BELLlighting Arial Multi Backlit LED Panel

Important Information
We recommend that luminaires are installed by a qualified electrician ensuring the installation complies with current IEE wiring regulations & local building control.
- On emergency fittings, all tests should be carried out in accordance with current emergency lighting regulations.
- BELL Lighting will not accept responsibility for any claims arising from poor installation.
- The operating temperature should be between -20°C and 35°C, and 0°C to 35°C for emergency fittings.
- Always switch off mains supply before installing.
- Upgrading of MCB may be necessary.
- Mount to a stable, secure surface that is rated for the weight of the luminaire.
- Ensure driver strain relief is fully applied when installing cables.
- Do not cover with insulation, ensure there is adequate free air ventilation around the fitting.
- Not suitable for ATEX hazardous zones (explosive atmospheres).
- Indoor use only.
- To ensure optimum performance, keep the front diffuser clean. Wipe with a soft, damp lint free cloth. Do not use soaps, detergents, solvents or abrasive materials.
- On emergency versions, only use battery as supplied.
- On emergency versions, allow the battery to fully charge for 24 hours before performing the initial discharge test.
- If the lighting fails within 3 hours of an emergency discharge test, the battery is to be replaced. Contact your local distributor for a suitable replacement.
- Not intended for use by children.
- The light source of this luminaire is not replaceable, when the light source reaches end of life, the whole luminaire must be replaced.
This product may contain substances that can be hazardous to the environment if not disposed of properly. Electrical and electronic equipment should never be disposed of with general household waste but must be separated for its correct treatment and recovery. Where possible recycle your packaging.

Luminaire Safety
Read these instructions before installation and retain for future reference.
This equipment should be installed by a competent electrician.

This luminaire contains a light source of energy rating E.
Recessed
Step 1: Remove the ceiling tile.

Step 2: Connect the Mains AC L&N into the driver terminal block, and connect the panel to the driver.

Step 3: Fix the panel into the ceiling grid.

Step 4: Ensure the panel is secure and turn on the power.

For color changeable model (controlled by Slide Switch in lamp), please select light color before installation, see image to the right
Choose color by slide switch with corresponding color temperature.

Emergency Product Specification
Emergency Product Specification (11742/11758/11781) Selectable Self-Test/Manual Test Emegency Function.
| Emergency Product Specification | |
| Dimensions | 340x116x44mm |
| Mains Voltage | 220-240VAC |
| Mains Frequency | 50-60Hz |
| Emergency Duration | 3 Hours |
| Battery Type | LiFePO4 6.4V 4Ah |
| Emergency Power Output | 3.4W |
| Emergency Power Voltage | 9-55V DC |
| Protection Class | Class I |
| Charging Time | 24 Hours |
| Ingress Protection Type | IP20 |
This product is factory pre-set to operate in STANDARD MANUAL TEST mode, with the selector switch set to position ON.
For SELF-TEST operation mode, move the switch to the right in position 1 before installation.
The selector switch is located on the emergency convertor inside the emergency pack.

Emergency Product Specification (11741/11757) Manual Test Only Emergency Function
| Emergency Product Specification | |
| Dimensions | 265x100x45mm |
| Mains Voltage | 220-240VAC |
| Mains Frequency | 50-60Hz |
| Emergency Duration | 3 Hours |
| Battery Type | LiFePO4 3.2V 4.4Ah |
| Emergency Power Output | 3.5W |
| Emergency Power Voltage | 20-55V DC |
| Protection Class | Class II |
| Charging Time | 24 Hours |
| Ingress Protection Type | IP20 |
Wiring Diagram
- Wiring diagram for 1-10V Dimming.

- Wiring diagram for DALI Dimming.

- Wiring diagram for Push/Switch Dimming.

- Wiring diagram for standard non-dimmable driver.

- Wiring diagram for emergency panel.

Testing And Commissioning
- Ensure the Load is connected.
- Connect the battery.
- Switch on the Unswitched Supply Check the Charge LED illuminates.
- Switch on the Maintained Supply Check the LED illuminates as normal.
- Switch off the Maintained Supply.
- Switch off the Unswitched Supply – Check the Charge LED extinguishes and the load LED illuminates at a reduced output.
- Enter the commissioning date on the Battery Pack. Switch on the Unswitched Supply.
Customer Support
Technical Helpline +44 (0)1924 893380
Technical@belllighting.co.uk
British Electric Lamps Ltd
BELL House, Foxbridge Way, Normanton Industrial Estate Normanton, West Yorkshire. WF6 1TN
BELL Ireland
Marina House, Clarence Street, Dun Laoghaire County Dublin, Ireland, A96 AX76
T: +44 (0)1924 893380
F: +44 (0)1924 894320
E: sales@belllighting.co.uk
www.belllighting.co.uk