Beijer ELECTRONICS GT-3901 Analog Input Module

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-product

Specifications

  • Model: GT-3901 Analog Input Module
  • Input: 1 channel 3-phase AC measurement, Lx-Ly
  • Maximum Voltage: 500 VAC
  • Maximum Current: 1 A
  • Resolution: 12-bit
  • Terminal Type: Cage Clamp, Not Removable

Product Usage Instructions

Installation

  • Ensure the power is off before connecting the module. Follow the wiring diagram provided in the manual for proper installation.

Setup

  • Configure the module according to your system requirements.
  • Refer to the G-series system overview for understanding the data mapping.

Usage

  • Once installed and set up, monitor the LED indicators for channel status. Data mapping into the image table can be done for further analysis.

About This Manual

This manual contains information on the software and hardware features of the Beijer Electronics GT-3901 Analog Input Module. It provides in-depth specifications, guidance on installation, setup, and usage of the product.

Symbols Used in This Manual

This publication includes Warning, Caution, Note and Important icons where appropriate, to point out safety-related, or other important information. The corresponding symbols should be interpreted as follows:

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-1WARNING

The Warning icon indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury, and major damage to the product.

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-2CAUTION

The Caution icon indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury, and moderate damage to the product.

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-3NOTE

The Note icon alerts the reader to relevant facts and conditions.

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-4IMPORTANT

The Important icon highlights important information.

Safety

Before using this product, please read this manual and other relevant manuals carefully. Pay full attention to safety instructions!

In no event will Beijer Electronics be responsible or liable for damages resulting from the use of this product.

The images, examples and diagrams in this manual are included for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Beijer Electronics cannot take responsibility or liability for actual use based on the examples and diagrams.

Product Certifications

The product has the following product certifications.

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-5

General Safety Requirements

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-1WARNING

  • Do not assemble the products and wires with power connected to the system. Doing so cause an “arc flash”, which can result in unexpected dangerous events (burns, fire, flying objects, blast pressure, sound blast, heat).
  • Do not touch terminal blocks or IO modules when the system is running. Doing so may cause electric shock, short circuit or malfunction of the device.
  • Never let external metallic objects touch the product when the system is running. Doing so may cause electric shock, short circuit or malfunction of the device.
  • Do not place the product near inflammable material. Doing so may cause a fire.
  • All wiring work should be performed by an electrical engineer.
  • When handling the modules, ensure that all persons, the workplace and the packing are well grounded. Avoid touching conductive components, the modules contain electronic components that may be destroyed by electrostatic discharge.

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-2CAUTION

  • Never use the product in environments with temperature over 60℃. Avoid placing the product in direct sunlight.
  • Never use the product in environments with over 90% humidity.
  • Always use the product in environments with pollution degree 1 or 2.
  • Use standard cables for wiring.

About the G-series System

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-6

System overview

  • Network Adapter Module: The network adapter module forms the link between the field bus and the field devices with the expansion modules. The connection to different field bus systems can be established by each of the corresponding network adapter module, e.g., for MODBUS TCP, Ethernet IP, EtherCAT, PROFINET, CC-Link IE Field, PROFIBUS, CANopen, DeviceNet, CC-Link, MODBUS/Serial etc.
  • Expansion Module: Expansion module types: Digital IO, Analog IO, and Special modules.
  • Messaging: The system uses two types of messaging: Service messaging and IO messaging.

IO Process Data Mapping

An expansion module has three types of data: IO data, configuration parameter, and memory register. The data exchange between the network adapter and the expansion modules is made via IO process image data by internal protocol.

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-7

Data flow between network adapter (63 slots) and expansion modules

The input and output image data depend on the slot position and the data type of the expansion slot. The ordering of input and output process image data is based on the expansion slot position. Calculations for this arrangement are included in the manuals for network adapter and programmable IO modules.

Valid parameter data depends on the modules in use. For example, analog modules have settings of either 0-20 mA or 4-20 mA, and temperature modules have settings such as PT100, PT200, and PT500. The documentation for each module provides a description of the parameter data.

Specifications

Environment Specifications

Operating temperature -20°C – 60°C
UL temperature -20°C – 60°C
Storage temperature -40°C – 85°C
Relative humidity 5% – 90% non-condensing
Mounting DIN rail
Shock operating IEC 60068-2-27 (15G)
Vibration resistance IEC 60068-2-6 (4 g)
Industrial emissions EN 61000-6-4: 2019
Industrial immunity EN 61000-6-2: 2019
Installation position Vertical and horizontal
Product certifications CE, FCC

General Specifications

Power dissipation Max. 125 mA @ 5 VDC
Isolation I/O to Logic: Photocoupler isolation

Field power: Non-isolation

Field power Supply voltage: 24 VDC nominal Voltage range: 18 – 30 VDC

Power dissipation: 0 mA @ 24 VDC

Wiring I/O cable max. 2.0mm2 (AWG 14)
Weight 63 g
Module size 12 mm x 99 mm x 70 mm

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-3NOTE

  • The measuring accuracy is reduced, if the extended temperature range is used (-40 – 70 ℃).
  • If the input value is small, the error of calculation value can be large (please input 10% or more of the whole range).

Dimensions

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-8

Module dimensions (mm)

Input Specifications

Number of channels 3 Ch voltage input, 3 Ch current input via CT
Indicators Status, VL1, VL2, VL3, IL1, IL2, IL3
Maximum input voltage range VLN= 288 VAC

VLL= 500 VAC

UL certified voltage range VLN= 240 VAC
Input resistance voltage path 1200 kΩ
Measuring current 1 A (max.)

CT 1: 4000 (max.)

Input resistance current path 30 mΩ
Resolution 24 bits
Input frequency range 45 – 65 Hz
Measured values Angle, Voltage, Current, Power, Energy, Frequency, Power Factors
Measuring error Voltage & current: 0.5 % @ -20 – 50 ℃ Voltage & current: 1 % @ -20 – 60 ℃ Voltage & current: 1.5 % @ -40 – 70 ℃ Frequency: ±0.1 Hz

Phase angle: ±0.6 ⁰

Update Cycle of Process Data

Read data Update time
Max
RMS voltage 300 us
Max. RMS voltage 300 us
Min. RMS voltage 300 us
RMS current 300 us
Max. RMS current 300 us
Min. RMS current 300 us
Apparent power 250 us
Active power 350 us
Max. active power 350 us
Min active power 350 us
Reactive power 2000 us
Apparent energy 100 ms
Total apparent energy 100 ms
Active energy 100 ms
Total active energy 100 ms
Reactive energy 100 ms
Total reactive energy 100 ms
cos phi 200 us
Supply network frequency 200 us
Max. supply network frequency 200 us
Min. supply network frequency 200 us
Phase angle phi 300 us

Wiring Diagram

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-9

Pin no. Signal description
0 Voltage input 0 (L1)
1 Voltage input 1 (L2)
2 Voltage input 2 (L3)
3 Voltage input common (neutral)
4 Current input L1
5 Current input N1
6 Current input L2
7 Current input N1
8 Current input L3
9 Current input N3

LED Indicator

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-10

LED no. LED function / description LED color
0 Status Green
1 Voltage input channel 1 Green
2 Current input channel 1 Green
3 Voltage input channel 2 Green
4 Current input channel 2 Green
5 Voltage input channel 3 Green
6 Current input channel 3 Green

LED Channel Status

Status LED Indicates
Over voltage Voltage input LED: Off Error occurred
Voltage input LED: Green Normal operation
Under voltage Voltage input LED: Off Error occurred
Voltage input LED: Green Normal operation
Over current Current input LED: Off Error occurred
Current input LED: Green Normal operation
No signal Voltage input LED: Off

Current input LED: Off

Error occurred
Voltage input LED: Green

Current input LED: Green

Normal operation
G-Bus status Status LED: Off Disconnection
Status LED: Green Connection

* Please refer to Input Image Data.(Error Byte)

Mapping Data Into the Image Table

Byte Output data Input data
0 Control byte 0 Status byte 0
1 Control byte 1 Status byte 1
2 Control byte 2 Status byte 2
3 Control byte 3 Status byte 3
4 Not used Error byte 0
5 Error byte 1
6 Error byte 2
7 Reserved
8 Process value 1
9
10
11
12 Process value 2
13
14
15
16 Process value 3
17
18
19
20 Process value 4
21
22
23

Input Image Value

Status bytes

Status byte 0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
RES Measure select CON_ID
Measure select 0 = Voltage        
  1 = Current
  2 = Power
  3 = PF
  4 = Phase angle
  5 = Frequency
  6 = Energy
  7 = Reserved
RES Resetting all min / max / energy values
CON_ID CON_ID
Status byte 1
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Measure select CON_ID
Measure select 0 = Voltage        
  1 = Current
  2 = Power
  3 = PF
  4 = Phase angle
  5 = Frequency
  6 = Energy
  7 = Reserved
CON_ID CON_ID
Status byte 2
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Measure Select CON_ID
Measure select 0 = Voltage        
  1 = Current
  2 = Power
  3 = PF
  4 = Phase angle
  5 = Frequency
  6 = Energy
  7 = Reserved
CON_ID CON_ID
Status byte 3
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Measure select CON_ID
Measure select 0 = Voltage

1 = Current

2 = Power

3 = PF

4 = Phase angle 5 = Frequency

6 = Energy

7 = Reserved

CON_ID CON_ID

Error bytes

Error byte 0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
ERR_VL2 VL2_Error code ERR_VL1 VL1_Error code
ERR_VL1 Phase 1 voltage input ERROR 0 = OK

1 = Error occurred

ERR_VL2 Phase 2 voltage input ERROR 0 = OK

1 = Error occurred

Error byte 1
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
ERR_IL1 IL1_Error code ERR_VL3 VL3_Error code
ERR_VL3 Phase 3 voltage input ERROR 0 = OK

1 = Error occurred

ERR_IL1 Phase 1 current input ERROR 0 = OK

1 = Error occurred

Error byte 2
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
ERR_IL3 IL3_Error code ERR_IL2 IL2_Error code
ERR_IL2 Phase 2 current input ERROR 0 = OK

1 = Error occurred

ERR_IL3 Phase 3 current input ERROR 0 = OK

1 = Error occurred

Error code 0 = No error

1 = Over input 2 = Under input 3 = No connect

Process value bytes

Process value 0-0 byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Proc0[7 : 0]
Proc0[7 : 0] Process value 0 of status byte 0
Process value 0-1 byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Proc0[15 : 8]
Proc0[15 : 8] Process value 0 of status byte 0
Process value 0-2 byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Proc0[23 : 16]
Proc0[23 : 16] Process value 0 of status byte 0
Process value 0-3 byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Proc0[31 : 24]
Proc0[31 : 24] Process value 0 of status byte 0
Process value 1-0 byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Proc1[7 : 0]
Proc1[7 : 0] Process value 1 of status byte 1
Process value 1-1 byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Proc1[15 : 8]
Proc1[15 : 8] Process value 1 of status byte 1
Process value 1-2 byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Proc1[23 : 16]
Proc1[23 : 16] Process value 1 of status byte 1
Process value 1-3 byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Proc1[31 : 24]
Proc1[32 : 24] Process value 1 of status byte 1
Process value 2-0 byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Proc2[7 : 0]
Proc2[7 : 0] Process value 2 of status byte 2
Process value 2-1 byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Proc2[15 : 8]
Proc2[15 : 8] Process value 2 of status byte 2
Process value 2-2 byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Proc2[23 : 16]
Proc2[23 : 16] Process value 2 of status byte 2
Process value 2-3 byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Proc2[31 : 24]
Proc2[31 : 24] Process value 2 of status byte 2
Process value 3-0 byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Proc3[7 : 0]
Proc3[7 : 0] Process value 3 of status byte 3
Process value 3-1 byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Proc3[15 : 8]
Proc3[15 : 8] Process value 3 of status byte 3
Process value 3-2 byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Proc3[23 : 16]
Proc3[23 : 16] Process value 3 of status byte 3
Process value 3-3 byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Proc3[31 : 24]
Proc3[31 : 24] Process value 3 of status byte 3

Output Image Value

Control byte 0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
RESET Measure select CON_ID
Measure select 0 = Voltage

1 = Current

2 = Power

3 = PF

4 = Phase angle 5 = Frequency

6 = Energy

7 = Reserved

RESET Resetting all of the min/max energy values
CON_ID CON_ID
Control byte 1
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Measure select CON_ID
Measure select 0 = Voltage        
  1 = Current
  2 = Power
  3 = PF
  4 = Phase angle
  5 = Frequency
  6 = Energy
  7 = Reserved
CON_ID CON_ID
Control byte 2
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Measure select CON_ID
Measure select 0 = Voltage        
  1 = Current
  2 = Power
  3 = PF
  4 = Phase angle
  5 = Frequency
  6 = Energy
  7 = Reserved
CON_ID CON_ID
Control byte X3
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Measure select CON_ID
Measure select 0 = Voltage

1 = Current

2 = Power

3 = PF

4 = Phase angle 5 = Frequency

6 = Energy

7 = Reserved

CON_ID CON_ID
CON_ID Measured value Data type Scaling
Measure select = Voltage
00 RMS voltage L1-N uint32 0.01 V
01 RMS voltage L2-N uint32 0.01 V
02 RMS voltage L3-N uint32 0.01 V
03 Max. RMS voltage L1-N uint32 0.01 V
04 Max. RMS voltage L2-N uint32 0.01 V
05 Max. RMS voltage L3-N uint32 0.01 V
06 Min. RMS voltage L1-N uint32 0.01 V
07 Min. RMS voltage L2-N uint32 0.01 V
08 Min. RMS voltage L3-N uint32 0.01 V
09 Reserved
0A
0B
0C
0D
0E
0F
CON_ID Measured value Data type Scaling
Measure select = Current
00 RMS Current L1-N uint32 0.001 A
01 RMS Current L2-N uint32 0.001 A
02 RMS Current L3-N uint32 0.001 A
03 Max. RMS Current L1-N uint32 0.001 A
04 Max. RMS Current L2-N uint32 0.001 A
05 Max. RMS Current L3-N uint32 0.001 A
06 Min. RMS Current L1-N uint32 0.001 A
07 Min. RMS Current L2-N uint32 0.001 A
08 Min. RMS Current L3-N uint32 0.001 A
09 Reserved
0A
0B  
0C
0D
0E
0F
CON_ID Measured value Data type Scaling
Measure select = Power
00 Apparent power L1 uint32 0.01VA
01 Apparent power L2 uint32 0.01VA
02 Apparent power L3 uint32 0.01VA
03 Active power L1 int32 0.01W
04 Active power L2 int32 0.01W
05 Active power L3 int32 0.01W
06 Max. active power L1 int32 0.01W
07 Max. active power L2 int32 0.01W
08 Max. active power L3 int32 0.01W
09 Min. active power L1 int32 0.01W
0A Min. active power L2 int32 0.01W
0B Min. active power L3 int32 0.01W
0C Reactive power L1 int32 0.01VAR
0D Reactive power L2 int32 0.01VAR
0E Reactive power L3 int32 0.01VAR
CON_ID Measured value Data type Scaling
Measure select = Energy
00 Apparent energy L1 uint32 Set the parameter
01 Apparent energy L2 uint32
02 Apparent energy L3 uint32
03 Total apparent energy uint32
04 Active energy L1 int32
05 Active energy L2 int32
06 Active energy L3 int32
07 Total active energy int32
08 Reactive energy L1 int32
09 Reactive energy L2 int32
0A Reactive energy L3 int32
0B Total reactive energy int32
0C Reserved
0D
0E
0F
CON_ID Measured value Data type Scaling
Measure select = Power factor    
00 Power factor L1 int32 0.01
01 Power factor L2 int32 0.01
02 Podwr factor L3 int32 0.01
03 Reserved
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
CON_ID Measured value Data type Scaling
Measure Select = Frequency
00 Supply network frequency L1 uint32 0.01 Hz
01 Supply network frequency L2 uint32 0.01 Hz
02 Supply network frequency L3 uint32 0.01 Hz
03 Max. supply network frequency L1 uint32 0.01 Hz
04 Max. supply network frequency L2 uint32 0.01 Hz
05 Max. supply network frequency L3 uint32 0.01 Hz
06 Min. supply network frequency L1 uint32 0.01 Hz
07 Min. supply network frequency L2 uint32 0.01 Hz
08 Min. supply network frequency L3 uint32 0.01 Hz
09 Reserved
0A
0B
0C
0D
0E

Parameter Data

Valid Parameter length: 5 Bytes

  Bit#7 Bit#6 Bit#5 Bit#4 Bit#3 Bit#2 Bit#1 Bit#0
Byte#0 CT sensor 1 : x
Value for the current transformer ratio divisor
Byte#1 Bit#7 Bit#6 Bit#5 Bit#4 Bit#3 Bit#2 Bit#1 Bit#0
Frequency Scaling for energy values CT sensor 1 : x
0 = 45 – 55

Hz

0 = 1m Wh/VARh/VAh Value for the current transformer ratio divisor
1 = 55 – 65

Hz

1 = 0.01 Wh/VARh/VAh  
  2 = 0.1 Wh/VARh/VAh
3 = 1 Wh/VARh/VAh
4 = 0.01k Wh/VARh/VAh
5 = 0.1k Wh/VARh/VAh
6 = 1k Wh/VARh/VAh
7 = Reserved
Byte#2 Bit#7 Bit#6 Bit#5 Bit#4 Bit#3 Bit#2 Bit#1 Bit#0
Overvoltage threshold Lx (value) resolution 0.2 V
Overvoltage threshold = 250 V + value * 0.2 V (max. 300 V)
Byte#3 Bit#7 Bit#6 Bit#5 Bit#4 Bit#3 Bit#2 Bit#1 Bit#0
Undervoltage threshold Lx (value) resolution 0.5 V
Undervoltage threshold = 0 V + value * 0.5 V (max. 125 V)
Byte#4 Bit#7 Bit#6 Bit#5 Bit#4 Bit#3 Bit#2 Bit#1 Bit#0
Overcurrent threshold Lx (value) Resolution 2 mA
Overcurent threshold = 0.8 A + value * 0.002 A (max. 1.3 A)

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-3NOTE

  • Set frequency to get the correct power factor and energy.

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-11

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-3NOTE

  • The reactive power measurement is negative when the load is capacitive, and when the load is inductive. The sign of the reactive power can therefore be used to reflect the sign of the power factor.

Power factor = (Sign fundamental reactive power) * (abs (Active power)) / Apparent power)

Example of setting

  • Read data: Phase1 RMS Voltage / RMS Current / Apparent power / Active power.
  • Input value: 220 V, 1000 A, PF 0.5.
  • Parameter: CT 1: 1000, input frequency 55-65 Hz, overvoltage threshold 260 V, other is Default(0).

Overvoltage threshold = (260 V (user setting value) – 250 V (default setting value)) / 0.2 V. Resolution: 0.2 V.

Overcurrent threshold = 1000 A (user setting CT 1: 1000) = ((1 A (user setting value) – 0.8 (default setting value)) / 0.001) * 1000 (CT). Resolution: 0.001 A.

All of default value is 0.

  1. Set the Parameter.
    Parameter Value
    CT sensor 1 : x (12 bit) 001111101000 (bit) Set CT 1000
    Scaling for energy values (3 bit) 000 (bit) Set 1m Wh/VARh/VAh
    Frequency (1 bit) 1 (bit) Set 55-65 Hz
    Overvoltage threshold Lx (8 bit) 00110010 (bit) Set 260 V
    Undervoltage threshold Lx (8 bit) 00000000 (bit) Set 0 V (default)
    Overcurrent threshold Lx(8 bit) 00000000 (bit) Set 0.8 A (default)
    All of parameter E8 83 32 00 00 (Byte hex)
  2. Set the Control byte (see chapter Output image value).
      Bit#7 Bit#6 Bit#5 Bit#4 Bit#3 Bit#2 Bit#1 Bit#0
    Control byte #0 RES Measure select (Voltage) CON_ID (RMS voltage L1-N)
    0 0 0 0 0 0 0 0
    Control byte #1 Reserved Measure select (Current) CON_ID (RMS current L1-N)
    0 0 0 1 0 0 0 0
    Control byte #2 Reserved Measure select (Power) CON_ID (Apparent power L1)
    0 0 0 1 0 0 0 0
    Control byte #3 Reserved Measure select (Power) CON_ID (Active power L1)
    0 0 0 1 0 0 1 1
  3. Check the Status byte. When Status byte and Control byte are the same, the Process value is updated.
      Bit#7 Bit#6 Bit#5 Bit#4 Bit#3 Bit#2 Bit#1 Bit#0
    Status byte #0 RES Measure select (Voltage) CON_ID (RMS voltage L1-N)
    0 0 0 0 0 0 0 0
    Status byte #0 Reserved Measure select (Current) CON_ID (RMS current L1-N)
    0 0 0 1 0 0 0 0
    Status byte #0 Reserved Measure select (Power) CON_ID (Apparent power L1)
    0 0 0 1 0 0 0 0
    Status byte #0 Reserved Measure select (Power) CON_ID (Active power L1)
    0 0 0 1 0 0 1 1
  4. Check the Process value.
    Process value#0 (RMS Voltage) 000055F0(Dword hex) 22000(Dec) 220 V
    Process value#1 (RMS Current) 000F4240(Dword hex) 1000000(Dec) 1000 A
    Process value#2 (Apparent power) 014FB180(Dword hex) 22000000(Dec) 220 kVA
    Process value#3 (Active power) 00A7D8C0(Dword hex) 11000000(Dec) 110 kW

Hardware Setup

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-2CAUTION

  • Always read this chapter before installing the module!
  • Hot surface! The surface of the housing can become hot during operation. If the device is used in high ambient temperatures, always let the device cool down before touching it.
  • Working on energized devices can damage the equipment! Always turn off the power supply before working on the device.

Space Requirements

The following drawings show the space requirements when installing the G-series modules. The spacing creates space for ventilation, and prevents conducted electromagnetic interference from influencing the operation. Installation position is valid vertical and horizontal. The drawings are illustrative and may be out of proportion.

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-2CAUTION

NOT following the space requirements may result in damaging the product.

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-12

Mount Module to DIN Rail

The following chapters describe how to mount the module to the DIN rail.

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-2CAUTION

The module must be fixed to the DIN rail with the locking levers.

Mount GL-9XXX or GT-XXXX Module

The following instructions apply to these module types:

  • GL-9XXX
  • GT-1XXX
  • GT-2XXX
  • GT-3XXX
  • GT-4XXX
  • GT-5XXX
  • GT-7XXX

GN-9XXX modules have three locking levers, one at the bottom and two on the side. For mounting instructions, refer to Mount GN-9XXX Module.

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-13

Mount GN-9XXX Module

To mount or dismount a network adapter or programmable IO module with the product name GN-9XXX, for example GN-9251 or GN-9371, see the following instructions:

Beijer-ELECTRONICS-GT-3901-Analog-Input-Module-fig-14

The information in this document is subject to change without notice and is provided as available at the time of printing. Beijer Electronics AB reserves the right to change any information without updating this publication. Beijer Electronics AB assumes no responsibility for any errors that may appear in this document. All examples in this document are only intended to improve understanding of the functionality and handling of the equipment. Beijer Electronics AB cannot assume any liability if these examples are used in real applications.

In view of the wide range of applications for this software, users must acquire sufficient knowledge themselves in order to ensure that it is correctly used in their specific application. Persons responsible for the application and the equipment must themselves ensure that each application is in compliance with all relevant requirements, standards, and legislation in respect to configuration and safety. Beijer Electronics AB will accept no liability for any damage incurred during the installation or use of equipment mentioned in this document. Beijer Electronics AB prohibits all modification, changes, or conversion of the equipment.

More Info

Head Office

Beijer Electronics AB

Box 426

201 24 Malmö, Sweden

FAQ

  • Q: What do the LED indicators signify?
    • A: The LED indicators show the status of each channel on the module. Refer to the LED Channel Status section in the manual for detailed information.
  • Q: How do I ensure safety while using the product?
    • A: Make sure to follow the general safety requirements mentioned in the manual. Ensure proper grounding and avoid touching conductive components to prevent damage from electrostatic discharge.