Walfront Walfrontxgm7f6na2w6572

Walfront Voltage Phase Sequence Protector User Manual

Model: Walfrontxgm7f6na2w6572

1. Introduction

This manual provides detailed instructions for the installation, operation, and maintenance of the Walfront Voltage Phase Sequence Protector. This device is designed to monitor 3-phase AC voltage systems and provide protection against overvoltage, undervoltage, voltage unbalance, phase error, phase loss, and zero line disconnection. Please read this manual thoroughly before installation and operation to ensure proper use and safety.

2. Safety Information

Always adhere to local electrical codes and safety regulations during installation and operation. Disconnect power before performing any wiring or maintenance. Only qualified personnel should install and service this device.

3. Product Overview

The Walfront Voltage Phase Sequence Protector (Model: Walfrontxgm7f6na2w6572) is a compact and versatile device designed for industrial electrical systems. It features a standard 35mm DIN rail mounting for easy integration into control cabinets.

Walfront Voltage Phase Sequence Protector front view

Figure 3.1: Front view of the Voltage Phase Sequence Protector, showing the LCD display and control buttons.

Walfront Voltage Phase Sequence Protector with dimensions

Figure 3.2: Dimensions of the Voltage Phase Sequence Protector (approx. 80x43x54mm).

Key Features:

Video 3.1: A demonstration of the Walfront Voltage Phase Sequence Protector, showcasing its physical appearance and handling.

4. Setup and Installation

The Voltage Phase Sequence Protector is designed for 35mm DIN rail installation. Follow the steps below for proper setup.

4.1 Wiring Diagram

Wiring diagram for Walfront Voltage Phase Sequence Protector

Figure 4.1: Standard wiring diagram for the Voltage Phase Sequence Protector. The contact shown is the state of the protector when it is de-energized or faulty.

4.2 Installation Steps

  1. Mounting: Securely attach the protector to a standard 35mm DIN rail in your control cabinet.
  2. Power Connection: Connect the L1, L2, and L3 input circuits to the corresponding terminals on the protector. Ensure correct phase sequence.
  3. Output Connection: Connect the output contacts (1CO and 1NC) to your control circuit as per your application's requirements. Refer to the wiring diagram (Figure 4.1).
  4. Verify Connections: Double-check all wiring for correctness and secure connections before applying power.

5. Operating Instructions

The protector features an LCD display and control buttons for configuration and monitoring.

5.1 Display and Controls

5.2 Parameter Adjustment

To adjust parameters such as overvoltage/undervoltage thresholds, unbalance rate, and action times:

  1. Press and hold the MOD button to enter the settings menu.
  2. Use the '+' and '-' buttons to navigate through the parameters.
  3. Press MOD to select a parameter for editing.
  4. Use '+' and '-' to adjust the value.
  5. Press MOD again to confirm the new value and exit the editing mode for that parameter.
  6. Repeat for other parameters or press and hold MOD to exit the settings menu.

5.3 Reset Methods

6. Maintenance

The Walfront Voltage Phase Sequence Protector requires minimal maintenance. Regular checks ensure optimal performance and longevity.

7. Troubleshooting

This section provides solutions to common issues you might encounter.

ProblemPossible CauseSolution
Device not powering on.No input voltage; incorrect wiring; internal fault.Check input power supply (L1, L2, L3). Verify wiring connections. If problem persists, contact support.
Protector trips frequently.Voltage fluctuations; incorrect parameter settings; actual fault condition.Monitor input voltage stability. Adjust overvoltage/undervoltage/unbalance thresholds if necessary. Investigate and resolve actual electrical faults.
Cannot reset after a trip.Fault condition still present; device set to manual reset and not pressed; internal error.Ensure the fault condition is resolved. Press the RST button. If auto-reset is enabled, check reset delay. If problem persists, contact support.
Display is blank or erratic.Power issue; display damage; internal fault.Check power supply. Gently tap the device to see if display recovers (may indicate loose connection). If problem persists, contact support.

8. Specifications

Detailed technical specifications for the Walfront Voltage Phase Sequence Protector.

ParameterValue
Item TypeVoltage Phase Sequence Protector
MaterialABS
Input CircuitL1, L2, L3 (3-Phase)
Working Voltage RangeAC 208 to 480V
Working Frequency45-65Hz
Output Type1CO and 1NC (Normally Open and Normally Closed)
Overvoltage/Undervoltage Action Time0.1-999s (Adjustable)
Unbalance Rate1-50% (Adjustable)
Unbalanced Hysteresis1-10%
Unbalanced Delay0.1-999s (Adjustable)
Phase Loss Action Time0.1-30s
Phase Error Action Time0.1-30s
Power On Delay0-999s
Reset ModeAuto / Manual
Reset Delay0.1-999s
Display ModeLCD display each action status
Contact Form1 group NO, 1 group NC
Contact Capacity6A 250VAC / 30VDC (resistive)
Dimensions (LxWxH)Approx. 80x43x54mm / 3.1x1.7x2.1in
Installation Method35mm guide rail
Protection ClassIP20
Working Environment-25℃ to 65℃, ≤85%RH
Mechanical Durability1,000,000 times
Dielectric Strength>2kVAC 1min

9. Warranty and Support

Walfront products are manufactured to high-quality standards. This product comes with a standard manufacturer's warranty. Please refer to the warranty card included in your package for specific terms and conditions.

For technical support, troubleshooting assistance, or warranty claims, please contact Walfront customer service through the retailer where you purchased the product or visit the official Walfront store on Amazon:

Visit the Walfront Store on Amazon

Please have your product model number (Walfrontxgm7f6na2w6572) and purchase information ready when contacting support.