Introduction
The BARRINS GLG Signal Isolator is designed to provide isolated power distribution for transmitters, while simultaneously isolating and converting current signals for control systems such as PLCs and DCS. This device ensures signal integrity and system protection through its advanced isolation technology.
It supports common current sources, 2-wire, and 3-wire input terminals. The input, output, and power circuits are mutually isolated using highly efficient magnetoelectric isolation technology. The isolator operates on a DC 24V or AC 85-265V power supply and is designed for standard 35mm DIN rail mounting, offering strong anti-interference capabilities and versatility.
Setup and Installation
Before installation, ensure the power supply is disconnected to prevent electrical hazards.
- Mounting: Mount the GLG Signal Isolator onto a standard 35mm DIN rail. The device is designed for independent mounting.
- Input Wiring: Connect the input signal wires to the designated input terminals. This model supports 2 inputs. Refer to the wiring diagram for specific terminal connections.
- Output Wiring: Connect the output signal wires to the designated output terminals. This model provides 2 outputs. Refer to the wiring diagram for specific terminal connections.
- Power Supply Connection: Connect the power supply (DC 24V or AC 85-265V) to the power terminals. Ensure correct polarity for DC power.
Refer to the following images for visual guidance on installation and wiring:

Figure 1: Wiring diagram for the GLG Signal Isolator, illustrating terminal connections for input, output, and power.

Figure 2: The GLG Signal Isolator securely mounted on a standard 35mm DIN rail.
Operation
Once correctly installed and powered, the GLG Signal Isolator will automatically begin processing signals. It converts and isolates the input signal (0-10mA for this model) into the specified output signal (0-5V for this model) for your control system. No user configuration is typically required for standard operation once the correct model is selected for your application.
Maintenance
To ensure the longevity and reliable performance of your GLG Signal Isolator, follow these maintenance guidelines:
- Regularly inspect the device for any signs of physical damage, such as cracks or loose connections.
- Keep the isolator clean and free from dust, dirt, and moisture. Use a soft, dry cloth for cleaning.
- Ensure the operating environment remains within the specified temperature and humidity ranges to prevent performance degradation.
Troubleshooting
If the GLG Signal Isolator is not functioning as expected, consider the following troubleshooting steps:
- No Power: Verify that the power supply is correctly connected and within the specified voltage range (DC 24V or AC 85-265V). Check power indicator lights if available.
- Incorrect Wiring: Double-check all input and output wiring for correct connections and polarity according to the wiring diagram.
- Signal Mismatch: Confirm that the input signal type and range (0-10mA) match the isolator's specifications and that the output device is compatible with the isolator's output (0-5V).
- Environmental Factors: Ensure the operating temperature and humidity are within the specified limits.
- If issues persist after performing these checks, consult a qualified technician or contact customer support.
Technical Specifications

Figure 3: Product label detailing specifications for the 2 Input 2 Output model.
| Parameter | Value |
|---|---|
| Model | GLG (2 Input 2 Output, 0-10mA Input, DC24V Power Supply, 0-5V Output) |
| Power Supply | DC24V ±10% or AC85-265V |
| Current Consumption | 100mA (2 in 2 out, 24V power supply, output 20mA) |
| Input Signal | 0-10mA |
| Input Burden | Current transformer CT0.2VA |
| Input Impedance | 50Ω |
| Output Signal | 0-5V |
| Output Load Resistance | RL ≥ 500Ω (output current signal); RL ≥ 10KΩ (output voltage signal) |
| Output Ripple | ≤ 0.5%RO |
| Accuracy | DC; ±0.1%F.S. |
| Respond Time | < 10ms |
| Temperature Drift | 0.005%F.S./°C (-20~+55°C) |
| Isolation Intensity | 1500V AC/1min (between input-output-power) |
| Insulation Resistance | ≥ 100MΩ (between input-output-power) |
| Overload Capacity | Withstand double rating (continuous), 10 times rating (10s) |
| Working Temperature & Humidity | -20~+55°C, <80% humidity (non-condensing) |
| Storage Temperature & Humidity | <70% humidity (non-condensing) |
| Dimensions | 110 x 114.5 x 22.5 mm |
| Item Weight | 7.1 ounces |
Warranty and Support
This BARRINS product is covered by a standard manufacturer's warranty. Please refer to the product packaging or contact BARRINS customer service for detailed warranty information regarding terms and conditions.
For technical assistance, troubleshooting support, or any inquiries regarding your GLG Signal Isolator, please contact your supplier or BARRINS customer service through their official channels.