Beijer Electronics GN-9289 Remote I-O Network Adapters
Specifications
- Product: G- and M-series network adapters
- Interface: RJ45 Ethernet
- Default IP for Remote I/O adapter: 192.168.1.100
Adjust PC Settings
Adjust the PC port to an IP address with the same subnet as the Remote I/O adapter:
- Open Network & Internet settings > Change adapter options > Internet Protocol Version 4 (TCP/IPv4) >Properties.
- Set IP address to 192.168.1.99 and Subnet mask to 255.255.255.0.
Power Up Device
Power up or restart the device to enter IAP mode.
Access Web Interface
- Ping the adapter from a command prompt:
ping 192.168.1.100
- Enter the web page from a standard web browser (Edge / Chrome) using IP address 192.168.1.100.
Firmware Update
- Login with User ID:
beijer
and Password:beijer
. - Select Choose File and upload the firmware file (*.bin).
- Press Update Firmware to start the upgrade process.
Complete Update
When the update is completed, reset all dip switches to their initial state and press Reset Adapter.
Update via Ethernet
(LAN cable)
For the Remote I/O network adapters with RJ45 Ethernet interface follow this guide. It’s relevant for all modules supporting the “IAP” firmware update mode these are:
- GN9287/GL9087/M9287 PROFINET
- GN9289/GL9089/M9289 MODBUS TCP/UDP
- GN-9284 CC-link IE Field Basic adapters
Note!
Below example show the GN-9289 Modbus TCP and the M9287 / GN-9287 ProfiNet adapters and screenshots made during update procedure. For other network adapters there may be differences, please check specification documents.
- First adjust the port to be used on the PC to an IP address with the same subnet as the Remote I/O adapter. Note, the Beijer Remote I/O adapters uses default IP: 192.168.1.100 Adjust settings in the PC: Open Network & Internet settings > Change adapter options
- Internet Protocol Version 4 (TCP/IPv4) > Properties, then adjust the IP address and Subnet mask settings.
- IP address: 192.168.1.99 and Subnet mask: 255.255.255.0 used in example below.
- Example GN-9289: Set the 10-pol dip switch of the network adapter to value 254 (dec) and then Restart the adapter, that will activate the IAP Mode to give the option to login and update the firmware. IAP mode will set a fixed IP Address of the adapter to 192.168.1.100 *
- Explanation of the dip switch value 254 (dec) = 00 1111 1110 (bin) counting from the dip switch No.1 to the left being the LSB bit.
- Dip switch 2 to 8 = ON and dip switch 1, 9, and 10 = OFF
- Power up / Restart the device, that will enter the IAP mode.
- In IAP mode the MOD LED = Flashing Red/Green, and the NET LED = Stable green.
- Ping the adapter from a command prompt: ping 192.168.1.100
- Enter the web page from a standard web browser (Edge / Chrome). 192.168.1.100
- Login with User id and Password:
- User ID : beijer
- Password : beijer
- To update firmware with binary file, select Choose File:
- Select the firmware file (*.bin) then press “Update Firmware” and the procedure will start. Example: Beijer GN-9289 Rev1.012 (2023-11-14)
- Example: Beijer GN-9287 Rev1.112 (2024-02-23)
- Example: Beijer GN-9287 Rev1.112 (2024-02-23)
- When the update is completed, this message is shown:
- Now reset all dip switches to its initial state, then press “Reset Adapter”.
- Power Off/On to Restart the device.
Note, in the pages below examples how to check the firmware version of the network adapter. - 13. Before using the Modbus adapter, check that the adapter has completed the update:
- a. Checking the Modbus TCP adapter via the built-in web server, use 192.168.1.100 (default IP)
- b. Picture show the adapter GN-9289 and Fiemware Revision: 1.012 (11/14/2023)
- Alternative check the firmware version of the same adapter GN-9289 using IOGuidePro
- a. Select submenu: Tools > Protocol Messenger > Modbus
- b. Device IP and Protocol: Modbus TCP
- c. From the GN-9289 manual read out the Modbus address for the Firmware version, that is address (hex): 1003
- d. Send Modbus message on address (hex): 1003
Example with F/W Rev 1.011 the unit will response: 010B (hex)
- Before using the ProfiNet adapters, check that the adapter has completed the update:
- a. Checking the ProfiNet adapter after firmware update using for example the free tool PRONETA from Siemens.
- b. Picture show the M9287 F/W 1.005 = V1.5.0 in the dialog.
- c. Picture show the GN-9287 F/W 1.112 = V1.112.0 in the dialog.
Initiated by: MCO
Date: 2024-03-11
Approved by
Revision: 3
Revision date: 2024-12-02
FAQ
- Q: How can I check the firmware version of the network adapter?
A: You can check the firmware version by accessing the built-in web server using the default IP or through IOGuidePro as outlined in the user manual.
Documents / Resources
![]() |
Beijer Electronics GN-9289 Remote I-O Network Adapters [pdf] User Guide GN-9289, M9287, GN-9287, GN-9289 Remote I-O Network Adapters, GN-9289, Remote I-O Network Adapters, Network Adapters, Adapters |