00:30 (mm:ss)
100 0 0 0 0
The Heat PID output that is used for staging the compressors. A positive value increases capacity; a negative value decreases capacity.
R: 100 to 100%
An offset value that is added to the effective Hot Water Setpoint. The
resulting value is the control point that is used by each chiller. This causes D: 2°F
each chiller to operate at a higher setpoint to achieve the desired hot
R: 0 to 10°F
water header temperature.
This BACnet Object calculates the amount of capacity required to satisfy the Chilled Water Setpoint and allows access to the control loop’s tuning parameters. NOTE: The following default values should be changed only by a technician trained in PID Loop algorithms:
Cool PID
Cool PID Output Chilled Water Control Offset Tower Fan Output Type
ACTION Update Interval
DIRECT 00:30 (mm:ss)
Proportional
100
Integral
0
Derivative
0
Deadband
0
Bias
0
The Cool PID output that is used for staging the compressors. A positive value increases capacity; a negative value decreases capacity.
An offset value that is subtracted from the effective Chilled Water Setpoint. The resulting value is the control point that is used by each chiller. This causes each chiller to operate at a lower setpoint to achieve the desired chilled water header temperature.
Defines the type of fan output control.
This BACnet Object calculates the fan speed required to achieve the desired condenser water temperature setpoint. NOTE: The following default values should be changed only by a technician trained in PID Loop algorithms.
R: 100 to 100%
D: 2°F R: 0° to 10°F
D: 0-10v R: 0-10v
2-10v
Tower Fan PID
ACTION Update Interval Proportional Integral Derivative Deadband Bias
DIRECT 01:00 (mm:ss) 10 2 0 0 0
22
APPENDIX C — 30MP MULTI-CHILLER POINTS/PROPERTIES (cont)
Table F — Service Configuration (cont)
Navigation: i-Vu® / Field Assistant: Properties Control Program Configuration Service Configuration
POINT NAME
DESCRIPTION
DEFAULT (D) / RANGE (R)
Occ Contact Normal Logic State
Specifies the occupancy contact’s normal logic state.
D: Open R: Open/Closed
RH Sensor Min. Input Volts
The lowest voltage that should be read from the hardwired relative humidity (RH) sensor.
D: 0.00 v R: 0 to 2.00v
RH Sensor Max. Input Volts
The highest voltage that should be read from the hardwired RH sensor.
D: 5.00 V R: 0 to 5.00v
RH Sensor Value at Min. Volts
The % relative humidity that correlates to the hardwired RH sensor’s low D: 0%
voltage reading.
R: 0 to 40%
RH Sensor Value at Max. Volts
The % relative humidity that correlates to the hardwired RH sensor’s high D: 100%
voltage reading.
R: 60 to 100%
Freeze Point Offset
An offset value that allows adjusting of the freeze point read from the chillers.
D: 0°F R: 0° to 10°F
System Space RH
Allows using another controller’s relative humidity value over the network. The remote controller must be equipped with a network-accessible relative humidity sensor value.
D: 999 R: 2 to 100%
System Outdoor Air Temperature
Allows the controller to use an outdoor air temperature value from the network. The remote controller must have a network accessible outdoor air temperature sensor value.
D: 999.00°F R: 50 to 150°F
System Leaving Cond. Water Temperature
Allows using another controller’s leaving condenser water temperature sensor value (system water temperature), to be read over the network. D: 999.00°F The remote controller must have a network-accessible leaving condenser R: 0 to 250°F water temperature sensor value.
System Leaving Load Water Temperature
Allows using another controller’s leaving load water temperature sensor value (system water temperature), to be read over the network. The remote controller must have a network-accessible leaving load water temperature sensor value.
D: 999.00°F R: 0 to 250°F
System Control Setpoint
Allows using another controller’s Control Setpoint value to be read over the D: 999.00°F
network. The remote controller must have a network-accessible point.
R: 0 to 250°F
System Heat Demand Level
The system heat demand level being received over the network.
D: 0.00 R: 0 to 3
System Cool Demand Level
The system cool demand level being received over the network.
D: 0.00 R: 0 to 3
System Occupancy
Allows reading and using another controller’s occupancy status value over the network. The remote controller must have a network-accessible Occupancy Status point.
D: Unoccupied R: Unoccupied/Occupied
The following is a list of available points used to set the alarm output to an alarm state if the alarm condition is true. Set the alarm condition to Enable to turn this feature on for any individual alarm.
CH-1 Linkage Failure Alarm
Enables Chiller #1 Linkage failure alarm.
D: Enable R: Disable/Enable
CH-2 Linkage Failure Alarm
Enables Chiller #2 Linkage failure alarm.
D: Enable R: Disable/Enable
CH-3 Linkage Failure Alarm
Enables Chiller #3 Linkage failure alarm.
D: Enable R: Disable/Enable
CH-4 Linkage Failure Alarm
Enables Chiller #4 Linkage failure alarm.
D: Enable R: Disable/Enable
CH-5 Linkage Failure Alarm
Enables Chiller #5 Linkage failure alarm.
D: Enable R: Disable/Enable
CH-6 Linkage Failure Alarm
Enables Chiller #6 Linkage failure alarm.
D: Enable R: Disable/Enable
CH-7 Linkage Failure Alarm
Enables Chiller #7 Linkage failure alarm.
D: Enable R: Disable/Enable
CH-8 Linkage Failure Alarm
Enables Chiller #8 Linkage failure alarm.
D: Enable R: Disable/Enable
23
APPENDIX C — 30MP MULTI-CHILLER POINTS/PROPERTIES (cont)
Table F — Service Configuration (cont)
Navigation: i-Vu® / Field Assistant: Properties Control Program Configuration Service Configuration
POINT NAME
DESCRIPTION
DEFAULT (D) / RANGE (R)
The following is a list of available points used to set the alarm output to an alarm state if the alarm condition is true. Set the alarm condition to Enable to turn this feature on for any individual alarm.
CH-1 Alarm State
When set to Enable, Chiller #1’s Alarm State initiates an Equipment D: Enable
Alarm and energizes the Alarm Lamp binary output.
R: Disable/Enable
CH-2 Alarm State
When set to Enable, Chiller #2’s Alarm State initiates an Equipment D: Enable
Alarm and energizes the Alarm Lamp binary output.
R: Disable/Enable
CH-3 Alarm State
When set to Enable, Chiller #3’s Alarm State initiates an Equipment D: Enable
Alarm and energizes the Alarm Lamp binary output.
R: Disable/Enable
CH-4 Alarm State
When set to Enable, Chiller #4’s Alarm State initiates an Equipment D: Enable
Alarm and energizes the Alarm Lamp binary output.
R: Disable/Enable
CH-5 Alarm State
When set to Enable, Chiller #5’s Alarm State initiates an Equipment D: Enable
Alarm and energizes the Alarm Lamp binary output.
R: Disable/Enable
CH-6 Alarm State
When set to Enable, Chiller #6’s Alarm State initiates an Equipment D: Enable
Alarm and energizes the Alarm Lamp binary output.
R: Disable/Enable
CH-7 Alarm State
When set to Enable, Chiller #7’s Alarm State initiates an Equipment D: Enable
Alarm and energizes the Alarm Lamp binary output.
R: Disable/Enable
CH-8 Alarm State
When set to Enable, Chiller #8’s Alarm State initiates an Equipment D: Enable
Alarm and energizes the Alarm Lamp binary output.
R: Disable/Enable
Leaving Cond. Water Temp. Alarm
When set to Enable, a Leaving Condenser Water Temperature Alarm indicated by the controller also initiates an Equipment Alarm and energizes the Alarm Lamp binary output.
D: Enable R: Disable/Enable
Leaving Cond. Water Sensor Failure Alarm
When set to Enable, a Leaving Condenser Water Sensor Failure Alarm indicated by the controller also initiates an Equipment Alarm and energizes the Alarm Lamp binary output.
D: Enable R: Disable/Enable
Entering Cond. Water Temp Alarm
When set to Enable, an Entering Condenser Water Temperature Alarm indicated by the controller also initiates an Equipment Alarm and energizes the Alarm Lamp binary output.
D: Enable R: Disable/Enable
Entering Cond. Water Sensor Failure Alarm
When set to Enable, an Entering Condenser Water Sensor Failure Alarm indicated by the controller also initiates an Equipment Alarm and energizes the Alarm Lamp binary output.
D: Enable R: Disable/Enable
Leaving Load Water Temp. Alarm
When set to Enable, a Leaving Load Water Temperature Alarm indicated by the controller also initiates an Equipment Alarm and energizes the Alarm Lamp binary output.
D: Enable R: Disable/Enable
Leaving Load Water Sensor Failure Alarm
When set to Enable, a Leaving Load Water Temperature Alarm indicated by the controller also initiates an Equipment Alarm and energizes the Alarm Lamp binary output.
D: Enable R: Disable/Enable
Entering Load Water Temp. Alarm
When set to Enable, an Entering Load Water Temperature Alarm indicated by the controller also initiates an Equipment Alarm and energizes the Alarm Lamp binary output.
D: Enable R: Disable/Enable
Entering Load Water Sensor Failure Alarm
When set to Enable, an Entering Load Water Sensor Failure Alarm indicated by the controller also initiates an Equipment Alarm and energizes the Alarm Lamp binary output.
D: Enable R: Disable/Enable
OA Temperature Alarm
When set to Enable, an Outdoor Air Temperature Alarm indicated by the controller also initiates an Equipment Alarm and energizes the Alarm Lamp binary output.
D: Enable R: Disable/Enable
OA Sensor Failure Alarm
When set to Enable, an Outdoor Air Temperature Sensor Failure Alarm indicated by the controller also initiates an Equipment Alarm and energizes the Alarm Lamp binary output.
D: Enable R: Disable/Enable
High RH Alarm
When set to Enable, a High Space Relative Humidity Alarm indicated by the controller also initiates an Equipment Alarm and energizes the Alarm Lamp binary output.
D: Enable R: Disable/Enable
RH Sensor Failure Alarm
When set to Enable, a Relative Humidity Sensor Failure Alarm indicated by the controller also initiates an Equipment Alarm and energizes the Alarm Lamp binary output.
D: Enable R: Disable/Enable
CHILLER CONTROLLERS
Chiller #1 Controller Selection
Specifies Chiller #1’s controller type.
D: None R: None
UPC PIC6.1
Chiller #2 to 8
Same information is available for CH-2 to CH-8 Controller Selection.
24
APPENDIX C — 30MP MULTI-CHILLER POINTS/PROPERTIES (cont)
Table G — Maintenance
Navigation: i-Vu® / Field Assistant: Properties Control Program Maintenance
POINT NAME
DESCRIPTION
DEFAULT (D) /RANGE (R)
UNIT
Unit Type
The type of equipment that the controller is controlling.
R: Air/Water
Controlling Mode
Displays the mode used to control this equipment.
R: Heat Mode/Cool Mode
Controlling Point
Displays the point used to control this equipment.
R: Leaving Water Temperature Entering Water Temperature
Chiller Size Compare
Indicates whether chillers are equal or unequal size.
R: Unequal/Equal
External Demand Limit Status
The external demand limit input status.
R: Off/On
Chiller Heat Mode Mismatch
Indicates that the chiller plant is in Heat Mode, but all the chillers are not in Heat Mode.
R: Inactive/Active
Heating OA Temp Lockout
Indicates that heating is not available because the outdoor air temperature is above the lockout temperature
R: Inactive/Active
Chiller Cool Mode Mismatch
Indicates that the chiller plant is in Cool Mode, but all the chillers are not in Cool Mode.
R: Inactive/Active
Cooling OA Temp Lockout
Indicates that cooling is not available because the outdoor air temperature is below the lockout temperature.
R: Inactive/Active
Number of Chillers
The total number of chillers in the chiller plant.
R: 0 to 8
Number of Stages
The total number of chiller plant stages – compressors, not including hot gas bypass.
R: 0 to 24
Chiller Plant Size
The chiller plant’s total size in MBtu/hr.
R: __MBtu/hr
Chiller Plant Size (tons)
The chiller plant’s total size in tons.
R: __ tons
Active Compressor Stages
The number of compressor stages currently operating.
R: 0 to 24
Leaving Cond. Water Temperature The current leaving condenser water temperature sensor’s value.
R: __°F
Entering Cond. Water Temperature The current entering condenser water temperature sensor’s value. R: __°F
Leaving Load Water Temperature The current leaving load water temperature sensor’s value.
R: __°F
Entering Load Water Temperature The current entering load water temperature sensor’s value.
R: __°F
Hot Water Setpoint
The effective hot water setpoint.
R: __°F
Chilled-Water Setpoint
The effective chilled water setpoint.
R: __°F
External AI Setpoint
The external analog input’s setpoint scaled value.
R: __°F
Leaving Cond. Water Temp. Source
The source of the Leaving Condenser Water Temp. value states:
· N/A: No sensor value associated with this device.
· Local: A physical sensor is wired and connected to the appropriate R: N/A
input channel of this controller.
Local
· Network: A network sensor value provided to this controller.
Network
· Linkage: The sensor value from a linked device, obtained through Linkage
air or water linkage.
Looked Value
· Locked Value: The controller’s sensor input is manually locked to a
specific value.
Entering Cond. Water Temp. Source
The source of the Entering Condenser Water Temp. value states: · N/A: No sensor value associated with this device. · Local: A physical sensor is wired and connected to the appropriate
input channel of this controller. · Network: A network sensor value provided to this controller. · Linkage: The sensor value from a linked device, obtained through
air or water linkage. · Locked Value: The controller’s sensor input is manually locked to a
specific value.
R: N/A Local Network Linkage Looked Value
Leaving Load Water Temperature Source
The source of the Leaving Load Water Temp. value states:
· ·
· ·
N/A: No sensor value associated with this device Local: A physical sensor is wired and connected to the appropriate input channel of this controller. Network: A network sensor value provided to this controller. Linkage: The sensor value from a linked device, obtained through air or water.
R: N/A Local Network Linkage Locked Value
· Locked Value: The controller’s sensor input is manually locked to a
specific value.
Entering Load Water Temperature Source
The source of the Entering Load Water Temp. value states:
· N/A: No sensor value associated with this device.
· Local: A physical sensor is wired and connected to the appropriate R: N/A
input channel of this controller.
Local
· Network: A network sensor value provided to this controller.
Network
· Linkage: The sensor value from a linked device, obtained through Linkage
air or water linkage.
Locked Value
· Locked Value: The controller’s sensor input is manually locked to a
specific value.
25
APPENDIX C — 30MP MULTI-CHILLER POINTS/PROPERTIES (cont)
Table G — Maintenance (cont)
Navigation: i-Vu® / Field Assistant: Properties Control Program Maintenance
POINT NAME
DESCRIPTION
DEFAULT (D) /RANGE (R)
UNIT
Control Setpoint Source
The control setpoint value’s source states:
· N/A: No sensor value associated with this device.
· Local: A physical sensor is wired and connected to the appropriate
· ·
·
·
input channel of this controller. Network; A network sensor value provided to this controller. Linkage: The sensor value from a linked device, obtained through air or water linkage. Locked Value: The controller’s sensor input is manually locked to a specific value. Configuration: The controller uses the equipment’s configuration
R: N/A Local Network Linkage Locked Value Configuration
(water/brine) and the analog input channel’s value to determine the
appropriate setpoint conversion range (1-5 Volts = 40 to 65°F for
water / 1-5 Volts = 20°F to 45°F for brine).
Outdoor Air Temperature Source
The source of the Outdoor Air Temperature value states:
· N/A: No sensor value associated with this device.
· Local: A physical sensor is wired and connected to the appropriate R: N/A
input channel of this controller.
Local
· Network: A network sensor value provided to this controller.
Network
· Linkage: The sensor value from a linked device, obtained through Linkage
air or water linkage.
Locked Value
· Locked Value: The controller’s sensor input is manually locked to a
specific value.
Relative Humidity Source
The source of the Space Relative Humidity value states:
· N/A: No sensor value associated with this device.
· Local: A physical sensor is wired and connected to the appropriate R: N/A
input channel of this controller.
Local
· Network: A network sensor value provided to this controller.
Network
· Linkage: The sensor value from a linked device, obtained through Linkage
air or water linkage.
Locked Value
· Locked Value: The controller’s sensor input is manually locked to a
specific value.
OCCUPANCY
Occupancy Status
The chiller plant’s occupancy status.
R: Unoccupied/Occupied
BAS On/Off
BAS On/Off determines the occupancy state of the controller and can be set over the network by another device or third-party BAS. Options: · Inactive – Occupancy is determined by a configured schedule. · Occupied – The controller is always in the occupied mode. · Unoccupied – The controller is always in the unoccupied mode
D: Inactive R: Inactive
Occupied Unoccupied
NOTE: If BAS On/Off is set to either Unoccupied or Occupied, the Optimal Start routine is automatically disabled.
Schedules
The controller’s occupancy status based on the local schedule.
R: Unoccupied/Occupied
Occupancy Contact
The current status of Input Channel No.5 when configured as a Remote Occupancy contact input.
R: Inactive
Global Occupancy
The System Occupancy network input’s current state.
D: Unoccupied R: Unoccupied/Occupied
RESET
Heating Supply Setpoint Reset
The Hot Water Supply Setpoint’s current reset method.
R: Inactive OAT Reset Demand Limit
Calculated OA Heating Reset
Based on outdoor air temperature, the amount of heating reset.
R: __°F
Cooling Supply Setpoint Reset
The Chilled Water Supply Setpoint’s current reset method.
R: Inactive OAT Reset RH Override Demand Limit
Calculated OA Cooling Reset
Based on outdoor air temperature, the amount of cooling reset.
R: __°F
Calculated RH Cooling Reset
Based on relative humidity, the amount of cooling reset that will be subtracted from the Calculated OA Cooling Reset.
R: __°F
DEMAND LIMIT
System Heating Demand Level
This unit’s system heat demand level currently in effect.
R: 0 to 3
System Cooling Demand Level
This unit’s system cool demand level currently in effect.
R: 0 to 3
External Demand Limit
The current chiller plant’s demand limit capacity received from an external source.
R: 0 to 100%
COMPRESSOR STATUS (Chiller #1)
Chiller #1 A1 Relay
Chiller #1’s compressor A1 relay status.
R: Off/On
Chiller #1 A2 Relay
Chiller #1’s compressor A2 relay status.
R: Off/On
Chiller #1 A3 Relay
Chiller #1’s compressor A3 relay status.
R: Off/On
Chiller #1 B1 Relay
Chiller #1’s compressor B1 relay status.
R: Off/On
Chiller #2 to 8
Same information is available for CH-2 to CH-8.
—
26
APPENDIX C — 30MP MULTI-CHILLER POINTS/PROPERTIES (cont)
Table H — Alarms
Navigation: i-Vu® / Field Assistant: Properties Control Program Alarms
POINT NAME
DESCRIPTION
RANGE (R)
Equipment Alarm
Indicates if the unit is in a general equipment alarm.
R: Normal/Alarm
Plant Power Failure
Indicates if the unit is in a Plant Power Failure alarm.
R: Normal/Alarm
Leaving Cond. Water Temperature
Indicates if the leaving condenser water temperature exceeds the high or low limits.
R: Normal/Alarm
Entering Cond. Water Temperature
Indicates if the entering condenser water temperature exceeds the high or low limits.
R: Normal/Alarm
Leaving Load Water Temperature
Indicates if the leaving load water temperature exceeds the high or low limits.
R: Normal/Alarm
Entering Load Water Temperature
Indicates if the entering load water temperature exceeds the high or low limits.
R: Normal/Alarm
Outdoor Air Temperature
Indicates an alarm if the outdoor air temperature exceeds the high or low alarm limits.
R: Normal/Alarm
Space Relative Humidity
Indicates if the relative humidity exceeds the high RH alarm limit. R: Normal/Alarm
Leaving Cond. Water Temp. Sensor Indicates if the leaving condenser water temperature sensor fails. R: Normal/Alarm
Entering Cond. Water Temp. Sensor Indicates if the entering condenser water temperature sensor fails. R: Normal/Alarm
Leaving Load Water Temp. Sensor Indicates if the leaving load water temperature sensor fails.
R: Normal/Alarm
Entering Load Water Temp. Sensor Indicates if the entering load water temperature sensor fails.
R: Normal/Alarm
Outdoor Air Temp. Sensor
Indicates if the controller is no longer receiving a valid outdoor air temperature value either through the network or from a local sensor.
R: Normal/Alarm
Space Relative Humidity Sensor
Indicates that a valid space relative humidity sensor or sensor value is no longer available to the controller.
R: Normal/Alarm
Chiller #1 Linkage
Indicates Chiller #1 Linkage has failed.
R: Normal/Alarm
Chiller #2 Linkage
Indicates Chiller #2 Linkage has failed.
R: Normal/Alarm
Chiller #3 Linkage
Indicates Chiller #3 Linkage has failed.
R: Normal/Alarm
Chiller #4 Linkage
Indicates Chiller #4 Linkage has failed.
R: Normal/Alarm
Chiller #5 Linkage
Indicates Chiller #5 Linkage has failed.
R: Normal/Alarm
Chiller #6 Linkage
Indicates Chiller #6 Linkage has failed.
R: Normal/Alarm
Chiller #7 Linkage
Indicates Chiller #7 Linkage has failed.
R: Normal/Alarm
Chiller #8 Linkage
Indicates Chiller #8 Linkage has failed.
R: Normal/Alarm
CHILLER ALARM STATE
Chiller #1 Alarm State
Displays Chiller #1’s Alarm State.
R: Normal Alert Alarm
Chiller #2 Alarm State
Displays Chiller #2’s Alarm State.
R: Normal Alert Alarm
Chiller #3 Alarm State
Displays Chiller #3’s Alarm State.
R: Normal Alert Alarm
Chiller #4 Alarm State
Displays Chiller #4’s Alarm State.
R: Normal Alert Alarm
Chiller #5 Alarm State
Displays Chiller #5’s Alarm State.
R: Normal Alert Alarm
Chiller #6 Alarm State
Displays Chiller #6’s Alarm State.
R: Normal Alert Alarm
Chiller #7 Alarm State
Displays Chiller #7’s Alarm State.
R: Normal Alert Alarm
Chiller #8 Alarm State
Displays Chiller #8’s Alarm State.
R: Normal Alert Alarm
27
APPENDIX C — 30MP MULTI-CHILLER POINTS/PROPERTIES (cont)
Table I — Linkage
Navigation: i-Vu® / Field Assistant: Properties Control Program Linkage
POINT NAME
DESCRIPTION
CH-1 Linkage Provider
Open each Provider and enter the correct Network Number and Collector MAC Address. NOTE: If the Network Number or Address is changed, use the i-Vu application or Field Assistant to cycle power to the controller for the changes to take effect.
SPECIFY FURTHER DETAILS OF THE LINKAGE PROVIDER
Network Number
The network number of the MS/TP network that connects the chiller plant controller and the chiller controllers.
Collector MAC Address CH-2 to CH-8 Linkage Provider Linkage Configuration Reset
The MAC address assigned to the chiller’s controller.
Same as CH-1 Linkage Provider. Reset the Linkage Configuration. NOTE: Use if Linkage was configured incorrectly.
DEFAULT (D) /RANGE (R)
D: 0 R: 16101
0= Unused Chiller D: 0 R: 1 to 8
0= Unused Chiller — D: Unchecked R: Unchecked/Checked
Table J — System Points
Navigation: i-Vu® / Field Assistant: Properties Control Program System Points
POINT NAME
DESCRIPTION
CHILLER #1
Chiller #1 SIZE
Chiller #1’s capacity model.
Chiller #1 A1
Chiller #1’s compressor A1 capacity.
Chiller #1 A2
Chiller #1’s compressor A2 capacity.
Chiller #1 A3
Chiller #1’s compressor A3 capacity.
Chiller #1 B1
Chiller #1’s compressor B1 capacity.
Chiller #1 STAT
Chiller #1’s running status.
Chiller #1 ALM
Chiller #1 HTCL
Chiller #1 FRZ Chiller #1 EWT Chiller #1 LWT Chiller #1 CEWT Chiller #1 CLWT Chiller #1 HRS
Chiller #1’s alarm state.
Chiller #1’s heat/cool status.
Chiller #1’s evaporator freeze point. Chiller #1’s entering evaporator water temperature. Chiller #1’s leaving evaporator water temperature. Chiller #1’s entering condenser water temperature. Chiller #1’s leaving condenser water temperature. Chiller #1’s machine operating hours.
DEFAULT (D) /RANGE (R)
D: 0 R: __
D: 0 Tons R: __Tons
D: 0 Tons R: __Tons
D: 0 Tons R: __Tons
D: 0 Tons R: __Tons
D: 1 R: 1 = No Comm
01 = Off 02 = Running 03 = Stopping 04 = Delay 05 = Tripout 06 = Ready 07 = Override 08 = Defrost 09 = Run Test 10 = Test 11 = Local 12 = Network 13 = Remote 14 = Free Cool 15 = Comm Failure
D: 0 R: 0 = Normal
1 = Alert 2 = Alarm
D: 1 R: 1 = No Comm
0 = Cool 1 = Heat 2 = Auto
D: 999.0°F R: __°F
D: 999.0°F R: __°F
D: 999.0°F R: __°F
D: 999.0°F R: __°F
D: 999.0°F R: __°F
D: 0 hrs R: __hrs
28
APPENDIX C — 30MP MULTI-CHILLER POINTS/PROPERTIES (cont)
Table J — System Points (cont)
Navigation: i-Vu® / Field Assistant: Properties Control Program System Points
POINT NAME
DESCRIPTION
CHILLER #1
Chiller #1 UTYP
Chiller #1’s unit type.
Chiller #1 K_A1
Chiller #1 K_A2
Chiller #1 K_A3
Chiller #1 K_B1
Chiller #1 MLV Chiller #1 CTRL_PNT Chiller #1 DEM_LIM Chiller #1 HC_SEL Chiller #1 CHIL_S_S Chiller #2 to 8 Configuration Reset
Chiller #1’s compressor A1 relay status.
Chiller #1’s compressor A2 relay status.
Chiller #1’s compressor A3 relay status.
Chiller #1’s compressor B1 relay status.
Chiller #1 minimum load valve select (hot gas bypass). Chiller #1’s control point write command. Chiller #1’s demand limit write command. Chiller #1’s heat/cool write command. Chiller #1’s start/stop write command. Same information is available for CH-2 to CH-8. Resets the System Points configuration. NOTE: Use if System Points was configured incorrectly.
DEFAULT (D) /RANGE (R)
D: 0 R: 0 = No Comm
1 = 2 = Air Cooled 3 = Water Cooled D: Off R: Off/On D: Off R: Off/On D: Off R: Off/On D: Off R: Off/On D: Off R: Off/On R: 20°F to 140°F R: 0 to 100% R: 0 = Cool 1 = Heat R: Off/On
D: Unchecked R: Unchecked/Checked
CAUTION
Do not change the Value, Offset/Polarity, Exp: Num, I/O Type, Sensor/Actuator Type, Min/Max, or Resolution I/O configuration parameter for the points listed below.
Changing these parameters could cause improper control and/ or equipment damage.
Use extreme caution if locking a point as this may also cause improper control and/or equipment damage.
Table K — I/O Points
Navigation: i-Vu® / Field Assistant: Properties I/O Points
POINT NAME
DESCRIPTION
RANGE (R)
RH Sensor
The current voltage of the controller’s RH input.
R: 0 to 5 vdc
AI Setpoint
The current voltage of the controller’s external chilled water setpoint sensor input. Allowable input range is 1 to 5 vdc.
R: 0 to 5 vdc
OAT Sensor
The value of the controller’s outdoor air temperature sensor input, prior to any operator-configured Calibration Offset.
R: 56 to 245°F
The value of the controller’s leaving chilled water header Leaving Chilled Water Header Temp. temperature sensor input, prior to any operator-configured
Calibration Offset.
R: 56 to 245°F
Leaving Hot Water Header Temp.
The value of the controller’s leaving hot water header temperature sensor input, prior to any operator-configured Calibration Offset.
R: 56 to 245°F
External Demand Limit
The external demand limit input’s current state.
R: Off/On
Remote Occupancy Contact
The remote occupancy contact input’s current state.
R: Open/Closed
Tower Fan Speed
The assigned output channel’s current commanded, configurationdependent, fan output.
R: 0 to 100%
Alarm Lamp
The assigned output channel’s current commanded, configurationdependent, output.
R: Off/On
29
APPENDIX D — 30MP MULTI-CHILLER TruVu ET DISPLAY NAVIGATION SCREEN SETTINGS
Plant Manager
Home Snapshot Properes Menu
Status Chiller Status
Unit Configuraon Sensor Calibraon Setpoints Alarm Configuraon Alarms Maintenance
Chiller Controllers UPC Linkage PIC6.1 System Points
Touchscreen Setup
Startup Wizard ET Show/Hide Config ET System
LEGEND
Log in Type Factory Login — All Admin Login — User Login —
Chiller #1 Status Chiller #2 Status Chiller #3 Status Chiller #4 Status Chiller #5 Status Chiller #6 Status Chiller #7 Status Chiller #8 Status
Unit Occupancy Reset Demand Limit Compressor Status
Chiller #1 System Points Chiller #2 System Points Chiller #3 System Points Chiller #4 System Points Chiller #5 System Points Chiller #6 System Points Chiller #7 System Points Chiller #8 System Points
Module Sengs Applicaon Sengs
Change User
Set Time and Date Communicaon IP Time Master
About Language Change Password Extended Screen Timeout End User License Agreement Update Interval Inacvity Timeout Time Format Selecon
Sengs
Module Sengs
Applicaon Sengs
NOTE: The Menu Map displays the menus and sub menus which are accessible with different logins.
Local Access Module Status Schedule Trends Alarms Browser
Change User
Fig. B — Menu Map
Set Time and Date Communicaon IP Time Master
About Language Change Password Extended Screen Timeout End User License Agreement Update Interval Inacvity Timeout Time Format Selecon
30
APPENDIX D — 30MP MULTI-CHILLER TruVu ET DISPLAY NAVIGATION SCREEN SETTINGS (cont)
Address the Chillers
After the controller has discovered the chillers in the 30MP modular chiller water plant, the next step is to ensure all chillers are addressed appropriately. Follow the steps below to address a chiller. See Fig. C-M. See Tables L-O for navigation details.
1. Press the Home icon in the top left corner to return to the home screen. See Fig. C.
2. Login as factory. See Table L.
3. Press “…” in the lower right hand corner of the screen to enter the Snapshot screen. See Fig. D.
Fig. C — Home Screen
Fig. E — Properties Menu
6. Select Controller UPC or PIC6.1 for each chiller on the system. If the chiller does not exist select None. See Fig. F.
Fig. D — Snapshot Screen 4. Press “…” in the lower right hand corner of the screen again to
enter Properties menu. See Fig. E.
5. Login as admin or factory to see different menus. Refer to “Menu Map” on page 30.
Fig. F — Chiller Controllers Screen
31
APPENDIX D — 30MP MULTI-CHILLER TruVu ET DISPLAY NAVIGATION SCREEN SETTINGS (cont)
7. Go to Properties menu, press the back button, then select UPC Linkage. This will open the UPC Chiller Linkage menu. For each chiller set the Network number to 16101 and set the MAC address the same as each chiller MAC address. See Fig. G.
NOTE: If the linkage source address does not match the chiller, check that the UPC Open controller for the chiller is addressed properly. Refer to section “ADDRESS THE UPC OPEN MODULES” on page 6.
9. To enable the communication status of the chillers with a PIC6.1 controller go to (PropertiesPIC6.1 System Points MenuChiller # System Points). Check all Comm Enable boxes. After all Comm are enabled, the Comm Status will show as Active See Fig. I- K.
Fig. G — UPC Chiller Linkage Screen
8. Go to (Properties Chiller Status Menu Chiller # Status). Chiller# 1-8 status menus show parameters and linkage status as Active. See Fig. H.
Fig. I — PIC6.1 System Points Menu (Not Enabled)
Fig. H — UPC Chiller Status Screen
Fig. J — Chiller System Points Menu
32
APPENDIX D — 30MP MULTI-CHILLER TruVu ET DISPLAY NAVIGATION SCREEN SETTINGS (cont)
Fig. K — PIC6.1 System Points Screen (Enabled) 10. To view the chiller status go to (PropertiesChiller Status
Menu Chiller # Status). See Fig. L. The network status shows as active.
Fig. M — Startup Wizard Screen 12. To return to the main Home screen press the Home icon
in the upper left hand corner to return to the Properties Menu screen, and press the icon again to return to the main Home screen. Fig. L — Chiller # Status Menu 11. Go back to (Properties Startup Wizard (FACTORY ONLY). Configure as necessary. See Fig. M. See Table M on page 37 for start-up wizard settings.
33
APPENDIX D — 30MP MULTI-CHILLER TruVu ET DISPLAY NAVIGATION SCREEN SETTINGS (cont)
SCREEN NAME
Table L — 30MP Navigation Screen Settings
DISPLAY
Press
in the lower right hand corner of the screen to navigate
to the Snapshot screen.
DETAILS
Home
Displays: · Controlling temperature · Control type · Plant Run Status · Occupancy · Outdoor air temperature, if available.
Snapshot
Press
in the lower left hand corner of the screen to return to
the Home screen.
Navigates to:
· Alarm Status – press the red alarm icon
Press
in the lower right hand corner of the screen to navigate · Schedules – press the clock icon
to the Properties Menu.
· Trends – press the graph icon
Displays: · Current Plant Capacity · Controlling temperature · Control setpoint · Outdoor air temperature, if available and
allowed · Alarms, if present
Chiller Stage Color Codes: · Black – Stage Off · Green – Stage On · Half-Green and Half Black – Stage in Hot Gas
Bypass · Light Red – Comm. Error · Solid Red – Alarm · Orange- Alert
Properties Menu
Navigates to Property pages Login with one of the following passwords:
· “User” level – type user · “Admin” level – type admin · “Factory” level – type Touch
NOTE(S): 1. Passwords are case sensitive. 2. Only the buttons that are authorized for a specific password level are visible. 3. See Fig. B on page 30 to see which menus are available to specific logins.
34
APPENDIX D — 30MP MULTI-CHILLER TruVu ET DISPLAY NAVIGATION SCREEN SETTINGS (cont)
SCREEN NAME
Table L — 30MP Navigation Screen Settings (cont)
DISPLAY
DETAILS
Show/Hide Configuration
Configure Show/Hide conditions for values on the following screens:
· Standby · Home · Snapshot
NOTE: Only displayed for the Factory or Admin password. (See above.)
Chiller Controller
Select the Controller UPC or PIC6.1 for each chiller on the system. If the chiller does not exist select None.
UPC Chiller Linkage
Set up Linkage using the following properties:
· Network Number · Address Type: MS/TP · MS/TP Address of the Collector · Linkage configuration reset
35
APPENDIX D — 30MP MULTI-CHILLER TruVu ET DISPLAY NAVIGATION SCREEN SETTINGS (cont)
Table L — 30MP Navigation Screen Settings (cont)
System Points
For chillers with a PIC6.1 controller check all the boxes to enable communication.
PIC6.1 System Points Menu
If the communication is enabled the status shows as active.
36
APPENDIX D — 30MP MULTI-CHILLER TruVu ET DISPLAY NAVIGATION SCREEN SETTINGS (cont)
Table M — 30MP Multi-Chiller Start-Up Wizard
POINT NAME Control Mode
Control Point Minimum No. of Chillers to Run ACR Timer (Additional Capacity Required) RCR Timer (Reduced Capacity Required) Heating Enable Heat Lockout Temperature Hot Water Setpoint
Hot Water Control Offset
Cool Enable Cooling Lockout Temperature Chilled Water Setpoint
Chilled Water Control Offset
Occ Contact Normal Logic State Tower Fan Output Type Heating Setpoint OA Reset Maximum OA HW Reset Cooling Setpoint OA Reset Maximum OA CHW Reset RH Cooling Setpoint Reset
DESCRIPTION
DEFAULT (D)/RANGE (R)
Defines whether to control this equipment to make hot water or chilled water.
D: Cool Mode R: Heat Mode
Cool Mode
Defines whether the control monitors and uses Leaving Water Temp. or Entering Water Temp. to control this equipment.
D: Leaving Water Temp. R: Leaving Water Temp.
Entering Water Temp.
The least number of chillers that can run at the same time.
D: 0 R: 0 to 8
Determines the time delay before an additional compressor stage can be added.
D: 5:00 minutes R: 2:00 to 20:00 minutes
Determines the time delay before an additional compressor stage can be removed.
D: 3:00 Minutes R: 1:00 to 5:00 minutes
Enables or disables heating operation.
D: Enable R: Disable/Enable
Heating is inhibited above this outdoor air temperature.
D: 65°F R: 30° to 120°F
The hot water temperature setpoint maintained by the chiller plant. D: 120°F
The setpoint is internally clamped so it will not exceed 140°F.
R: 80° to 140°F
An offset value that is added to the effective Hot Water Setpoint. The resulting value is the control point that is used by each chiller. This D: 2°F causes each chiller to operate at a higher setpoint to achieve the R: 0° to 10°F desired hot water header temperature.
Enables or disables cooling operation.
D: Enable R: Disable/Enable
Cooling is inhibited below this outdoor air temperature.
D: 45°F R: 65 to 80°F
The chilled water temperature setpoint maintained by the chiller plant. The setpoint is internally clamped so it will not exceed the highest freeze point configured in any chiller.
D: 44°F R: 40 to 65°F for water
20 to 45°F for brine
An offset value that is subtracted from the effective Chilled Water
Setpoint. The resulting value is the control point that is used by each D: 2°F
chiller. This causes each chiller to operate at a lower setpoint to
R: 0° to 10°F
achieve the desired chilled water header temperature.
Specifies the occupancy contact’s normal logic state.
D: Open R: Open/Closed
Defines the type of fan output control.
D: 0-10v R: 0-10v
2-10v
Enables OA reset of the heating water supply temp’s setpoint.
D: Disable R: Disable/Enable
The highest heating water supply temp setpoint reset allowed by the D: 20°F
OAT.
R: 0° to 40°F
Enables OA reset of the cooling water supply temp’s setpoint.
D: Disable R: Disable/Enable
The highest cooling water supply temp. setpoint reset allowed by the D: 10°F
OAT.
R: 0 to 25°F
Enables or disables reset of the cooling water supply temp. setpoint, D: Disable
based on relative humidity.
R: Disable/Enable
POINT NAME Collector Network Number MS/TP Address
Table N — 30MP Multi-Chiller Linkage Source Address
DESCRIPTION The chiller’s MS/TP network number. Set the MAC address of the chiller UPC Open controller.
DEFAULT (D) / RANGE (R)
D: 0 R: 0 to 65,534
D: 0 R: 0 to 99
37
APPENDIX D — 30MP MULTI-CHILLER TruVu ET DISPLAY NAVIGATION SCREEN SETTINGS (cont)
SCREEN NAME
Table O — UPC Open’s System TouchTM Navigation Screens
DISPLAY
DETAILS
Standby Home
OAT 75°F Occupied
12:15 PM
50
F
7
Leaving Water Temp
Screen displays after the Inactivity Timer expires (default is 5 minutes).
Displays: · Leaving water temperature · Mode · Occupancy · Outdoor Occupancy
Emergency Stop
Not an interactive screen. Touch anywhere to advance to Home screen.
Displays:
Click
in the lower right hand corner of the screen to navigate · Leaving water temperature
to the Snapshot screen.
· Mode
· Occupancy
· Outdoor air temperature, if available
Snapshot
OAT 75°F
Snapshot
echw lchw
52.3°F 50.7°F
…
65.4°F
lcw ecw
…
Displays:
· Entering chilled water temperature · Leaving chilled water temperature · Entering condenser water temperature,
if present · Outdoor air temperature, if available · Machine type, air or water · Alarms, if present
To return to the Home screen press corner of the screen.
in the lower left hand
To move forward to the Properties Menu press right hand corner of the screen.
in the lower
38
APPENDIX D — 30MP MULTI-CHILLER TruVu ET DISPLAY NAVIGATION SCREEN SETTINGS (cont)
Table O — UPC Open Modules System TouchTM Navigation Screens (cont)
SCREEN NAME
DISPLAY
DETAILS
Properties Menu
Properties Menu
Place Holder for the Name Field [LOGIN] PROPERTIES MENU CCN Status CCN Configuration Linkage Linkage Configuration Startup Wizard ET Show/Hide Config ET System Touchscreen Setup
Navigates to Property pages Login with one of the following passwords: · User level – type user · Admin level – type admin · Factory level – type Touch
NOTE: Only the buttons that are authorized for a specific password level are visible.
Show/hide Configuration
Show/Hide Configuration
Show values on Screens
OAT sensor installed?
Show
Configure Show/Hide conditions for values on the following screens: · Standby · Home · Snapshot
NOTE: Only displayed for the Factory or Admin password. (See above.)
Linkage Configuration
Linkage Configuration
Application Instance:
2
Set up Linkage by entering the Application Instance
39
© 2024 Carrier
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300273-01
Printed in U.S.A.
Form No. 30MP-6ASI
Pg 40
10-24
Replaces: 30MP-27SI
Documents / Resources
![]() |
Carrier MPW017-080 Multi Chiller Controller Accessory [pdf] Installation Guide MPW017-080 Multi Chiller Controller Accessory, MPW017-080, Multi Chiller Controller Accessory, Controller Accessory, Accessory |