Beijer-logo

Beijer ELECTRONICS GT-123F Digital Input Module

Beijer-ELECTRONICS-GT-123F-Digital-Input-Module-product

Specifications

  • Model: GT-123F Digital Input Module
  • Channels: 16
  • Voltage: 24 VDC
  • Type: Sink/Source
  • Connector: 20 pt

Product Usage Instructions

About This Manual
This manual contains detailed information on the Beijer Electronics GT-123F Digital Input Module, including software and hardware features. It provides specifications, installation guidance, setup instructions, and product usage information.

Safety
Ensure to follow all safety guidelines mentioned in this manual to prevent any potential hazards during installation and usage of the product.

Wiring Diagram
Refer to the wiring diagram section (Page 11) in the manual for detailed instructions on how to wire the digital input module correctly.

LED Indicator
The LED indicator section (Page 12) provides information on the channel status and how to interpret the LED signals for each channel.

Hardware Setup
Follow the hardware setup instructions (Page 16) to understand the space requirements, mounting the module to a DIN rail, and connecting field power and data pins.

Copyright © 2025 Beijer Electronics AB. All rights reserved.

  • The information in this document is subject to change without notice and is provided as available at the time of printing. Beijer Electronics AB reserves the right to change any information without updating this publication. Beijer Electronics AB assumes no responsibility for any errors that may appear in this document. All examples in this document are only intended to improve understanding of the functionality and handling of the equipment. Beijer
  • Electronics AB cannot assume any liability if these examples are used in real applications.
  • In view of the wide range of applications for this software, users must acquire sufficient knowledge themselves in order to ensure that it is correctly used in their specific application. Persons responsible for the application and the equipment must themselves ensure that each application is in compliance with all relevant requirements, standards, and legislation in respect to configuration and safety. Beijer Electronics AB will accept no liability for any damage incurred during the installation or use of equipment mentioned in this document. Beijer Electronics AB prohibits all modification, changes, or conversion of the equipment.

Head Office Beijer Electronics AB Box 426

About This Manual

This manual contains information on the software and hardware features of the Beijer Electronics GT-123F Digital Input Module. It provides in-depth specifications, guidance on installation, setup, and usage of the product.

Symbols Used in This Manual
This publication includes Warning, Caution, Note, and Important icons where appropriate, to point out safety-related or other important information. The corresponding symbols should be interpreted as follows:

Beijer-ELECTRONICS-GT-123F-Digital-Input-Module-fig- (1)WARNING
The Warning icon indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury, and major damage to the product.

Beijer-ELECTRONICS-GT-123F-Digital-Input-Module-fig- (2)CAUTION
The Caution icon indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury, and moderate damage to the product.

Beijer-ELECTRONICS-GT-123F-Digital-Input-Module-fig- (3)NOTE
The Note icon alerts the reader to relevant facts and conditions.

Beijer-ELECTRONICS-GT-123F-Digital-Input-Module-fig- (4)IMPORTANT
The Important icon highlights important information.

Safety

  • Before using this product, please read this manual and other relevant manuals carefully. Pay full attention to safety instructions!
  • In no event will Beijer Electronics be responsible or liable for damages resulting from the use of this product.
  • The images, examples and diagrams in this manual are included for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Beijer Electronics cannot take responsibility or liability for actual use based on the examples and diagrams.

Product Certifications
The product has the following product certifications.

Beijer-ELECTRONICS-GT-123F-Digital-Input-Module-fig- (5)

General Safety Requirements

WARNING

  • Do not assemble the products and wires with power connected to the system. Doing so cause an “arc flash”, which can result in unexpected dangerous events (burns, fire, flying objects, blast pressure, sound blast, heat).
  • Do not touch terminal blocks or IO modules when the system is running. Doing so may cause an electric shock, a short circuit or a malfunction of the device.
  • Never let external metallic objects touch the product when the system is running. Doing so may cause an electric shock, short circuit or a malfunction of the device.
  • Do not place the product near inflammable material. Doing so may cause a fire.
  • All wiring work should be performed by an electrical engineer.
  • When handling the modules, ensure that all persons, the workplace and the packing are well grounded. Avoid touching conductive components, the modules contain electronic components that may be destroyed by electrostatic discharge.

CAUTION

  • Never use the product in environments with temperature over 60℃. Avoid placing the product in direct sunlight.
  • Never use the product in environments with over 90% humidity.
  • Always use the product in environments with pollution degree 1 or 2.
  • Use standard cables for wiring.

About the G-series System

Beijer-ELECTRONICS-GT-123F-Digital-Input-Module-fig- (6)

System overview

  • Network Adapter Module – The network adapter module forms the link between the field bus and the field devices with the expansion modules. The connection to different field bus systems can be established by each of the corresponding network adapter module, e.g., for MODBUS TCP, Ethernet IP, EtherCAT, PROFINET, CC-Link IE Field, PROFIBUS, CANopen, DeviceNet, CC-Link, MODBUS/Serial etc.
  • Expansion Module – Expansion module types: Digital IO, Analog IO, and Special modules.
  • Messaging – The system uses two types of messaging: Service messaging and IO messaging.

IO Process Data Mapping
An expansion module has three types of data: IO data, configuration parameter, and memory register. The data exchange between the network adapter and the expansion modules is made via IO process image data by internal protocol.

Beijer-ELECTRONICS-GT-123F-Digital-Input-Module-fig- (7)

  • Data flow between network adapter (63 slots) and expansion modules
  • The input and output image data depend on the slot position and the data type of the expansion slot. The ordering of input and output process image data is based on the expansion slot position. Calculations for this arrangement are included in the manuals for network adapter and programmable IO modules.
  • Valid parameter data depends on the modules in use. For example, analog modules have settings of either 0-20 mA or 4-20 mA, and temperature modules have settings such as PT100, PT200, and PT500. The documentation for each module provides a description of the parameter data.

Specifications

Environmental Specifications

Operating temperature-20°C – 60°C
UL temperature-20°C – 60°C
Storage temperature-40°C – 85°C
Relative humidity5% – 90% non-condensing
MountingDIN rail
Shock operatingIEC 60068-2-27 (15G)
Vibration resistanceIEC 60068-2-6 (4 g)
Industrial emissionsEN 61000-6-4: 2019
Industrial immunityEN 61000-6-2: 2019
Installation positionVertical and horizontal
Product certificationsCE, FCC, UL, cUL

General Specifications

Power dissipationMax. 50 mA @ 5 VDC
IsolationI/O to logic: Photocoupler isolation
UL field powerSupply voltage: 24 VDC nominal, class 2
Field powerSupply voltage: 24 VDC nominal Voltage range: 15 – 30 VDC

Power dissipation: 0 mA @ 24 VDC

WiringConnector type, up to AWG22

Module connector: HIF3BA-20D-2.54DSA

Weight52 g
Module size12 mm x 99 mm x 70 mm

Dimensions

Beijer-ELECTRONICS-GT-123F-Digital-Input-Module-fig- (8)Module dimensions (mm)

Input Specifications

Inputs per module16 points, universal (sink or source) type
Indicators16 green input status
On-state voltage24 VDC nominal

15 – 30 VDC @ 60 ℃

On-state current2.25 mA @ 24 VDC

3 mA @ 30 VDC

Off-state voltage9.3 VDC @ 25 ℃
Input signal delayOFF to ON: Max. 0.3 ms

ON to OFF: Max. 0.3 ms

Input filterAdjustable, up to 10 ms
Nominal input impedance10.2 kΩ typical
Common type16 points / 2 COM (universal)

Wiring Diagram

Beijer-ELECTRONICS-GT-123F-Digital-Input-Module-fig- (9)

Pin no.Signal description
1Input channel 0
2Input channel 1
3Input channel 2
4Input channel 3
5Input channel 4
6Input channel 5
7Input channel 6
8Input channel 7
9Input channel 8
10Input channel 9
11Input channel 10
12Input channel 11
13Input channel 12
14Input channel 13
15Input channel 14
16Input channel 15
17Common (sink oper. 0 V / source oper. 24 V)
18Common (sink oper. 0 V / source oper. 24 V)
19NC
20NC

LED Indicator

Beijer-ELECTRONICS-GT-123F-Digital-Input-Module-fig- (10)

LED no.LED function / descriptionLED color
0INPUT channel 0Green
1INPUT channel 1
2INPUT channel 2
3INPUT channel 3
4INPUT channel 4
5INPUT channel 5
6INPUT channel 6
7INPUT channel 7
8INPUT channel 8
9INPUT channel 9
10INPUT channel 10
11INPUT channel 11
12INPUT channel 12
13INPUT channel 13
14INPUT channel 14
15INPUT channel 15

LED Channel Status

StatusLEDIndication
No signalOffNormal operation
On signalGreenNormal operation

Mapping Data Into the Image Table

Input module data

D7D6D5D4D3D2D1D0
D15D14D13D12D11D10D9D8

Input image value

Bit no.Bit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
Byte 0D7D6D5D4D3D2D1D0
Byte 1D15D14D13D12D11D10D9D8

Parameter Data

Valid parameter length: 2 bytes

Bit no.Bit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
Byte 0Input filter value: 0 – 10 (unit: ms)
Byte 1Reserved

Hardware Setup

CAUTION

  • Always read this chapter before installing the module!
  • Hot surface! The surface of the housing can become hot during operation. If the device is used in high ambient temperatures, always let the device cool down before touching it.
  • Working on energized devices can damage the equipment! Always turn off the power supply before working on the device.

Space Requirements
The following drawings show the space requirements when installing the G-series modules. The spacing creates space for ventilation, and prevents conducted electromagnetic interference from influencing the operation. Installation position is valid vertical and horizontally. The drawings are illustrative and may be out of proportion.

CAUTION
NOT following the space requirements may result in damaging the product.

Beijer-ELECTRONICS-GT-123F-Digital-Input-Module-fig- (11) Mount Module to DIN Rail
The following chapters describe how to mount the module to the DIN rail.

CAUTION
The module must be fixed to the DIN rail with the locking levers.

Mount GL-9XXX or GT-XXXX Module
The following instructions apply to these module types:

  • GL-9XXX
  • GT-1XXX
  • GT-2XXX
  • GT-3XXX
  • GT-4XXX
  • GT-5XXX
  • GT-7XXX

GN-9XXX modules have three locking levers, one at the bottom and two on the side. For mounting instructions, refer to Mount GN-9XXX Module.

Beijer-ELECTRONICS-GT-123F-Digital-Input-Module-fig- (12)

Mount GN-9XXX Module
To mount or dismount a network adapter or programmable IO module with the product name GN-9XXX, for example GN-9251 or GN-9371, see the following instructions:

Beijer-ELECTRONICS-GT-123F-Digital-Input-Module-fig- (13)

Field Power and Data Pins
Communication between the G-series network adapter and the expansion module, as well as system /field power supply of the bus modules is carried out via the internal bus. It is comprised of 2 Field Power Pins and 6 Data Pins.

WARNING
Do not touch the data and field power pins! Touching can result in soiling and damage by ESD noise.

Beijer-ELECTRONICS-GT-123F-Digital-Input-Module-fig- (14)

Pin no.NameDescription
P1System VCCSystem supply voltage (5 VDC)
P2System GNDSystem ground
P3Token outputToken output port of the processor module
P4Serial outputTransmitter output port of the processor module
P5Serial inputReceiver input port of the processor module
P6ReservedReserved for bypass token
P7Field GNDField ground
P8Field VCCField supply voltage (24 VDC)

FAQs

Q: What do the Warning and Caution icons signify in the manual?
Answer: The Warning icon indicates potentially hazardous situations that could result in death or serious injury if not avoided. The Caution icon signifies potentially hazardous situations that could lead to minor or moderate injury.

Documents / Resources

Beijer ELECTRONICS GT-123F Digital Input Module [pdf] User Manual
GT-123F, GT-123F Digital Input Module, GT-123F, Digital Input Module, Input Module, Module

References

Leave a comment

Your email address will not be published. Required fields are marked *