GEYA 2P 40A 30mA
GEYA Auto Recloser with A Type RCCB RCD ELCB Self-Reclosing Device Safety Breaker
Model: 2P 40A 30mA
Introduction
The GEYA Auto Recloser is an advanced safety device designed to automatically restore power after an unexpected trip of a Residual Current Circuit Breaker (RCCB) or Miniature Circuit Breaker (MCB). This device significantly reduces the need for manual intervention, thereby decreasing maintenance costs and improving operational efficiency by promptly addressing electrical faults.
It is suitable for a wide range of applications, including power grid terminal lines, unattended mobile phone base stations, elevators, air conditioners, smart homes, smart factories, and new energy vehicle charging stations.

Figure 1: GEYA Auto Recloser device.
Product Features
- Coupled with leakage protection switch for automatic reclosing upon unexpected RCCB trips.
- Built-in 3 reclosing attempts. If continuous closing failure occurs within 15 minutes, an alarm can be sent via an auxiliary contact.
- Features a manual/automatic selector switch for flexible operation.
- Equipped with mechanical/electronic double locking function for enhanced safety.
- Can be matched with auxiliary contact, alarm contact, shunt release, and under-voltage release.
- Closing times are reset if no trip occurs or after a manual reset within 15 minutes of successful closing.

Figure 2: Product overview showing indicators and mode selection switch.
Setup and Installation
The GEYA Auto Recloser is designed for easy integration with existing circuit breaker systems. It can be installed alongside an RCCB or MCB on a DIN rail.
Component Assembly
The auto recloser module (GRD9L-R) is designed to connect directly to an RCCB or MCB. Ensure proper alignment and secure connection between the units.

Figure 3: The GRD9L-R module can be installed with auxiliary components and an RCCB/MCB on a DIN rail.
Wiring Example
Follow the wiring diagram carefully to ensure correct and safe installation. Connect the power supply (L and N) to the designated terminals on the recloser and the RCCB/MCB. The load should be connected to the output terminals of the RCCB/MCB.

Figure 4: Example wiring diagram for the GEYA Auto Recloser with an RCCB and an indicator light.
Installation Video Guide
For a visual guide on installation and setup, please refer to the official product video below:
Video 1: Installation and operation demonstration of the GEYA Auto Recloser. This video shows how to connect the recloser to a circuit breaker and power supply, and demonstrates its manual and automatic reclosing functions.
Operating Instructions
Mode Selection
The device features a selector switch for choosing between automatic and manual operation modes.
- AUTO Mode: The auto reclosing function is enabled. The device will automatically attempt to reclose the circuit breaker after a trip.
- MANU Mode: The auto reclosing function is disabled. The MCB/RCCB can only be opened and closed manually.

Figure 5: Detailed description of AUTO and MANU modes.
Automatic Reclosing Logic
The auto recloser is designed to attempt reclosing multiple times with increasing delays to ensure stability and identify persistent faults. The reclosing sequence is as follows:
- 1st Trip: Automatically closes after 10 seconds.
- 2nd Trip: Automatically closes after 60 seconds.
- 3rd Trip: Automatically closes after 300 seconds (5 minutes).
If continuous closing failure occurs within 15 minutes after the 3rd trip, the reclosing module will send an alarm through the auxiliary contact, and the circuit breaker will remain in the OFF/break status. The program clears accumulated closing times if the interval between two closings exceeds 15 minutes, or after a manual reset.

Figure 6: Function description and timing diagram for Auto Mode.

Figure 7: Detailed function diagram illustrating the reclosing logic and timing.
Indicator Lights
- When powered on, the green indicator will flash for 2 seconds to wait for the power supply to stabilize, then stay on.
- If the RCCB/MCB fails to trip, the red indicator light will be on.
- During auto reclosing delay, the red indicator will flash. After the delay, it will switch on automatically and the green light will be on again.
Maintenance
Regular maintenance ensures the optimal performance and longevity of your GEYA Auto Recloser. It is recommended to perform a monthly test to verify its functionality.
Monthly Test
To perform a monthly test, ensure the device is in AUTO mode and press the "Test Monthly" button. This will simulate a leakage signal and trigger the reclosing sequence. Observe if the device trips and recloses according to the automatic reclosing logic.
Locking Function
For safety during maintenance or inspection, the device includes a locking function. When the lock function is activated, the RCCB cannot be closed. This prevents accidental re-energization of the circuit.

Figure 8: The locking function prevents the RCCB from closing when activated, ensuring safety during circuit checks.
Troubleshooting
If you encounter issues with your GEYA Auto Recloser, refer to the following table for common faults and their resolutions:
| Fault Description | Resolvent |
|---|---|
| 1. Unable to close or open |
|
| 2. Trip immediately after closing |
|

Figure 9: Troubleshooting guide for common issues.
Specifications
Detailed technical parameters and dimensions of the GEYA Auto Recloser (GRD9L-R) are provided below:
| Parameter | Value |
|---|---|
| Control mode | Auto Reclosing |
| Supply terminals | A1-A2 |
| Power input | DC max.1W(standby) max.20W(action) |
| Voltage range | AC 220V (50-60Hz) |
| Supply voltage tolerance | -10%~+10% |
| Supply indication | red LED |
| Action time | ≤1s |
| Auto reclosing times | 3 |
| Auto reclosing interval time | 10s-60s-300s |
| Reset the closing times | No trip or manual reset within 15 minutes after successful closing |
| Mechanical life | 10000 |
| Electrical life (AC1) | 4000 |
| Operating temperature | -20℃ to +55℃ (-4℉ to 131℉) |
| Storage temperature | -35℃ to +75℃ (-22℉ to 158℉) |
| Mounting/DIN rail | Din rail EN/IEC 60715 |
| Protection degree | IP20 |
| Operating position | any |
| Overvoltage category | III. |
| Pollution degree | 2 |
| Max.cable size (mm²) | solid wire max.1×2.5or 2×1.5; with sleeve max.1×2.5 (AWG 12) |

Figure 10: Product dimensions in millimeters.

Figure 11: Comprehensive technical parameters, panel diagram, and wiring diagram for GRD9L-R.
Warranty and Support
For warranty information and technical support, please refer to the official GEYA website or contact your local distributor. Keep your purchase receipt for any warranty claims.