GEYA 2P 40A 30mA

GEYA Auto Recloser with A Type RCCB RCD ELCB Self-Reclosing Device Safety Breaker

Model: 2P 40A 30mA

Introduction

The GEYA Auto Recloser is an advanced safety device designed to automatically restore power after an unexpected trip of a Residual Current Circuit Breaker (RCCB) or Miniature Circuit Breaker (MCB). This device significantly reduces the need for manual intervention, thereby decreasing maintenance costs and improving operational efficiency by promptly addressing electrical faults.

It is suitable for a wide range of applications, including power grid terminal lines, unattended mobile phone base stations, elevators, air conditioners, smart homes, smart factories, and new energy vehicle charging stations.

GEYA Auto Recloser device

Figure 1: GEYA Auto Recloser device.

Product Features

  • Coupled with leakage protection switch for automatic reclosing upon unexpected RCCB trips.
  • Built-in 3 reclosing attempts. If continuous closing failure occurs within 15 minutes, an alarm can be sent via an auxiliary contact.
  • Features a manual/automatic selector switch for flexible operation.
  • Equipped with mechanical/electronic double locking function for enhanced safety.
  • Can be matched with auxiliary contact, alarm contact, shunt release, and under-voltage release.
  • Closing times are reset if no trip occurs or after a manual reset within 15 minutes of successful closing.
GEYA Auto Recloser with indicators

Figure 2: Product overview showing indicators and mode selection switch.

Setup and Installation

The GEYA Auto Recloser is designed for easy integration with existing circuit breaker systems. It can be installed alongside an RCCB or MCB on a DIN rail.

Component Assembly

The auto recloser module (GRD9L-R) is designed to connect directly to an RCCB or MCB. Ensure proper alignment and secure connection between the units.

Assembly of Auto Recloser with accessories

Figure 3: The GRD9L-R module can be installed with auxiliary components and an RCCB/MCB on a DIN rail.

Wiring Example

Follow the wiring diagram carefully to ensure correct and safe installation. Connect the power supply (L and N) to the designated terminals on the recloser and the RCCB/MCB. The load should be connected to the output terminals of the RCCB/MCB.

Wiring diagram for GEYA Auto Recloser

Figure 4: Example wiring diagram for the GEYA Auto Recloser with an RCCB and an indicator light.

Installation Video Guide

For a visual guide on installation and setup, please refer to the official product video below:

Video 1: Installation and operation demonstration of the GEYA Auto Recloser. This video shows how to connect the recloser to a circuit breaker and power supply, and demonstrates its manual and automatic reclosing functions.

Operating Instructions

Mode Selection

The device features a selector switch for choosing between automatic and manual operation modes.

  • AUTO Mode: The auto reclosing function is enabled. The device will automatically attempt to reclose the circuit breaker after a trip.
  • MANU Mode: The auto reclosing function is disabled. The MCB/RCCB can only be opened and closed manually.
Auto and Manual mode descriptions

Figure 5: Detailed description of AUTO and MANU modes.

Automatic Reclosing Logic

The auto recloser is designed to attempt reclosing multiple times with increasing delays to ensure stability and identify persistent faults. The reclosing sequence is as follows:

  • 1st Trip: Automatically closes after 10 seconds.
  • 2nd Trip: Automatically closes after 60 seconds.
  • 3rd Trip: Automatically closes after 300 seconds (5 minutes).

If continuous closing failure occurs within 15 minutes after the 3rd trip, the reclosing module will send an alarm through the auxiliary contact, and the circuit breaker will remain in the OFF/break status. The program clears accumulated closing times if the interval between two closings exceeds 15 minutes, or after a manual reset.

Function description of Auto Mode

Figure 6: Function description and timing diagram for Auto Mode.

Function diagram of reclosing logic

Figure 7: Detailed function diagram illustrating the reclosing logic and timing.

Indicator Lights

  • When powered on, the green indicator will flash for 2 seconds to wait for the power supply to stabilize, then stay on.
  • If the RCCB/MCB fails to trip, the red indicator light will be on.
  • During auto reclosing delay, the red indicator will flash. After the delay, it will switch on automatically and the green light will be on again.

Maintenance

Regular maintenance ensures the optimal performance and longevity of your GEYA Auto Recloser. It is recommended to perform a monthly test to verify its functionality.

Monthly Test

To perform a monthly test, ensure the device is in AUTO mode and press the "Test Monthly" button. This will simulate a leakage signal and trigger the reclosing sequence. Observe if the device trips and recloses according to the automatic reclosing logic.

Locking Function

For safety during maintenance or inspection, the device includes a locking function. When the lock function is activated, the RCCB cannot be closed. This prevents accidental re-energization of the circuit.

Locking function of the Auto Recloser

Figure 8: The locking function prevents the RCCB from closing when activated, ensuring safety during circuit checks.

Troubleshooting

If you encounter issues with your GEYA Auto Recloser, refer to the following table for common faults and their resolutions:

Fault DescriptionResolvent
1. Unable to close or open
  1. Please confirm whether the power supply voltage is normal.
  2. Please confirm whether the working mode is set in AUTO mode.
  3. Please confirm the buckle of the electric operation mechanism and MCB / RCCB.
2. Trip immediately after closing
  1. Please check the circuit to confirm whether there is overload / short circuit / leakage fault at the lower end of MCB / RCCB.
  2. Whether the circuit breaker is damaged or not, and whether it is slipped.
Common faults and resolutions table

Figure 9: Troubleshooting guide for common issues.

Specifications

Detailed technical parameters and dimensions of the GEYA Auto Recloser (GRD9L-R) are provided below:

ParameterValue
Control modeAuto Reclosing
Supply terminalsA1-A2
Power inputDC max.1W(standby) max.20W(action)
Voltage rangeAC 220V (50-60Hz)
Supply voltage tolerance-10%~+10%
Supply indicationred LED
Action time≤1s
Auto reclosing times3
Auto reclosing interval time10s-60s-300s
Reset the closing timesNo trip or manual reset within 15 minutes after successful closing
Mechanical life10000
Electrical life (AC1)4000
Operating temperature-20℃ to +55℃ (-4℉ to 131℉)
Storage temperature-35℃ to +75℃ (-22℉ to 158℉)
Mounting/DIN railDin rail EN/IEC 60715
Protection degreeIP20
Operating positionany
Overvoltage categoryIII.
Pollution degree2
Max.cable size (mm²)solid wire max.1×2.5or 2×1.5; with sleeve max.1×2.5 (AWG 12)
Dimensions of the Auto Recloser

Figure 10: Product dimensions in millimeters.

Technical parameters and panel/wiring diagrams

Figure 11: Comprehensive technical parameters, panel diagram, and wiring diagram for GRD9L-R.

Warranty and Support

For warranty information and technical support, please refer to the official GEYA website or contact your local distributor. Keep your purchase receipt for any warranty claims.