beok TR9B WIFI-WPB Smart Combi Boiler
Specifications:
- Shell material: Anti-Flammable PC
- Version: TR9B 1.6(12/2023)
Product Overview:
This series of thermostat offers Floor Heating, Fan Coil, and Integrated versions to meet various requirements in different scenarios.
Display Symbols:
- Child-lock
- Frost Protection
- Wi-Fi (optional)
- Weather forecast (optional)
- Fan-Coil Cooling Mode
- Fan-Coil Ventilation Mode
- Room Temp.
- Fan-Coil Heating Mode
- Floor Heating Mode
- Floor Temp.
- Floor Heating on
- Fan-Coil Heating on
- Cooling on
- Week Display Mode
- % RH Set to Auto
- Timer Task
- Time Display
- Indoor humidity (optional)
Temperature Control Modes
- Manual Mode: Thermostat works based on manually-set temperature, disconnecting from auto mode.
- Auto Mode: Weekly-circled program allowing up to 6 heating events per day. Customizable heating events, workdays, and temperatures.
- Temporary Mode: Thermostat temporarily operates based on manually-set temperature and then shifts back to auto mode until the next event.
User Operation:
- Power on/off: Press the power button shortly to turn on/off the thermostat.
- Auto-mode: Press the auto-mode button for 3 seconds to edit auto-mode settings (Floor Heating/Integrated).
- Timer task: Press the timer task button for 3 seconds to edit timer task settings (Fan Coil/Integrated).
- Time setting: Press the time setting button for 3 seconds to set the time (Floor Heating).
- Child-lock: Press and hold the child-lock button for 3 seconds to activate child-lock feature.
Frequently Asked Questions (FAQ):
- Q: Can the thermostat display local weather conditions?
A: Yes, the device can obtain local weather conditions and outdoor temperature if the optional feature is enabled. - Q: How many events can be set per day on the thermostat?
A: The thermostat allows up to 6 events to be set per day for customized temperature plans. - Q: What is the purpose of the sail-shape curved design?
A: The sail-shape curved design adds a touch of fashion, elegance, and durability to the thermostat. - Q: Is it possible to link the thermostat with other equipment?
A: Yes, the thermostat supports 485 modbus and room card linkage for customized equipment, though this feature is optional.
Ultra-large colorful screen capacitive touch LCD smart thermostat
- The device can obtain local weather condition and outdoor temperature (optional)
- Customized exclusive temperature plan – up to 6 events allowed to set per day
- Sail-shape curved design – fashion,
- UItra-large screen – better user interaction experience
- 485 Modbus and room card linkage – customized equipment (optional)
Parameter
- Supply voltage AC100~240V; 50/60Hz
- Power consumption 1W Max (Wi-Fi 3W Max)
- Temp. setting range 5~95℃(41~99℉)
- Floor limited range 20~90℃(68~99℉)
- Temp. Dif. 0.5~10℃(1~10℉), Factory setting ±1℃
- Ambient temperature -5~50℃(23~99℉)
- Protection level IP20
- Shell material Anti-Flammable PC
Product Overview
This series of thermostats has Floor Heating, Fan Coil, and Integrated version, meeting the requirements under different scenarios.
Version | System mode | Model | Application |
Floor heating | Heating | EP | Built-in & floor sensor, floor limit sensor + Weekly programming |
WP | A NC/NO dual-output + Weekly programming | ||
WPB | A NC/NO dual-output + Weekly programming+ Potential-free output | ||
Fan Coil | Heating /Cooling / Ventilation | AC2 | Timer task + 2-pipe system |
AC2-485 | Timer task + 2-pipe system + 485Modbus (optional) | ||
AC4 | Timer task + 4-pipe system + 485Modbus (optional) | ||
Integrated | Heating / Cooling / Ventilation/Floor heating / Floor heating + Heating |
AWY |
Floor heating & fan coil, weekly programming + Potential-free output + Timer task + 485Modbus (optional) + Door card (optional) |
Display Symbols
Temperature Control Mode(Floor Heating/Integrated)
Manual Mode
Thermostat works based on manually-set temperature, disconnecting from auto mode.
Auto Mode
Weekly-circled programme, up to 6 heating events can be set per day. Heating events, workdays and temperature can be separately customized based on personal routines.
Temporary Mode
Thermostat works based on manually-set temperature temporarily and then shifts back to auto mode till next event.
User Operation
- Power on/off : Press “
” shortly to turn on/off the thermostat.
- Auto-mode : Press “
” for 3 seconds to edit auto-mode settings. (Floor Heating/Integrated)
- Timer task: Press “
” for 3 seconds to edit timer task. (Fan Coil/Integrated)
- Time setting: Press “
” for 3 seconds to set time. (Floor Heating)
- Press “
” twice for 3 seconds to set time. (Automatic time synch for Wi-Fi version)
- Press “
- Temp setting: Press
shortly to change setting temperature by 0.5°C.
- Child-lock: Press
for 3 seconds to activate child-lock.
- System mode: Press “
” shortly to switch cooling/heating/ventilation. (Fan Coil)
- Press “=
” shortly to switch cooling/heating/ventilation/floor heating/floor heating + heating. (Integrated)
- Temp control mode: Press “
” shortly to switch manual/auto mode. (Floor heating)
- Press “
” shortly to switch manual/auto mode. (Integrated, floor heating)
- Fan speed setting: Press “
” shortly to adjust fan speed.(Fan Cail/Integrated)
- ECO mode: Press“
”shortly to set to ECO mode 18°C(64°F). (Floor heating)
Advanced Setting (Usually for Professional Technicians)
Under power-off, press “ ” for 3 seconds to enter advanced setting mode, then re-press “ ” to switch to next mode. Press “ ” to save and exit advanced setting mode.
Code | Meaning | ![]() |
Default Value | Integrated | Fan Coil | Floor
Heating |
||||
AWY | AC2- 485 | AC4 | AC2 | EP | WP | WPB | ||||
00 | Postal address(optional) | Adjustment range 0x00~0xFA | 00 | √ | √ | √ | × | √ | √ | √ |
01 | Temp. calibration | -9.9~9.9℃(-9~9℉) | -3℃ | √ | √ | √ | √ | √ | √ | √ |
02 | Temp. Dif. | 0.5~10℃(1~10℉) | ±1℃ | √ | √ | √ | √ | √ | √ | √ |
03 | Temp. upper limit | 5~95℃(41~99℉) | 50℃ | √ | √ | √ | √ | √ | √ | √ |
04 | Temp. lower limit | 5~47℃(41~99℉) | 5℃ | √ | √ | √ | √ | √ | √ | √ |
05 | Frost protection | ON: frost protection on OFF: frost protection off | OFF | √ | √ | √ | √ | √ | √ | √ |
06 | Temperature unit | ℃/℉ | ℃ | √ | √ | √ | √ | √ | √ | √ |
07 |
Sensor selection |
IN: Controlled by built-in sensor OUT: Limited by floor sensor ALL: Controlled by built-in sensor and limited by floor sensor |
IN |
√ |
× |
× |
× |
√ |
√ |
√ |
08 | Floor limited Value | 20~90℃(68~99℉) | 35℃ | √ | × | × | × | √ | √ | √ |
09 | Weekly programming setting | 12345: 5/2 week mode 123456: 6/1 week mode 1234567: 7/0 week mode |
12345 |
√ | × | × | × | √ | √ | √ |
10 | Fan control settings | 00: Fan speed controllable 01: Fan speed uncontrollable |
00 | √ | √ | √ | √ | × | × | × |
11 | Delay time of outputs | 0~5min | 0 | √ | × | × | × | √ | √ | √ |
12 |
Child-lock |
00: Child-lock inactivate when screen off; lock all when child-lock activate 01: Child-lock activate when screen off; lock all when child-lock activate 02: Child-lock activate when screen off; lock all except Fan Speed, Up and Down when child-lock activate 03: Child-lock activate when screen off; lock all except Power on/off when child-lock activate |
00 |
√ |
√ |
√ |
√ |
√ |
√ |
√ |
13 | Boot Status | 00: Power OFF 01: Power ON 02: The last status before power loss |
02 |
√ | √ | √ | √ | √ | √ | √ |
14 |
Room card status |
00: turn off room card function 01: set to ECO temp. after pulling room card out 02: stay power-off after pulling room card out |
00 |
√ |
√ |
× |
× |
× |
× |
× |
15 | Room card heating
ECO temp. |
10~21℃(50-69℉) | 18℃ | √ | √ | × | × | × | × | × |
16 | Room card cooling
ECO temp. |
22~32℃(72-89℉) | 26℃ | √ | √ | × | × | × | × | × |
17 | Fan coil mode setting | 00: Cooling and heating 01: Cooling only |
00 | √ | √ | √ | √ | × | × | × |
18 | Weekly programming for Integrated | 00: turn on 01: turn off |
01 | √ | × | × | × | × | × | × |
19 | Reset | Press “ ”for 3 seconds to reset | / | √ | √ | √ | √ | √ | √ | √ |
Ultra-large colorful screen capacitive touch LCD smart thermostat
Auto-mode Setting (Floor Heating / Integrated)
Press “ ” for 3 seconds to edit auto-mode setting.
Timer Task Setting (Fan Coil / Integrated )
Press “ ” for 3 seconds to enter timer task setting; press “
” to change settings; press
to adjust parameters; press
to save and exit.
Dimensions (Unit: mm)
Mounting Steps
The thermostat adopt pre-guide and limited snap-fit design. It is easy to mount.
- Release front cover by inserting a head screw-driver into bottom crack.
- Insert the wires and then fix these wires with screws. Suggested wire-stripping length is 7-9mm.
- Mount backing plate into wall-cassette, put screws and then fix thermostat. Make sure that the thermostat is fixed without deformation. Suggested torque is 0.2~0.4N.m (2.0~4. 1kgf.cm).
- Re-mount the front cover via snap-fit connection.
Sensor failure
Please select work mode of sensors mrrectly. When it shows EO/EI emor, thermostat will stay power-off till the emor is eliminated.E0: built-in sensor is short-circuited or dismnnected. El : floor sensor is short-circuited or disconnected.
Installation instructions
Connecting Diagram
The thermostat operates in full capacity in areas with the altitude of less than 2500 above sea level. Power rating of external load should be less than or equal to 80% rated power of the thermostat in areas with altitude of 2500m to 4200m.
Bluetooth Mode
*Please turn on the Bluetooth of your phone in advance.
Sign Up & Log in
AP Mode
Device sharing
App control interface
Documents / Resources
![]() |
beok TR9B WIFI-WPB Smart Combi Boiler [pdf] User Guide TR9B WIFI-WPB Smart Combi Boiler, TR9B, WIFI-WPB Smart Combi Boiler, Smart Combi Boiler, Combi Boiler, Boiler |