1. Introduction
This manual provides essential information for the safe and efficient operation of the Zunate NLQ4-125 4P Automatic Dual Power Transfer Switch (ATS). Please read these instructions carefully before installation, operation, or maintenance to ensure proper function and prevent potential hazards. Keep this manual for future reference.
Safety Precautions
- Installation and maintenance should only be performed by qualified electricians.
- Ensure all power sources are disconnected before performing any work on the switch.
- Always follow local electrical codes and regulations.
- Do not operate the switch if it appears damaged.
2. Product Overview
The Zunate NLQ4-125 4P Automatic Dual Power Transfer Switch is designed to automatically switch between two power sources (e.g., utility power and a generator) to ensure continuous power supply. It features reliable transmission, excellent insulation, and a compact structure for various industrial and commercial applications.

Figure 2.1: Front view of the NLQ4-125 4P ATS, showing the manual/auto selector and power indicators.
Key Features
- Automatic and Manual Operation: The switch can be operated automatically or manually, providing flexibility in power management.
- Millisecond Switching: Ensures seamless power transfer without interruption during power failures or recoveries.
- Durable Construction: Made from excellent flame-retardant PC material with high-temperature resistance and anti-aging properties. Utilizes silver contacts for good conductivity.
- Reliable Transmission: Designed for stable and secure power switching.
- Easy Installation and Maintenance: Compact structure facilitates straightforward setup and upkeep.

Figure 2.2: The ATS highlighting its automatic/manual operation and millisecond switching capability.
3. Specifications
| Specification | Value |
|---|---|
| Model | NLQ4 125 4P |
| Material | PC, Silver |
| Rated Frequency | 50Hz / 60Hz |
| Insulation Voltage | AC690V 50Hz |
| Rated Voltage | AC400V 50Hz |
| Grade | PC Grade |
| Poles | 4P |
| Electrical Life | 2000 times |
| Mechanical Life | 5000 times |
| Rated Short-Circuit Current | 50kA |
| Fuse | RT16 00 63A |
| Rated Impulse Withstand Voltage | 8kV |
| Control Circuit Rated Control Voltage (Us) | AC220V (85% Us - 110% Us) |
| Auxiliary Circuit | Two relays, each with two sets of AC220V 50Hz 5A capacity |
| Operation Mode | Automatic, Manual |
| Switch Style | Toggle |
| Connector Type | Screw Terminals |
| Product Dimensions | 142mm x 76mm x 105mm (approx. 5.59in x 2.99in x 4.13in) |

Figure 3.1: Dimensions of the NLQ4-125 4P Automatic Dual Power Transfer Switch.
4. Setup and Installation
Proper installation is crucial for the safe and reliable operation of the ATS. It is highly recommended that installation be performed by a certified electrician.
Installation Steps
- Mounting: Securely mount the ATS in a suitable electrical enclosure, ensuring adequate ventilation and clearance for wiring. The device is designed for panel mounting.
- Wiring Connections: Connect the main power source (Source A) and the backup power source (Source B) to their respective terminals on the ATS. Connect the load to the output terminals. Refer to the wiring diagram provided with the product for precise connections.
- Control Circuit Wiring: Connect the control circuit as per the diagram. The control voltage is AC220V.
- Grounding: Ensure the ATS is properly grounded according to local electrical codes.
- Inspection: After wiring, visually inspect all connections to ensure they are tight and correct.

Figure 4.1: Example of the ATS installed within an electrical system, showing wiring connections.

Figure 4.2: The ATS integrated into a larger electrical control panel, demonstrating typical installation environment.
5. Operating Instructions
The NLQ4-125 4P ATS offers both automatic and manual operation modes.
Mode Selection
- Automatic Mode (Auto): In this mode, the switch automatically detects the status of both power sources. If the normal power (Source A) fails, the switch will automatically transfer the load to the backup power (Source B). When normal power is restored, the switch will automatically transfer the load back to Source A.
- Manual Mode (Manual): In manual mode, the power transfer is controlled by the user. Use the toggle switch on the front panel to select between Source A and Source B. Ensure the switch is in the 'Manual' position before attempting manual operation.

Figure 5.1: Detail of the manual/auto selector switch and power source indicators on the ATS.
Operation Process
When operating in automatic mode:
- The ATS continuously monitors the normal power supply (Source A).
- If Source A becomes abnormal or fails, the ATS will detect this condition.
- Within milliseconds, the ATS will transfer the load from Source A to the backup power supply (Source B).
- Once Source A is restored and stable, the ATS will automatically transfer the load back to Source A.
This process ensures continuity, reliability, and safety of the power supply, achieving an uninterrupted power effect.

Figure 5.2: The ATS is suitable for various applications where continuous power is critical, such as factories, shopping malls, and facilities with solar power integration.
6. Maintenance
Regular maintenance helps ensure the longevity and reliable performance of your ATS.
- Visual Inspection: Periodically inspect the switch for any signs of physical damage, loose connections, or overheating.
- Cleaning: Keep the switch clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
- Terminal Tightness: Check and tighten all terminal connections annually to prevent arcing and ensure good conductivity.
- Functional Test: Periodically test the automatic transfer function by simulating a power failure (if safe to do so and with proper precautions) to ensure it operates correctly.
7. Troubleshooting
If you encounter issues with your ATS, refer to the following common problems and solutions:
| Problem | Possible Cause | Solution |
|---|---|---|
| No power transfer in Auto mode | Control circuit fault, power source not detected, switch in Manual mode | Check control circuit wiring. Verify both power sources are active. Ensure selector is in 'Auto' position. |
| Switch does not return to normal power | Normal power not fully restored or stable | Verify normal power source is stable and within specifications. |
| Overheating or unusual noise | Loose connections, overloaded circuit, internal fault | Immediately disconnect power. Check all connections. Reduce load if overloaded. Contact qualified personnel for inspection. |
| Indicators not lighting up | No power to the ATS, faulty indicator light | Check incoming power supply. If power is present, the indicator may be faulty. |
For issues not listed above or if troubleshooting steps do not resolve the problem, contact a qualified electrician or Zunate customer support.
8. Environmental Conditions
To ensure optimal performance and longevity of the ATS, adhere to the following environmental guidelines:
- Temperature: The maximum ambient temperature should not exceed 40℃ (104°F). The minimum temperature should not be below -5℃ (23°F). The average temperature over a 24-hour period should not exceed 35℃ (95°F).
- Altitude: The installation site altitude should not exceed 2000 meters (6562 feet).
- Humidity: When the maximum temperature is 40℃, the relative humidity of the installation site should not exceed 50%. At lower temperatures, higher relative humidity is permissible (e.g., 90% relative humidity at 25℃). Special measures should be taken to address occasional condensation on the product surface due to temperature changes.
9. Package Contents
Upon opening the package, verify that all items are present and undamaged:
- 1 x Automatic Dual Power Transfer Switch (NLQ4-125 4P)
- 1 x Instruction Manual