GEYA GRT8-B2

GEYA GRT8-B2 Delay Off Single Function Time Relay

Instruction Manual

1. Safety Information

Please read this manual carefully before installation and operation. Failure to follow these instructions may result in equipment damage, injury, or death. Keep this manual for future reference.

  • Electrical Hazard: Installation and maintenance must be performed by qualified personnel only. Disconnect all power before working on the device.
  • Voltage Compatibility: Ensure the supply voltage matches the device's specifications (AC230V for this model).
  • Proper Wiring: Use appropriate wire gauges and ensure all connections are secure to prevent overheating or short circuits.
  • Environment: Do not expose the device to moisture, extreme temperatures, or corrosive environments.

2. Product Overview

The GEYA GRT8-B2 is a single-function electronic time relay designed for delay-off applications. It features two SPDT (Single Pole Double Throw) output contacts and offers a wide range of adjustable time settings. This relay is suitable for DIN rail mounting and provides visual indication of its status via LED indicators.

Key Features:

  • Delay can be set directly via panel knobs for convenience.
  • Function Mode: Delay OFF (Type B).
  • Time scale: 0.1s - 10 days, divided into 10 ranges.
  • Supply voltage: AC230V.
  • Output contact: 2 SPDT (2NO2NC).
  • Relay status indicated by LED.
  • 1-MODULE, DIN rail mounting.
  • Ultra-small size: 18mm width.

Component Identification:

The image below illustrates the main components and terminals of the GRT8-B2 time relay.

GEYA GRT8-B2 Time Relay Component Identification

Figure 2.1: Front view of the GEYA GRT8-B2 time relay, showing the trigger terminal (A1, S, A2), supply terminal (Un), LED indicators (Green for Supply, Red for Output), 10 time range selection knob, time percentage setting knob, and output contacts (15, 16, 18 for 1SPDT; 25, 26, 28 for 2SPDT).

3. Setup and Installation

Mounting:

The GRT8-B2 time relay is designed for DIN rail mounting. Ensure the DIN rail is securely installed in a suitable enclosure, away from excessive heat, moisture, and vibration.

Wiring Diagram:

Refer to the wiring diagrams below for proper connection of the time relay. Always ensure power is disconnected before making any connections.

GEYA GRT8-B2 Wiring Diagram and Dimensions

Figure 3.1: Wiring diagram for GRT8-B2 (2SPDT) showing connections for supply voltage (Un), trigger (S), and output contacts (15-16-18 and 25-26-28). Also includes physical dimensions.

GEYA GRT8-B2 Example Wiring Diagram

Figure 3.2: Example wiring diagram for GRT8-B2 showing connection to a trigger switch and a load (signal light). Terminals 15-18 (NO) close on power-on and disconnect after delay. Terminals 15-16 (NC) disconnect on power-on and close after delay.

Terminal Connections:

  • A1(+), A2(-): Supply voltage input (AC230V).
  • S: Trigger terminal for external control (e.g., push button).
  • 15, 16, 18: First SPDT output contact. 15 is common, 16 is normally closed (NC), 18 is normally open (NO).
  • 25, 26, 28: Second SPDT output contact. 25 is common, 26 is normally closed (NC), 28 is normally open (NO).

4. Operating Instructions

The GRT8-B2 operates in Delay OFF mode (Function B). This means that upon receiving a trigger or power-on, the output contacts will immediately change state, and then revert to their original state after a set delay time.

Time Setting:

The delay time is set using two rotary knobs on the front panel:

GEYA GRT8-B2 Time Setting Knobs and Ranges

Figure 4.1: Time setting knobs. Knob 1 selects the delay gear (s, m, h, d, ON, OFF). Knob 2 provides fine adjustment of the delay time from 10% to 100% within the selected range.

  • Knob 1 (Time Range Selection): Selects the base time unit (seconds, minutes, hours, days) and the maximum value within that unit. Available ranges include: 0.1-1s, 1-10s, 6-60s, 1-10min, 6-60min, 1-10hr, 0.1-1day, 1-10day. There are also 'only ON' and 'only OFF' settings for continuous operation or immediate disconnection.
  • Knob 2 (Time Percentage Setting %): Adjusts the delay time as a percentage (10% to 100%) of the selected time range.

Example: To set a 5-minute delay, select the '10m' range with Knob 1 and set Knob 2 to '50%'.

Function Mode B (Delay OFF):

In Delay OFF mode, when power is applied or the trigger (S terminal) is activated, the load connected to the relay's output contacts (e.g., 15-18) will turn ON immediately. After the set delay time has elapsed, the load will turn OFF. If the trigger is held during the delay, the load remains ON until the trigger is released, then the delay starts.

GEYA Delay ON and Delay OFF Function Explanation

Figure 4.2: Illustration of Delay ON (A) and Delay OFF (B) functions. For Delay OFF (B), after power-up, the light turns on and the relay begins to delay. After the set time (e.g., 10 seconds), the light will turn off.

Operational Demonstration:

Watch the video below for a practical demonstration of how to use a GEYA GRT8-B1 (similar to GRT8-B2) off-delay time relay.

Video 4.1: A demonstration of the GEYA GRT8-B1 off-delay time relay. The video shows setting the delay, applying power, and observing the load's behavior (light turning on immediately and then off after the delay). It also demonstrates the effect of holding down a reset button during the timing delay.

5. Maintenance

The GEYA GRT8-B2 time relay is designed for reliable operation with minimal maintenance. However, regular checks can help ensure its longevity and proper function.

  • Visual Inspection: Periodically inspect the relay for any signs of physical damage, discoloration, or loose connections.
  • Terminal Tightness: Ensure all screw terminals remain tight to prevent intermittent connections or overheating.
  • Cleaning: If necessary, gently clean the exterior of the device with a dry, soft cloth. Do not use abrasive cleaners or solvents.
  • Environmental Conditions: Verify that the operating environment remains within the specified temperature and humidity ranges.

6. Troubleshooting

If the GEYA GRT8-B2 time relay is not functioning as expected, consider the following common issues and solutions:

ProblemPossible CauseSolution
Relay does not activate (LEDs off)No power supply; Incorrect wiring; Faulty unit.Check supply voltage at A1/A2 terminals; Verify wiring according to diagram; Replace unit if faulty.
Load does not switch after delayIncorrect time setting; Faulty load; Incorrect output wiring.Adjust time range and percentage knobs; Test the load independently; Verify output contact wiring (NO/NC).
Delay time is inaccurateIncorrect time range/percentage setting.Carefully re-adjust both time setting knobs.
Relay continuously ON/OFFKnob 1 set to 'only ON' or 'only OFF'.Adjust Knob 1 to a specific time range.

7. Technical Specifications

Below are the detailed technical specifications for the GEYA GRT8-B2 Delay Off Single Function Time Relay (AC230V model).

GEYA GRT8-B2 Technical Specifications Table

Figure 7.1: Detailed technical parameter table for GRT8-A1/B1 and GRT8-A2/B2 models, highlighting the AC230V specifications.

ParameterValue
FunctionB: Delay OFF
Supply TerminalsA1-A2
Voltage RangeAC230V (50-60Hz)
Power InputAC max. 6VA / 1.9W
Supply Voltage Tolerance-15%; +10%
Supply IndicationGreen LED
Time Ranges0.1s - 10 days, ON, OFF
Time SettingPotentiometer
Time Deviation10% - mechanical setting
Repeat Accuracy0.2% - set value stability
Temperature Coefficient0.05%/°C, at=20°C (0.05%/°F, at=68°F)
Output2xSPDT
Current Rating2x16A (AC1)
Switching Voltage250VAC / 24VDC
Min. Breaking Capacity DC500mW
Output IndicationRed LED
Mechanical Life1x107
Electrical Life (AC1)1x105
Reset Timemax. 200ms
Operating Temperature-20°C to +55°C (-4°F to 131°F)
Storage Temperature-35°C to +75°C (-22°F to 158°F)
MountingDIN rail EN/IEC 60715
Protection DegreeIP40 for front panel / IP20 terminals
Operating PositionAny
Overvoltage CategoryIII
Pollution Degree2
Max. Cable Size (mm²)Solid wire max. 1x2.5 or 2x1.5 / with sleeve max. 1x2.5 (AWG 12)
Dimensions90x18x64mm
StandardsEN 61812-1, IEC6947-5-1

8. Warranty and Support

Warranty Information:

GEYA products are manufactured to high-quality standards and are covered by a limited warranty against defects in materials and workmanship. Please refer to the warranty card included with your product or visit the official GEYA website for detailed warranty terms and conditions.

Customer Support:

For technical assistance, troubleshooting, or product inquiries, please contact GEYA customer support through the following channels:

  • Online: Visit the official GEYA website for FAQs, product documentation, and contact forms.
  • Email: Refer to your product packaging or the GEYA website for the appropriate support email address.
  • Phone: Contact numbers for regional support may be available on the GEYA website.

When contacting support, please have your product model number (GRT8-B2) and purchase information ready.

© 2024 GEYA. All rights reserved.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.