GEYA GRT6-B1

GEYA GRT6-B1 10A Adjustable Delay Off Time Relay User Manual

Model: GRT6-B1

1. Product Overview

The GEYA GRT6-B1 is a compact, electronic adjustable delay off time relay designed for various industrial and domestic applications. It features a single pole double throw (1NO1NC) output and is suitable for DIN rail mounting. The delay time can be conveniently set using the panel knobs, offering a wide range from 0.1 seconds to 10 days.

  • High Performance: Delay settings are easily adjustable via panel knobs for intuitive operation.
  • Function Mode: Supports Delay OFF (Function B) operation.
  • Time Range: Adjustable from 0.1 seconds to 10 days, divided into 10 distinct ranges.
  • Relay Status Indication: Equipped with LED indicators; a green light for power and a red light for working status.
  • Compact Design: Ultra-small size, only 18mm width, designed for 35mm DIN rail mounting.
GEYA GRT6-B1 10A Delay Off Time Relay front view

Figure 1: Front view of the GEYA GRT6-B1 Delay Off Time Relay, showing control knobs and LED indicators.

2. Safety Information

Please read this manual carefully before installation and operation. Failure to follow these instructions may result in equipment damage, personal injury, or death. Always observe local and national electrical codes.

  • Installation and maintenance should only be performed by qualified personnel.
  • Ensure power is disconnected before performing any wiring or maintenance.
  • Verify correct voltage and current ratings before connecting the device.
  • Do not operate the device in environments exceeding its specified operating conditions.
  • Protect the device from moisture, dust, and extreme temperatures.

3. Product Dimensions

The GRT6-B1 relay features a compact design suitable for space-constrained installations. Refer to the diagram below for detailed dimensions.

GEYA GRT6-B1 Delay Off Time Relay product dimensions in millimeters

Figure 2: Detailed dimensions of the GEYA GRT6-B1 relay in millimeters.

4. Installation and Wiring

4.1 Mounting

The GEYA GRT6-B1 is designed for standard 35mm DIN rail mounting. Ensure the rail is securely fastened and provides adequate space for ventilation and wiring.

4.2 Wiring Connections

Connect the power supply and load according to the wiring diagrams provided. The GRT6-B1 model features A1(+) and A2(-) for supply terminals, S for trigger terminal, and 15, 16, 18 for the 1SPDT output contacts (15-16 normally closed, 15-18 normally open).

Diagram showing terminal connections and LED indicators for GEYA GRT6-A1 and GRT6-B1 models

Figure 3: Terminal layout and LED indicators for GRT6-A1 and GRT6-B1 models.

Wiring diagrams for GEYA GRT6-A1/B1 and GRT6-A2/B2 models with single and double pole double throw outputs

Figure 4: Example wiring diagrams for GRT6-A1/B1 (1SPDT) and GRT6-A2/B2 (2SPDT) models.

4.3 Installation Demonstration Video

Watch this video for a visual guide on connecting power and load to the GRT6-B1 relay.

Video 1: This video demonstrates the power connection, load access, time setting, and operation of the GEYA GRT6-B1 delay off time relay with a light bulb.

5. Operating Instructions

5.1 Function Mode (Delay OFF)

The GRT6-B1 operates in Delay OFF mode (Function B). In this mode, when input voltage U is applied, the relay contacts change state immediately and timing begins. When the delay time is complete, the contacts return to their shelf state. If input voltage U is removed before the delay is complete, the contacts return to their shelf state immediately. The trigger switch is not used in this function.

Timing diagrams illustrating Delay ON (A) and Delay OFF (B) functions for the GEYA GRT6 series

Figure 5: Timing diagrams for Delay ON (A) and Delay OFF (B) functions.

5.2 Time Setting

The delay time is set using two rotary knobs on the front panel: one for the time range and one for the percentage of that range.

  1. Adjust Time Range Knob: Select the desired time range (e.g., 10s, 1m, 1h, 1d, 10d).
  2. Adjust Percentage Knob: Fine-tune the delay time within the selected range by setting a percentage (e.g., 50% of 10s = 5 seconds).

For example, to set a delay of 5 minutes:

  • Adjust the time range knob to '10m' (10 minutes).
  • Turn the percentage knob to '50%' (50% of 10 minutes = 5 minutes).
Instructions on how to set time on the GEYA GRT6-B1 relay using time range and percentage knobs

Figure 6: Illustration of time setting using the time range and percentage knobs.

6. Technical Specifications

The following table details the technical specifications for the GEYA GRT6 series relays, including the GRT6-B1 model.

Technical parametersGRT6-A1/B1GRT6-A2/B2GRT6-At/Bt
FunctionA:delay ON; B:delay OFF
Supply terminalsA1-A2
Voltage rangeAC/DC 24-240V (50-60Hz)
BurdenAC 0.7-3VA/DC 0.5-1.7WAC max.6VA/1.9W
Voltage rangeAC 230V (50-60Hz)
Power inputAC max.6VA/1.3WAC max.6VA/1.9W
Supply voltage tolerance-15%; +10%
Supply indicationgreen LED
Time ranges0.1s-10days, ON, OFF
Time settingpotentiometer
Time deviation10%-mechanical setting
Repeat accuracy0.2%-set value stability
Temperature coefficient0.05%/°C, at=20°C (0.05%/°F, at=68°F)
Output1×SPDT2×SPDT1×SPDT(del)+1SPDT(ins)
Current rating10A/AC1
Switching voltage250VAC/24VDC
Min. breaking capacity DC500mW
Output indicationred LED
Mechanical life1×107
Electrical life (AC1)1×105
Reset timemax.200ms
Operating temperature-20°C to +55°C (-4°F to 131°F)
Storage temperature-35°C to +75°C (-22°F to 158°F)
Mounting/DIN railDin rail EN/IEC 60715
Technical parameters table for GEYA GRT6-B1 and GRT6-A1/B1, GRT6-A2/B2 models

Figure 7: Technical specifications for GEYA GRT6 series time relays.

7. Troubleshooting

If the relay does not function as expected, consider the following common issues:

  • No Power Indication (Green LED off): Check the power supply connections and ensure the voltage is within the specified range (AC/DC 24V-240V).
  • Load Not Switching: Verify the load wiring. Ensure the load's voltage and current requirements do not exceed the relay's contact ratings (10A/AC1, 250VAC/24VDC). Check if the red LED indicates working status.
  • Incorrect Delay Time: Re-check the settings on both the time range and percentage knobs. Ensure they are set according to your desired delay.
  • Intermittent Operation: Inspect all wiring for loose connections. Ensure the operating environment is within the specified temperature and humidity limits.

If issues persist, consult a qualified electrician or contact GEYA customer support.

8. Maintenance

The GEYA GRT6-B1 relay is designed for reliable, long-term operation with minimal maintenance. Follow these guidelines:

  • Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
  • Inspection: Periodically inspect wiring connections for tightness and signs of wear or damage.
  • Environment: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent premature aging or malfunction.

9. Warranty and Support

GEYA products are manufactured to high-quality standards and come with a standard warranty against manufacturing defects. For specific warranty terms, technical support, or service inquiries, please refer to the warranty card included with your product or visit the official GEYA website. When contacting support, please have your product model (GRT6-B1) and purchase information available.

Related Documents - GRT6-B1

Preview GEYA GRT6 Series Single-Function Time Relay: Instruction Manual & Technical Specifications
Detailed instruction manual and technical specifications for the GEYA GRT6 Series single-function time relays (GRT6-A, GRT6-B). Covers applications, features, wiring diagrams, and technical parameters.
Preview GEYA GRT8-EC Time Relay - Technical Specifications and Features
Detailed technical specifications, features, and operational guidance for the GEYA GRT8-EC time relay. This relay is designed for industrial automation, controlling lighting, heating elements, motors, and fans, offering adjustable delay times and DIN rail mounting.
Preview GEYA GRT8-M Multifunction Time Relay - Instruction Manual
Comprehensive instruction manual for the GEYA GRT8-M Multifunction Time Relay, detailing its applications, technical specifications, functions, wiring, and installation.
Preview GEYA GRT8-M Multifunction Time Relay Instruction Manual
Instruction manual for the GEYA GRT8-M multifunction time relay, detailing its applications, features, technical specifications, functions, dimensions, and wiring diagrams. Provides guidance on installation and setting.
Preview GEYA GRLE8-01 Earth Leakage Relay: Instruction Manual & Technical Specifications
Comprehensive instruction manual for the GEYA GRLE8-01 Earth Leakage Relay. Details applications, technical parameters, wiring diagrams, panel layout, testing procedures, dimensions, and ZCT accessory options for electrical safety monitoring.
Preview GEYA GRT8-S Asymmetric Cycler Time Relay Instruction Manual
Instruction manual for the GEYA GRT8-S Asymmetric Cycler Time Relay. Covers applications, function features, technical specifications, panel and wiring diagrams, and setting instructions for ventilation, lighting, and pump control.