PRATICA IP42 AT
ta 0÷40°C
230V-50Hz
IK07 IP42
Pratica IP42 AT Emergency Luminaire
www.beghelli.com
BEGHELLI S.p.A. – Via Mozzeghine 13/15 – località Monteveglio 40053 Valsamoggia (BO) ITALY – Tel. +39 051 9660411 – Fax +39 051 9660444 – N° Verde 800 626626
- For autonomy management refer to the table
- available option
Azione locale su singolo apparecchio Local action on a single device AT + APP |
|||
CONFIGURAZIONI E COMANDI CONFIGURATIONAND COMMANDS |
AT (senza APP) AT (without APP) |
||
CONFIGURAZIONI CONFIGURATION | Autonomia-DuratIon 1h | •Default | •Default |
Autonomia-Duration 1,5h | • | ||
Autonomia-Duration 2h | • | ||
Autonomia- Duration 3h | •con Jumper | • | |
Autonomia-Duration 8h | • | ||
Setting Non-maintained/Maintained (only on Maintained Luminaire) | Settaggio SE/SA (solo su lampade SA) | ||
Settaggio pari/dIspari AT / Setting even/odd AT | • •Deflnito dall’ID del OR code. Non modiflcablle •Preset by ID of OR code. Cannot be modified |
• | |
Durata Test 1h/ pari all’autonomia scelta / Test duration lh or autonomy set | •Durata Test 1h • Test duration 1h | • | |
Reset di fabbrica / Manufacturer data reset | • | ||
Start/Stop Test Funzionale / Start/Stop functional Test | • | ||
COMA FUNZI COMMAN FUNGI |
Sync Test automalco / Sync automatic Test | • |
Use with App B.connect
A- Open App B.connect (available for download on the App Store and Google Play).
B- The configuration of the lamp can be accessed through the “luminaire” menu.
LAMP RESPONSE:
Fast flashing= function performed
Slow flashing= function NOT enabled
No flashing= command NOT received
POSIZIONAMENTO LAMPADA PER COPERTURA APP B.connect (es. molta luce – minore distanza)
POSITION LAMP FOR COVER ENSURE THE PROGRAM (eg. a lot of light – less distance)
AUTOMATIC TESTS PERIODICITY:
FUNCTIONAL TEST (30 sec)= every 28 days
AUTONOMY TEST (1h)= every 26 weeks
Even lamps carry out the autonomy test 1 week after the odd lamps.
(0,2,…,8,A,C,E)= even; (1,3,…,9,B,D,F)= odd.
LED SIGNALS
FIXED GREEN | BATTERY CHARGED |
FLASHING GREEN | BATTERY CHARGING |
ONE RED FLASH | BATTERY ERROR DURATION |
TWO RED FLASHES | LIGHTING LED ERROR |
THREE RED FLASHES | BATTERY DISCONNECTED |
OPENING THE COMMUNICATION FROM APP:
Remove and reset the network for less than 3 seconds.
The communication remains possible for 2 hours and for 1 min the LED flashes orange to signal the communication opening.
The Functional Test and the Functional STOP Test are con- trolled by the B.Connect App at any time without having to open communication with the device.
WARNINGS – GUARANTEE
– This device shall be used exclusively for the purpose for which it has been designed. Any other use is considered
improper and therefore dangerous.
– Rechargeable battery and LED source are non-replaceable type. Contact an authorised technical service centre for any repairs possibly required use only original spare parts. The lacked respect of the above conditions may compromise the safety of the device. *** Caution: electric shock