BerkoMEP RUX Series Explosion-Proof Unit Heater

BerkoMEP-RUX-Series-Explosion-Proof-Unit-Heater-product

CAPACITIES

  • 2.5–35 kW | 208–600V | 1Ø or 3Ø
  • Thermostat Range: 50°–90° F
  • Air Volume: 550–3850 CFM
  • Air Throw Range: 13–75 feet
  • Class 1, Divisions 1 & 2, Groups C & D
  • Class Il, Divisions 1 & 2, Groups F & G
  • Class 1, Zones 1 & 2, Groups lIB
  • Ignition Temperature Code T3C, 320° F
    • JOB NAME:
    • LOCATION:
    • ARCHITECT:
    • ENGINEER:
    • CONTRACTOR:
    • SUBMITTED BY:
    • DATE

RUX SERIES – EXPLOSION-PROOF UNIT HEATER

 

TAG/ITEM

 

QTY.

 

CATALOG NUMBER

HEATER  

AMPS

AIR MOVEMENT
KW VOLTS Ø CFM THROW TEMP. RISE
                   
                   
                   
                   
                   
                   
                   
                   
                   
 

ACCESSORIES AND CONTROLS

TAG/ITEM QTY. CATALOG NUMBER DESCRIPTION
       
       
       
       
SUBMITTED BY: DATE
   
   
   
   
APPROVED BY: DATE
   
   
   
   

ARCHITECT’S AND ENGINEER’S SPECIFICATIONS

Electric explosion proof unit heater(s) shall be supplied by Berko®, a Marley Engineered Products® Brand, Bennettsville, SC, USA, and shall be of the KW rating, voltage and phase specified in the schedule. They shall be fan-forced type, certified to cCSAus, and approved for Class I, Divisions 1 and 2, Group C and D; Class II, Divisions 1 and 2, Groups E, F, and G; Class I, Zones 1 and 2, Group IIB; Temperature Code T3C, 320°F (160°C).

  • SAFETY: Unit heaters shall be outfitted with dual overtemperature production—both a manual and automatic reset thermal cutout.
  • HEAT EXCHANGER: Efficient liquid-to-air design utilizes all-welded steel headers and finned tube construction with spiral wound aluminum fins. Industrial-grade heating elements are immersed in a nontoxic, inhibited, propylene glycol heat transfer fluid that provides freeze protection down to -49°F (-45°C). The heat exchanger is hydrostatically tested at 350 psig. A pressure relief valve provides excess pressure protection and is set at 70 psig.
  • ENCLOSURE: Heat exchanger and components to be enclosed in an industrial-grade, corrosion-resistant cabinet fabricated from polyester powder-coated, 14-gauge steel. Adjustable outlet louvers to have minimum opening safety stops.
  • FAN MOTOR ASSEMBLY: Unit heaters consist of an explosion-proof motor (60Hz standard, 50hz optional) fitted with an aluminum fan blade. The motor has double shielded, permanently lubricated ball bearings and automatic reset line breaking thermal overload protection. Motors furnished on standard units operate at line voltage and are prewired to the control enclosure so separate field wiring to the motor is not required. The standard motor is rated for Class I, Groups C and D, Class II, Groups F and G. The minimum operating temperature is -14°F (-25°C) and the minimum storage temperature is -49°F (-45°C). Optional motor ratings available.
  • MOUNTING: The heater shall be provided with an accessory mounting kit designed to bear the weight of heater assembly. Options include a ceiling mounting kit, wall mounting kit, or a pole mounting kit.
  • OPTIONAL BUILT-IN CONTROLS: Units come standard with a controlling magnetic contactor and 24 Volt control circuit transformer housed in a NEMA 7, 9 cast aluminum enclosure. The following factory installed and prewired control options are available: adjustable built-in thermostat, disconnect switch with external handle, fan-only switch, 120 Volt control circuit for special external thermostat circuit, “warning” pilot light (to indicate abnormal operation), “Heater On” pilot light
    • Berko reserves the right to change specifications without prior notice.

RUX SERIES

60 Hz Models & Specifications

ITEM INFORMATION

 

CATALOG NO.

 

 

VOLTS

ELECTRICAL DATA

 

PHASE        TOTAL AMPS*

 

 

KW

 

 

HP

MOTOR

 

RPM          FAN BLADE DIAMETER

 

 

RISE**

AIR FLOW

 

CFM                 THROW

 

FRAME SIZE

 

SHIP WT.

RUX-233-FA-0036C 208 1 17  

 

 

 

3.0

1/4 1725 12″ 15°F 650 15″ 1 130 lbs
RUX-233-FA-0036J 240 1 15 1/4 1725 12″ 15°F 650 15″ 1 130 lbs
RUX-233-FA-0036D 208 3 10 1/4 1725 12″ 15°F 650 15″ 1 130 lbs
RUX-233-FA-0036K 240 3 9 1/4 1725 12″ 15°F 650 15″ 1 130 lbs
RUX-233-FA-0036U 480 3 5 1/4 1725 12″ 15°F 650 15″ 1 130 lbs
RUX-233-FA-0036Z 600 3 4 1/4 1725 12″ 15°F 650 15″ 1 130 lbs
RUX-233-FA-0056C 208 1 26  

 

 

 

5.0

1/4 1725 12″ 25°F 650 15″ 1 130 lbs
RUX-233-FA-0056J 240 1 23 1/4 1725 12″ 25°F 650 15″ 1 130 lbs
RUX-233-FA-0056D 208 3 16 1/4 1725 12″ 25°F 650 15″ 1 130 lbs
RUX-233-FA-0056K 240 3 14 1/4 1725 12″ 25°F 650 15″ 1 130 lbs
RUX-233-FA-0056U 480 3 7 1/4 1725 12″ 25°F 650 15″ 1 130 lbs
RUX-233-FA-0056Z 600 3 6 1/4 1725 12″ 25°F 650 15″ 1 130 lbs
RUX-233-FA-0086C 208 1 38  

 

 

 

7.5

1/4 1725 12″ 28°F 850 25″ 1 130 lbs
RUX-233-FA-0086J 240 1 34 1/4 1725 12″ 28°F 850 25″ 1 130 lbs
RUX-233-FA-0086D 208 3 23 1/4 1725 12″ 28°F 850 25″ 1 130 lbs
RUX-233-FA-0086K 240 3 20 1/4 1725 12″ 28°F 850 25″ 1 130 lbs
RUX-233-FA-0086U 480 3 10 1/4 1725 12″ 28°F 850 25″ 1 130 lbs
RUX-233-FA-0086Z 600 3 9 1/4 1725 12″ 28°F 850 25″ 1 130 lbs
RUX-233-FA-0106J 240 1 44  

 

 

10

1/4 1725 12″ 38°F 850 25″ 1 130 lbs
RUX-233-FA-0106D 208 3 30 1/4 1725 12″ 38°F 850 25″ 1 130 lbs
RUX-233-FA-0106K 240 3 26 1/4 1725 12″ 38°F 850 25″ 1 130 lbs
RUX-233-FA-0106U 480 3 13 1/4 1725 12″ 38°F 850 25″ 1 130 lbs
RUX-233-FA-0106Z 600 3 11 1/4 1725 12″ 38°F 850 25″ 1 130 lbs
RUX-233-FB-0156D 208 3 44  

 

15

1/4 1725 16″ 27°F 1800 45″ 2 169 lbs
RUX-233-FB-0156K 240 3 38 1/4 1725 16″ 27°F 1800 45″ 2 169 lbs
RUX-233-FB-0156U 480 3 19 1/4 1725 16″ 27°F 1800 45″ 2 169 lbs
RUX-233-FB-0156Z 600 3 16 1/4 1725 16″ 27°F 1800 45″ 2 169 lbs
RUX-233-FB-0206U 480 3 25  

20

1/4 1725 16″ 35°F 1800 45″ 2 169 lbs
RUX-233-FB-0206Z 600 3 21 1/4 1725 16″ 35°F 1800 45″ 2 169 lbs
RUX-233-FC-0256U 480 3 31  

25

1/2 1725 20″ 26°F 3110 65″ 3 216 lbs
RUX-233-FC-0256Z 600 3 25 1/2 1725 20″ 26°F 3110 65″ 3 216 lbs
RUX-233-FC-0306U 480 3 37  

30

1/2 1725 20″ 25°F 3850 75″ 3 216 lbs
RUX-233-FC-0306Z 600 3 30 1/2 1725 20″ 25°F 3850 75″ 3 216 lbs
RUX-233-FC-0356U 480 3 43  

35

1/2 1725 20″ 29°F 3850 75″ 3 216 lbs
RUX-233-FC-0356Z 600 3 35 1/2 1725 20″ 29°F 3850 75″ 3 216 lbs

50 Hz Models & Specifications

ITEM INFORMATION

 

CATALOG NO.

 

 

VOLTS

ELECTRICAL DATA

 

PHASE        TOTAL AMPS*

 

 

KW

 

 

HP

MOTOR

 

RPM          FAN BLADE DIAMETER

 

 

RISE**

AIR FLOW

 

CFM                 THROW

 

FRAME SIZE

 

SHIP WT.

RUX-233-FA-0036E 220 1 14  

 

 

2.5

1/4 1438 12″ 14°F 550 13″ 1 130 lbs
RUX-233-FA-0036F 220 3 9 1/4 1438 12″ 14°F 550 13″ 1 130 lbs
RUX-233-FA-0036G 380 3 6 1/4 1438 12″ 14°F 550 13″ 1 130 lbs
RUX-233-FA-0036H 400 3 6 1/4 1438 12″ 14°F 550 13″ 1 130 lbs
RUX-233-FA-0036I 415 3 5 1/4 1438 12″ 14°F 550 13″ 1 130 lbs
RUX-233-FA-0056E 220 1 21  

 

 

4.2

1/4 1438 12″ 24°F 550 13″ 1 130 lbs
RUX-233-FA-0056F 220 3 13 1/4 1438 12″ 24°F 550 13″ 1 130 lbs
RUX-233-FA-0056G 380 3 9 1/4 1438 12″ 24°F 550 13″ 1 130 lbs
RUX-233-FA-0056H 400 3 8 1/4 1438 12″ 24°F 550 13″ 1 130 lbs
RUX-233-FA-0056I 415 3 7 1/4 1438 12″ 24°F 550 13″ 1 130 lbs
RUX-233-FA-0076E 220 1 31  

 

 

6.3

1/4 1438 12″ 28°F 700 22″ 1 130 lbs
RUX-233-FA-0076F 220 3 19 1/4 1438 12″ 28°F 700 22″ 1 130 lbs
RUX-233-FA-0076G 380 3 12 1/4 1438 12″ 28°F 700 22″ 1 130 lbs
RUX-233-FA-0076H 400 3 11 1/4 1438 12″ 28°F 700 22″ 1 130 lbs
RUX-233-FA-0076I 415 3 10 1/4 1438 12″ 28°F 700 22″ 1 130 lbs
RUX-233-FA-0096E 220 1 40  

 

 

8.4

1/4 1438 12″ 38°F 700 22″ 1 130 lbs
RUX-233-FA-0096F 220 3 24 1/4 1438 12″ 38°F 700 22″ 1 130 lbs
RUX-233-FA-0096G 380 3 15 1/4 1438 12″ 38°F 700 22″ 1 130 lbs
RUX-233-FA-0096H 400 3 13 1/4 1438 12″ 38°F 700 22″ 1 130 lbs
RUX-233-FA-0096I 415 3 13 1/4 1438 12″ 38°F 700 22″ 1 130 lbs
RUX-233-FB-0136F 220 3 35  

 

12.5

1/4 1438 16″ 26°F 1500 39″ 2 169 lbs
RUX-233-FB-0136G 380 3 21 1/4 1438 16″ 26°F 1500 39″ 2 169 lbs
RUX-233-FB-0136H 400 3 19 1/4 1438 16″ 26°F 1500 39″ 2 169 lbs
RUX-233-FB-0136I 415 3 18 1/4 1438 16″ 26°F 1500 39″ 2 169 lbs
RUX-233-FB-0176F 220 3 46  

 

16.7

1/4 1438 16″ 35°F 1500 39″ 2 169 lbs
RUX-233-FB-0176G 380 3 28 1/4 1438 16″ 35°F 1500 39″ 2 169 lbs
RUX-233-FB-0176H 400 3 25 1/4 1438 16″ 35°F 1500 39″ 2 169 lbs
RUX-233-FB-0176I 415 3 24 1/4 1438 16″ 35°F 1500 39″ 2 169 lbs
RUX-233-FC-0216G 380 3 33  

21

1/2 1438 20″ 26°F 2600 57″ 3 216 lbs
RUX-233-FC-0216H 400 3 32 1/2 1438 20″ 26°F 2600 57″ 3 216 lbs
RUX-233-FC-0216I 415 3 31 1/2 1438 20″ 26°F 2600 57″ 3 216 lbs
RUX-233-FC-0256G 380 3 39  

25

1/2 1438 20″ 30°F 2600 57″ 3 216 lbs
RUX-233-FC-0256H 400 3 37 1/2 1438 20″ 30°F 2600 57″ 3 216 lbs
RUX-233-FC-0256I 415 3 36 1/2 1438 20″ 30°F 2600 57″ 3 216 lbs

Factory Built-in Options

CATALOG NO. OPTION                                                                                    DESCRIPTION
D Disconnect Switch Factory installed on the unit heater above the control enclosure. This is an inexpensive and positive way to meet NEC/CEC requirements for a disconnecting means within sight of the heater.
E Group E (Metal Dust) Construction Class II, Group E (Metal Dust) Construction Temperature Code T3C, 320° F (160°C).
K “Warning” Pilot Light Indicates when the thermal cutouts have tripped and the unit heater needs servicing.

Not available with combination V & L.

L “Heater On” Pilot Light Indicates when the electric heating elements are energized. Not available with combination V & K
M Manual Reset Thermal Cutout with Backup Contactor A pilot duty manual reset thermal cutout with a backup contactor is provided for independent secondary overtemperature protection. Cannot be installed with S, S1 or V.
S Auto/Fan Selector Switch A two-position switch wired to the control circuit for auto (automatic heat) and fan only control.

Cannot be installed with M, V or S1.

S1 Built-In Controls for Remote Auto/Fan Selector Switch Unit is prewired for field addition of remote auto/fan selector switch.

Cannot be installed with M, V or S.

T Adjustable Thermostat Factory installed and prewired to the control enclosure. Thermostat is adjustable from 50° to 90° F (10° to 32°C).
T1 Adjustable Thermostat for Wet Locations Factory installed and prewired to the control enclosure. Thermostat is adjustable from 40° to 80° F (5° to 25°C). Can be specified for all constructions.
V 120 Volt Control Circuit Can be provided when required for special external thermostat circuit.

Cannot be installed with S, S1, M or the combination of both K & L together.

Note: Both pilot lights (K & L) are not available with 120V option (V). Only one pilot light can be ordered with 120V control heaters.

Standard Mounting Kits

CATALOG NO. DESCRIPTION
1022451 Ceiling Mounting Kit
1022454 Wall Mounting Kit
1022457 Pole Mounting Kit

Note: One kit required per heater. Work with all frame sizes

Accessory Remote Thermostats

CATALOG NO. SWITCH TYPE TYPE RATING TEMP RANGE DESCRIPTION
1007002 Bimetal SPDT 125–277V, 22A 50°–90°F (10°–32°C) Class 1, Div. 1, Groups C & D. Class II, Div. 1, Groups E, F, & G
BX-1024754  

Bulb and Capillary with Internal Set Point Adjustment

SPDT 120–240V, 25A

277V, 22A

40°–120°F (5°–49°C) Class 1, Div. 1, Groups B, C & D. Class II, Div. 1, Groups E, F, & G
BX-1025396 SPST 120–240V, 25A

277V, 22A

40°–120°F (5°–49°C) Corrosion-Resistant Class 1, Div. 1, Groups B, C, & D. Class II, Div. 1, Groups E, F & G
1036506 Bimetal SPDT 480V, 15A 40°–80°F (5°–25°C) Class I, Div. 1, Groups C & D. Class II, Div. 1, Groups E, F, & G. Class III. IP66, Type 4

Remote Fan Switch

CATALOG NO. SWITCH TYPE RATING HUBS DESCRIPTION
1001744 2-Position 120/277V, 30A  

(2) 3/4″ NPT Hubs

Class I, Div. 1, Groups C & D. Class II, Div. 1, Groups E, F, & G. Class III
1031042 2-Position 110V, 6A Class I, Div. 1, Groups C & D. Class II, Div. 1, Groups E, F, & G. Class III. NEMA 4X

Dimensions and Clearances

BerkoMEP-RUX-Series-Explosion-Proof-Unit-Heater-fig-2

How to Order

Example

BerkoMEP-RUX-Series-Explosion-Proof-Unit-Heater-fig-3

  • Round up to the nearest whole kW
  • For custom requests, contact Marley sales representative for assistance and additional detail
  • Option Code “H” indicates 50 Hz Heater Contact Marley Sales Representative for additional configuration details

No matter the industry or application, Marley Engineered Products has a robust portfolio of innovative, reliable, high-performance comfort heating and ventilation solutions for all your heating needs.  For more information or assistance on your next project, contact Technical Services at 800-642-4328

Scan the QR code to access additional specs and features

BerkoMEP-RUX-Series-Explosion-Proof-Unit-Heater-fig-4

FAQs

What should I do if the unit heater fails to turn on?

Check the power supply, thermostat settings, and ensure all connections are secure. If issues persist, contact a certified technician for further inspection.

Can this unit heater be used in outdoor environments?

The unit is designed for indoor use in specified hazardous locations as mentioned in the manual. Outdoor usage may require additional protective measures.