BANNER-LOGO

BANNER-TL70-Series-Pro-Modbus-Modular-Tower-Light-PRODUCT

Chapter 1

Features

Banner’s TL70 Pro Modbus Modular Tower Light is a 70 mm, modular LED indicator with bright and uniform light. The modularity gives the user flexibility to customize tower lights as needed and change positions in the field. The TL70 is also available preassembled for easy installation.
Modbus control allows access to full color, flashing, and dimming settings, as well as advanced animations and audible tones Up to five indicator segments and one audible segment in one device Rugged, water-resistant IP65 housing with UV-stabilized material Bright, uniform indicator segments appear gray when off to eliminate false indications from ambient light Simple and fast connection with M12 quick-disconnect connector.

BANNER-TL70-Series-Pro-Modbus-Modular-Tower-Light-FEATURED

Models

Segment Models

Model Description
SG-TL70P-L RGB light segment
SG-TL70P-A Audible segment

Pre-Assembled Models

Model Description
TL70PM3Q Modbus RS-485 with three RGB segments
 

TL70PM3AQ

Modbus RS-485 with three RGB segments and an

audible segment

Base Models

Model Description
 

B-TL70PM-Q

Modbus RS-485 base module with an integral 4-pin M12 A-Code male quick-disconnect connector

Chapter 2

Installation Instructions

BANNER-TL70-Series-Pro-Modbus-Modular-Tower-Light-FIG- (2)

Assembling the Modules
To assemble the modules

BANNER-TL70-Series-Pro-Modbus-Modular-Tower-Light-FIG- (3)

Chapter 2 Installation Instructions

  1. Align the notches on each module and press together.
  2. Rotate the top module clockwise to lock it into place (notches shown in the locked position).

Chapter 3
Wiring for Modbus Models

Chapter 4
Modbus Configuration Instructions

For more information about the TL70 Pro Modbus Modular Tower Light device registers, refer to document PN 243474.

Tower Light Segment Modes
Basic Segment Mode
Use a single run time register per LED segment to set it to Off, On, Flash, or Animation mode. Use a single run time register for an audible segment to set it to Off or On. Use additional configuration registers to change color, intensity, and flash speed, select animation type on LED segments , and change volume and tone on audible segments.

Advanced Segment Mode
Use multiple run time registers per LED segment to control color, intensity, flash, and other animation types. Use multiple run time registers for an audible segment to control sync, volume, and tone settings. Use additional configuration registers to create custom intensity and flash speeds.

LED Segment Control

Animation Description
Off Segment is off
Steady Color 1 is solid at a defined intensity
Flash Color 1 flashes at defined speed, color intensity, and pattern
Two Color Flash Color 1 and Color 2 flash alternately at defined speed, color intensities, and pattern
50/50 Color 1 is displayed on 50% of the segment and Color 2 is displayed on the other 50% of the segment at the defined color intensities
 

50/50 Rotate

Color 1 is displayed on 50% of the segment and Color 2 is displayed on the other 50% of the segment while rotating at the defined speed and color intensities
 

Chase

Color 1 is displayed as a single spot against the background of Color 2 while rotating at the defined speed, color intensities, and rotational direction
Intensity Sweep Color 1 repeatedly increases and decreases intensity between 0% to 100% at a defined speed and color intensity
Demo The demo sequence cycles through several sets of colors and configurations to highlight example applications

Audible Segment Control

Setting Description
Audible State Sets the segment to off, on, or synced to the flash pattern of the last LED segment
Audible Volume Defines the volume of the audible tone
Audible Tone Defines the audible tone frequency

Chapter Contents
FCC Part 15 Class A for Unintentional Radiators………………………………………………………………………………………………………………………………. 8
Industry Canada ICES-003(A)………………………………………………………………………………………………………………………………………………………… 8
Dimensions………………………………………………………………………………………………………………………………………………………………………………….. 9

Chapter 5

Specifications

  • Supply Voltage
  • 18 V DC to 30 V DC

Supply Current

 

Device

Typical Current (mA) per Device  

Max Current (mA)

18 V DC 24 V DC 30 V DC
Modbus Base  

60

 

45

 

40

 

75

Light and Audible segment  

110

 

85

 

75

 

125

  • Environmental Rating IP65

Supply Protection Circuitry
Protected against reverse polarity and transient voltages Initial Startup Time 30 seconds

Construction
Bases, segments, and covers: polycarbonate

Operating Temperature

  • –40 °C to +50 °C (–40 °F to +122 °F)
  • 95% at +50 °C maximum relative humidity (non-condensing)

Connections
See “Wiring” on page 5

Audible Alarm

  • Tone 0: 1.7 kHz ± 250 Hz oscillation frequency; maximum intensity (typical) 81 dB at 1 m (3.3 ft)
  • Tone 1: 2.2 kHz ± 250 Hz oscillation frequency; maximum intensity (typical) 100 dB at 1 m (3.3 ft)
  • Tone 2: 2.7 kHz ± 250 Hz oscillation frequency; maximum intensity (typical) 104 dB at 1 m (3.3 ft)
  • Vibration and Mechanical Shock
  • Meets IEC 60068-2-6 requirements (Vibration: 10 Hz to 55 Hz, 0.5 mm amplitude, 5 minutes sweep, 30 minutes dwell)
  • Meets IEC 60068-2-27 requirements (Shock: 15G 11 ms duration, half sine wave)

Certifications

  • Banner Engineering BV
  • Park Lane, Culliganlaan 2F bus 3
  • 1831 Diegem, BELGIUM
  • Turck Banner LTD Blenheim House
  • Blenheim Court
  • Wickford, Essex SS11 8YT

GREAT BRITAIN

Default Light Segment Characteristics

 

Color

Dominant Wavelength (nm) or Color Temperature (CCT) Color Coordinates(1) Lumen Output Per Segment (Typical at 25 °C)
X Y
Green 532 0.181 0.735 34.8
Red 621 0.691 0.308 15.4
Yellow 578 0.473 0.474 21
Blue 467 0.137 0.056 27.6
White 5700K 0.328 0.337 29.7
Cyan 492 0.150 0.334 20.9
Magenta 0.379 0.177 18.7
Amber 590 0.552 0.414 6.6
Rose 0.508 0.230 9.3
Lime Green 565 0.393 0.535 23.8
Sky Blue 485 0.146 0.241 14.1
Orange 600 0.611 0.370 24.1
Violet 0.212 0.091 19.6
Spring Green 509 0.157 0.553 12.7

FCC Part 15 Class A for Unintentional Radiators

This equipment has been tested and found to comply with the limits for a Class A digital device, under Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used by the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. (Part 15.21) Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.

Industry Canada ICES-003(A)
This device complies with CAN ICES-3 (A)/NMB-3(A). Operation is subject to the following two conditions: 1) This device may not cause harmful interference; and 2) This device must accept any interference received, including interference that may cause undesired operation.
Refer to the CIE 1931 chromaticity diagram or color chart to show equivalent color with indicated color coordinates. Actual coordinates may differ by 10%.

Dimensions

BANNER-TL70-Series-Pro-Modbus-Modular-Tower-Light-FIG- (4)

Model Height (H)
1 light module 87.6 mm (3.45 in)
1 light module, 1 audible module 144.3 mm (5.68 in)
2 light modules 137.3 mm (5.41 in)
2 light modules, 1 audible module 194 mm (7.64 in)
3 light modules 187 mm (7.36 in)
3 light modules, 1 audible module 243.7 mm (9.59 in)
4 light modules 236.7 mm (9.32 in)
4 light modules, 1 audible module 293.4 mm (11.55 in)
5 light modules 286.4 mm (11.28 in)
5 light modules, 1 audible module 343.1 mm (13.51 in)

Chapter Contents
Cordsets ……………………………………………………………………………………………………………………………………………………………………………………. 10
Mounting Brackets………………………………………………………………………………………………………………………………………………………………………..11
Elevated Mount System ………………………………………………………………………………………………………………………………………………………………. 12
LMB Sealed Right Angle Bracket ………………………………………………………………………………………………………………………………………………….. 13

Chapter 6

Accessories

Cordsets

BANNER-TL70-Series-Pro-Modbus-Modular-Tower-Light-FIG- (5)

4-Pin Double-Ended, M12 Female-M12 Male Cordset

BANNER-TL70-Series-Pro-Modbus-Modular-Tower-Light-FIG- (6)

Mounting Brackets

All measurements are listed in millimeters unless noted otherwise.

BANNER-TL70-Series-Pro-Modbus-Modular-Tower-Light-FIG- (7)BANNER-TL70-Series-Pro-Modbus-Modular-Tower-Light-FIG- (9)

Elevated Mount System

BANNER-TL70-Series-Pro-Modbus-Modular-Tower-Light-FIG- (10)BANNER-TL70-Series-Pro-Modbus-Modular-Tower-Light-FIG- (11)

LMB Sealed Right Angle Bracket

BANNER-TL70-Series-Pro-Modbus-Modular-Tower-Light-FIG- (12)

Chapter 7

Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not cover damage or liability for misuse, abuse, or improper application or installation of the Banner product.

THIS LIMITED WARRANTY IS EXCLUSIVE AND INSTEAD OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER THE COURSE OF PERFORMANCE, COURSE OF DEALING, OR TRADE USAGE.

This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO THE BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL, OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.

Banner Engineering Corp. reserves the right to change, modify, or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection applications when the product is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval by Banner Engineering Corp will void the product warranties. All specifications published in this document are subject to change; Banner reserves the right to modify product specifications or update documentation at any time. Specifications and product information in English supersede that which is provided in any other language. For the most recent version of any documentation, refer to: www.bannerengineering.com. For patent information, see www.bannerengineering.com/patents.

2024. All rights reserved.
www.bannerengineering.com

Documents / Resources

BANNER TL70 Series Pro Modbus Modular Tower Light [pdf] Instruction Manual
TL70 Series Pro Modbus Modular Tower Light, TL70 Series, Pro Modbus Modular Tower Light, Modular Tower Light, Tower Light, Light

References

Leave a comment