TOMZN TOVPD3-63VA

TOMZN TOVPD3-63VA Din Rail 3 Phase Voltage Protector Relay User Manual

Model: TOVPD3-63VA

1. Introduction

This manual provides detailed instructions for the installation, operation, and maintenance of the TOMZN TOVPD3-63VA Din Rail 3 Phase Adjustable Over and Under Voltage Protector Relay with Current Protection. This device is designed to safeguard electrical equipment from voltage fluctuations and overcurrent conditions in three-phase systems.

Please read this manual thoroughly before installation and operation to ensure proper use and to prevent damage to the device or connected equipment.

TOMZN TOVPD3-63VA Din Rail 3 Phase Voltage Protector Relay

Figure 1: Front view of the TOMZN TOVPD3-63VA Din Rail 3 Phase Voltage Protector Relay.

2. Safety Information

WARNING: Electrical shock hazard. Installation and maintenance should only be performed by qualified personnel.

  • Always disconnect power before installing or servicing the device.
  • Ensure all wiring connections are secure and comply with local electrical codes.
  • Do not operate the device in wet or damp conditions.
  • Verify the voltage and current ratings of your system match the device specifications.
  • Never attempt to open or repair the device yourself. Refer to qualified service personnel.

3. Key Features

The TOMZN TOVPD3-63VA offers robust protection and monitoring capabilities:

  • Instant Fault Response: Detects and reacts to electrical abnormalities within milliseconds to prevent equipment damage.
  • Multi-Protection System: Comprehensive coverage against overcurrent, under-voltage, phase loss, and short circuits.
  • Industrial-Grade Durability: Heavy-duty construction with flame-retardant materials for demanding environments.
  • Universal Compatibility: Works with AC/DC systems, motors, transformers, and power distribution panels.
  • Clear Visual Indicators: LED status lights and fault alarms for quick system diagnostics.
  • Adjustable over-voltage, under-voltage, and over-current protection thresholds.
  • Asymmetry and phase sequence protection.
  • Adjustable active time and reconnect time.
  • Manual voltage and current calibration capability.

4. Product Variants

The TOVPD3 series is available in several configurations to suit different electrical systems. The primary differences lie in the current rating and the presence of a neutral (N) connection, which affects the voltage display and wiring:

  • 63A With N (3X120V/3X220V/3X230V): Designed for 3-phase systems with a neutral line. Each phase voltage (L1, L2, L3) is displayed relative to the neutral. For example, in a 3*220V+N system, each phase will display 220V.
  • 63A without N (380V): Designed for 3-phase systems without a neutral line. The device displays the line-to-line voltage for each phase (e.g., L1-L2, L2-L3, L3-L1), typically showing 380V across all phases.
  • 100A With N (3X220V): Similar to the 63A With N variant but with a higher current capacity.
  • 100A without N (380V): Similar to the 63A without N variant but with a higher current capacity.

Ensure you select the correct variant for your specific electrical installation.

5. Components and Display

The device features a clear digital display and intuitive control buttons for monitoring and configuration.

Diagram of TOMZN TOVPD3-63VA with labeled components

Figure 2: Labeled components and display of the TOMZN TOVPD3-63VA.

5.1 Display Screens

  • Voltage Display Screen (V): Shows the voltage for each phase (L1, L2, L3).
  • Current Display Screen (A): Shows the current for each phase (L1, L2, L3).

5.2 Control Buttons and Indicators

  • Manual Switch (Power Button): Used to manually turn the output on or off.
  • SET (Menu Key): Enters the setting menu and confirms selections.
  • Adjustment Keys (Up/Down Arrows): Used to navigate menu options and adjust parameter values.
  • Output Indication: LED indicator for output status.
  • Over-voltage Indication (>U): LED indicator illuminates when an over-voltage condition is detected.
  • Under-voltage Indication (<U): LED indicator illuminates when an under-voltage condition is detected.
  • Over-current Indication (>I): LED indicator illuminates when an over-current condition is detected.
  • Asymmetry Indication (Asy): LED indicator illuminates when phase asymmetry is detected.

6. Installation

6.1 Mounting

The TOMZN TOVPD3-63VA is designed for Din Rail mounting. Ensure the Din Rail is securely installed in an appropriate electrical enclosure, away from moisture and excessive heat.

6.2 Wiring

IMPORTANT: Disconnect all power before proceeding with wiring.

  1. Identify the input (IN) and output (OUT) terminals on the device. The terminals are typically labeled L1, L2, L3, and N (if applicable).
  2. Connect the incoming three-phase power supply to the 'IN' terminals (L1, L2, L3). If your model includes a neutral connection, connect the neutral line to the 'N' terminal.
  3. Connect the load (equipment to be protected) to the 'OUT' terminals (L1, L2, L3). If your model includes a neutral connection, connect the load's neutral line to the 'N' output terminal.
  4. Ensure all connections are tight and secure to prevent loose contacts, which can cause overheating or malfunction.
  5. Double-check all wiring against your system's electrical diagram and local codes before restoring power.
Top-down view of TOMZN TOVPD3-63VA showing input and output terminals

Figure 3: Top-down view illustrating the input and output terminals for wiring.

7. Operation

7.1 Initial Power-Up

  1. After completing the wiring, restore power to the circuit.
  2. The device display will illuminate, showing the current voltage and current readings for each phase.
  3. The device will perform a self-check and, if no faults are detected, will connect the output after the configured reconnect time.

7.2 Parameter Settings

To adjust protection parameters:

  1. Press and hold the SET button for a few seconds to enter the setting menu.
  2. Use the Up and Down adjustment keys to navigate through the parameters (e.g., Over-voltage threshold, Under-voltage threshold, Over-current threshold, Active time, Reconnect time, Asymmetry threshold, Phase sequence protection enable/disable).
  3. Press SET again to select a parameter for adjustment.
  4. Use the Up and Down keys to change the value.
  5. Press SET to confirm the new value and move to the next parameter or exit the menu.
  6. If no buttons are pressed for a certain period, the device will automatically exit the setting menu and save changes.

7.3 Manual Calibration

The device supports manual calibration of voltage and current readings for enhanced accuracy. Refer to the device's on-screen menu for specific calibration steps, typically involving comparing readings with a known accurate meter and adjusting the device's internal values.

8. Maintenance

The TOMZN TOVPD3-63VA is designed for minimal maintenance. However, periodic checks are recommended:

  • Visual Inspection: Regularly inspect the device for any signs of physical damage, discoloration, or loose connections.
  • Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use solvents or abrasive cleaners.
  • Functionality Check: Periodically verify the device's protection functions by simulating fault conditions (if safely possible and recommended by a qualified electrician) or by observing its normal operation.

9. Troubleshooting

If you encounter issues with your TOMZN TOVPD3-63VA, refer to the following common problems and solutions:

ProblemPossible CauseSolution
Device does not power on.No input power; incorrect wiring.Check power supply and wiring connections. Ensure input voltage is within specifications.
Output is off, and a protection indicator is lit.Over-voltage, under-voltage, over-current, or phase fault detected.Identify the fault indicated by the LED. Rectify the electrical issue in the system. The device will automatically reconnect after the set reconnect time once the fault clears.
Display shows incorrect voltage/current.Calibration required; sensor issue.Perform manual calibration as described in Section 7.3. If the issue persists, contact support.
Device frequently trips.Protection thresholds set too low/high; unstable power supply.Review and adjust protection parameters (Section 7.2) to match system requirements. Investigate power supply stability.

If the problem persists after attempting these solutions, please contact a qualified electrician or the product manufacturer for assistance.

10. Specifications

FeatureDescription/Value
Model NumberTOVPD3-63VA (Base Model)
Rated Current63A, 100A (depending on variant)
Rated Voltage3*220V+N, 3*380V (depending on variant)
Protection FunctionsOver-voltage, Under-voltage, Over-current, Asymmetry, Phase Sequence
Adjustable ParametersOver-voltage, Under-voltage, Over-current thresholds, Active time, Reconnect time
DisplayDigital Voltage (V) and Current (A) for each phase
Mounting Type35mm Din Rail
CertificationCE
Package DimensionsApproximately 0.39 x 0.39 x 0.39 inches
Item WeightApproximately 3.53 ounces

11. Warranty and Support

This product is manufactured to high-quality standards. For specific warranty information, please refer to the documentation provided at the time of purchase or contact your retailer. In case of technical issues or questions not covered in this manual, please reach out to the product manufacturer or your supplier for support.

Related Documents - TOVPD3-63VA

Preview TOMZN DDS238-VAP Multifunctional Voltage and Current Protector User Manual
User manual for the TOMZN DDS238-VAP multifunctional protective device, detailing its features, specifications, operation, and installation for overvoltage, undervoltage, and overcurrent protection, along with energy metering capabilities.
Preview Tomzn Isolation Type Automatic Transfer Switch Operating Instructions
Operating manual for the Tomzn Isolation Type Automatic Transfer Switch, detailing installation, operation, technical specifications, and wiring for reliable dual power source management.
Preview TOMZN TOQ7e Series Wi-Fi Smart Automatic Transfer Switch Instruction Manual
Comprehensive instruction manual for the TOMZN TOQ7e series Wi-Fi Smart Automatic Transfer Switch, detailing installation, operation, technical specifications, and remote control features for reliable power management.
Preview DTS238-7: 3-Phase Wi-Fi Smart Energy Meter - HIKING TOMZN Technical Specification
Comprehensive technical datasheet for the HIKING TOMZN DTS238-7 DIN rail 3-phase Wi-Fi smart energy meter. Details specifications, features, communication protocols (RS485, Wi-Fi), app control, installation, and warranty information.