1. Introduction
This manual provides detailed instructions for the safe and efficient operation, setup, and maintenance of your Xetron High-end HVAC Set, which includes the SRC-400 Refrigerant Scale and the LMG-10X Digital Manifold. Please read this manual thoroughly before using the equipment to ensure proper function and to prevent damage or injury.
2. Safety Information
Always observe the following safety precautions when operating the Xetron HVAC Set:
- Wear appropriate personal protective equipment (PPE), including safety glasses and gloves, when handling refrigerants.
- Ensure proper ventilation when working with refrigerants.
- Do not exceed the maximum pressure ratings of the manifold or the capacity of the scale.
- Keep the equipment away from moisture and extreme temperatures.
- Only use the equipment for its intended purpose in HVAC/R systems.
- Disconnect power before performing any maintenance or cleaning.
3. Product Overview
The Xetron HVAC Set combines a high-precision refrigerant scale and a versatile digital manifold for comprehensive HVAC system analysis and servicing.
3.1. Xetron SRC-400 Refrigerant Scale
The SRC-400 is designed for accurate refrigerant charging and recovery. It features a robust construction and high-resolution measurements.

Image 3.1.1: The Xetron SRC-400 Refrigerant Scale, highlighting its high-performance chip for accurate and high-resolution measurements.
- Capacity: Up to 220 lbs (100 kg)
- Accuracy: ≤±0.05% of reading
- Resolution: 0.011 lbs
- Overload Detection: Displays 'FULL' and alarms to protect sensors.
- Construction: Strong aluminum with rubber armors for collision resistance.

Image 3.1.2: The SRC-400 scale supports three optional units: Kilograms (KG), Pounds (LB), and Ounces (OZ).
3.2. Xetron LMG-10X Digital Manifold
The LMG-10X Digital Manifold replaces traditional analog gauges, offering advanced features for precise HVAC system diagnostics.

Image 3.2.1: The Xetron LMG-10X Digital Manifold, demonstrating its ability to replace multiple analog gauges with a single digital display.
- Refrigerant Database: Built-in data for up to 88 types of refrigerants.
- Calculations: Automatic supercool and superheat calculations.
- Sight Window: Allows observation of refrigerant filling status.
- Pressure Range: -14.5 to 800 psi
- Temperature Range: -40 to 320 °F (-40 to 160 °C)
- Pressure Accuracy: ±0.5% FS
- Temperature Accuracy: ±0.9 °F
- Pressure Resolution: 0.5 psi
- Temperature Resolution: 0.2 °F
- Units: Pressure: [psi, kg/cm², kPa, Mpa, bar]; Temperature: [°F/°C].
- Compliance: Meets SAE (Society of Automotive Engineers) requirements.

Image 3.2.2: Key components of the LMG-10X Digital Manifold, including control valves, hose bracket, and SAE 1/4 inch refrigerant hose fittings.

Image 3.2.3: The LMG-10X features a built-in database of 88 refrigerants and a sight window to visually check the refrigerant's state.
4. Setup
4.1. Refrigerant Scale (SRC-400) Setup
- Battery Installation: The remote control for the SRC-400 scale is powered by 5 AAA batteries. Open the battery compartment on the remote and insert the batteries, observing correct polarity.
- Placement: Place the scale on a flat, stable surface. The remote can be placed directly into the designated slot on the scale for storage or detached for remote viewing.

Image 4.1.1: The SRC-400 scale with its remote control, illustrating battery power and remote placement.
4.2. Digital Manifold (LMG-10X) Setup
- Hose Connection: Connect the appropriate refrigerant hoses to the SAE 1/4 inch fittings on the manifold. Ensure connections are tight to prevent leaks.
- Power On: Press the power button to turn on the manifold. The display will illuminate, showing initial readings.
5. Operating Instructions
5.1. Using the Refrigerant Scale (SRC-400)
- Power On: Press the 'ON/OFF' button on the remote to power on the scale.
- Unit Selection: Use the 'UNIT' button to cycle through available units (KG, LB, OZ) until your desired unit is displayed.
- Zeroing: Place the empty refrigerant cylinder on the scale. Press the 'ZERO' or 'TARE' button to zero out the weight of the cylinder.
- Charging/Recovery: Connect the refrigerant hose to the cylinder and the system. Monitor the weight change on the display during charging or recovery processes.
5.2. Using the Digital Manifold (LMG-10X)
- Refrigerant Selection: Use the 'MODE' button to navigate through the menu and select the specific refrigerant type (e.g., R114) being used in the system.
- Pressure/Temperature Readings: The main display will show real-time pressure and temperature readings for both high and low sides.
- Superheat/Subcooling Measurement: The manifold automatically calculates and displays superheat (SH) and subcooling (SC) values based on the selected refrigerant and measured temperatures.

Image 5.2.1: The LMG-10X Digital Manifold actively measuring and displaying both superheat and subcooling values.
- Unit Conversion: Use the dedicated buttons to switch between pressure units (psi, kg/cm², kPa, Mpa, bar) and temperature units (°F/°C) as needed.
- Zeroing Pressure: If necessary, use the 'ZERO' button to calibrate the pressure sensors before taking readings.
6. Maintenance
- Cleaning: Wipe the scale platform and manifold display with a soft, damp cloth. Do not use abrasive cleaners or solvents.
- Battery Replacement: Replace batteries in the scale remote when the low battery indicator appears.
- Hose Inspection: Regularly inspect refrigerant hoses for wear, cracks, or damage. Replace damaged hoses immediately.
- Storage: Store the equipment in a clean, dry place away from direct sunlight and extreme temperatures when not in use.
7. Troubleshooting
| Problem | Possible Cause | Solution |
|---|---|---|
| Scale not powering on | Dead batteries in remote | Replace 5 AAA batteries in the remote. |
| Inaccurate scale readings | Scale not level; Overload; External vibrations | Ensure scale is on a flat surface; Do not exceed 220 lbs; Operate in a stable environment. |
| Manifold display blank | No power; Low battery | Check power connection or replace batteries (if applicable). |
| Manifold pressure readings incorrect | Sensors need zeroing; Incorrect refrigerant selected | Perform pressure zeroing; Verify correct refrigerant type is selected. |
| 'FULL' displayed on scale | Scale overloaded | Remove excess weight; Do not exceed 220 lbs capacity. |
8. Specifications
8.1. SRC-400 Refrigerant Scale
- Capacity: 220 lbs (100 kg)
- Accuracy: ≤±0.05% of reading
- Resolution: 0.011 lbs
- Units: KG, LB, OZ
- Power: 5 x AAA Batteries (for remote)
- Material: Aluminum, Rubber
8.2. LMG-10X Digital Manifold
- Refrigerant Database: 88 types
- Pressure Range: -14.5 to 800 psi
- Temperature Range: -40 to 320 °F (-40 to 160 °C)
- Pressure Accuracy: ±0.5% FS
- Temperature Accuracy: ±0.9 °F
- Pressure Resolution: 0.5 psi
- Temperature Resolution: 0.2 °F
- Pressure Units: psi, kg/cm², kPa, Mpa, bar
- Temperature Units: °F, °C
- Fittings: SAE 1/4 inch
9. Warranty and Support
For warranty information, technical support, or service inquiries, please refer to the official Xetron website or contact their customer service department. Keep your purchase receipt as proof of purchase for warranty claims.