JOYELEC SS766N

JOYELEC SS766N Single Phase Electronic Energy Meter Instruction Manual

Model: SS766N

Brand: JOYELEC

1. Introduction

This manual provides essential information for the safe and efficient installation, operation, and maintenance of your JOYELEC SS766N Single Phase Electronic Energy Meter. Please read this manual thoroughly before using the product and retain it for future reference.

The JOYELEC SS766N is designed to accurately measure the total energy consumption (kWh) of a single-phase AC circuit. It features a clear LCD display and is suitable for DIN rail mounting.

2. Product Overview

2.1 Features

  • Total Energy Consumption Display: The LCD screen displays only the total energy consumption (kWh) of the connected circuit. It does not feature a backlight.
  • Memory Function: The meter retains the total energy consumption value even after power interruption. It continues recording from the last saved value once power is restored. The total energy consumption value cannot be reset to zero after initial use.
  • Accurate Measurement: Utilizes large-scale integrated circuits and SMT technology for precise and reliable electrical energy measurement. This helps in monitoring and recording circuit equipment energy consumption for cost calculation and energy saving.
  • Low Power Consumption: The entire unit consumes less than 2W / 5VA. Approximately 1 kWh of power is consumed only after 500 hours of continuous operation, minimizing additional cost.
  • Easy Installation: Designed for standard DIN35mm rail mounting, allowing for installation in distribution boxes. It is secured with clips for stable placement.

2.2 Technical Specifications

ParameterValue
ModelSS766N
BrandJOYELEC
Rated Voltage230V AC
Rated Current10 (60) A
Frequency50/60Hz
Display TypeDigital LCD (kWh only, no backlight)
Pulse Output1600 imp/kWh
InstallationDIN35mm Rail
Max Load Capacity13000W
Dimensions (L x W x H)3.62 x 3.81 x 7.84 cm
Weight120 grams
Operating TemperatureRefer to product packaging for specific range
Manufacturerwenzhoumaozhoudianqikejiyouxiangongsi

3. Safety Instructions

WARNING: Electrical shock hazard. Installation and maintenance should only be performed by qualified personnel.

  • Always disconnect power to the circuit before installing or servicing the energy meter.
  • Ensure all wiring connections are secure and comply with local electrical codes and standards.
  • Do not exceed the maximum rated current (60A) or load capacity (13000W) of the device.
  • Do not open the meter casing. There are no user-serviceable parts inside.
  • Keep the device away from moisture, dust, and extreme temperatures.

4. Setup and Installation

4.1 Mounting

The SS766N energy meter is designed for mounting on a standard 35mm DIN rail. Locate a suitable position within your distribution box or electrical panel.

  1. Ensure the DIN rail is securely installed.
  2. Align the meter's mounting clip with the DIN rail.
  3. Press the meter firmly onto the rail until the clip engages and locks the meter in place.
Side view of JOYELEC SS766N energy meter showing DIN rail mounting clip
Figure 1: Side view illustrating the DIN rail mounting clip.
Dimensions of the JOYELEC SS766N energy meter
Figure 2: Product dimensions for installation planning.

4.2 Wiring Diagram

Follow the wiring diagram carefully. Incorrect wiring can damage the device or pose a safety risk. The meter requires connection to both the live (L) and neutral (N) wires of the power supply and the circuit to be monitored.

  1. Identify the Live (L) and Neutral (N) terminals on the energy meter. These are typically labeled.
  2. Connect the incoming Live (L) wire from the power source (e.g., circuit breaker) to the Live input terminal of the meter.
  3. Connect the incoming Neutral (N) wire from the power source to the Neutral input terminal of the meter.
  4. Connect the Live (L) output terminal of the meter to the Live wire of the electrical equipment/circuit you wish to monitor.
  5. Connect the Neutral (N) output terminal of the meter to the Neutral wire of the electrical equipment/circuit you wish to monitor.
  6. Ensure all connections are tight and secure.
Wiring scheme for JOYELEC SS766N energy meter showing connections to power switch and electrical equipment
Figure 3: Typical wiring diagram for the energy meter.
Alternative wiring diagram for JOYELEC SS766N energy meter
Figure 4: Another perspective on the wiring connections.

5. Operating Instructions

5.1 Powering On

After successful installation and wiring, restore power to the circuit. The meter's LCD display will illuminate and begin showing the total accumulated energy consumption in kWh.

5.2 Reading the Display

The SS766N meter is designed to display only the total energy consumption in kilowatt-hours (kWh). There are no other parameters or modes to cycle through.

Front view of JOYELEC SS766N energy meter displaying total kWh
Figure 5: Front view of the energy meter display.

Important Note on Memory Function: The meter's total energy consumption value cannot be reset to zero after it has started recording. This feature ensures continuous and cumulative tracking of energy usage.

JOYELEC SS766N display showing total energy consumption and non-resettable value
Figure 6: Display details highlighting total energy consumption and non-resettable feature.

6. Maintenance

6.1 Cleaning

To clean the meter, ensure power is disconnected. Use a soft, dry cloth to wipe the exterior. Do not use abrasive cleaners, solvents, or spray liquids directly onto the device.

6.2 Storage

If storing the device, keep it in a cool, dry place, away from direct sunlight and extreme temperatures. Ensure it is protected from physical damage.

7. Troubleshooting

7.1 Common Issues and Solutions

  • No Display:
    • Check if power is supplied to the circuit and the meter.
    • Verify all wiring connections are secure and correct according to the diagram.
    • Ensure the circuit breaker is in the ON position.
  • Incorrect Readings / No Energy Accumulation:
    • Double-check the wiring connections for Live (L) and Neutral (N) inputs and outputs.
    • Ensure the load connected to the meter is within its specified operating range (max 13000W).
    • Confirm the meter is correctly installed on the DIN rail and not loose.
  • Meter is Hot:
    • This may indicate an overload. Immediately disconnect power and check the connected load. Ensure it does not exceed 13000W.
    • If the issue persists after reducing the load, contact a qualified electrician.

If you encounter issues not listed here or if troubleshooting steps do not resolve the problem, please consult a qualified electrician or contact customer support.

8. Warranty and Support

This JOYELEC product is covered by a standard manufacturer's warranty against defects in materials and workmanship. The warranty period typically begins from the date of purchase. Please refer to your purchase documentation or contact your retailer for specific warranty terms and conditions.

For technical support, inquiries, or warranty claims, please contact the vendor or manufacturer through the contact information provided at the point of purchase or on the product packaging.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.