Annadue XY504

Annadue XY504 PID Temperature Controller User Manual

Model: XY504

1. Introduction

The Annadue XY504 is an intelligent PID temperature controller designed for precise temperature management in a variety of applications. It features a dual digital display for simultaneous viewing of set temperature (SV) and process value (PV), universal input compatibility, and a self-tuning function for optimal performance. This manual provides essential information for the safe and effective installation, operation, and maintenance of your XY504 temperature controller.

2. Product Overview

The XY504 PID Temperature Controller is a versatile device capable of controlling heating and cooling processes. Its robust design and advanced features make it suitable for industrial and laboratory environments.

Key Features:

  • Dual digital display for process value (PV) and set value (SV).
  • Universal input support for 10 different types of thermocouples and RTD sensors.
  • PID control method with ON/OFF option.
  • Self-tuning function to automatically determine optimal PID parameters.
  • Equipped with ALM1 alarm output.
  • Compact design for easy integration.
Annadue XY504 PID Temperature Controller with an oven in the background

Figure 2.1: Annadue XY504 PID Temperature Controller in an application setting, demonstrating its use for oven temperature control.

Front view of the Annadue XY504 PID Temperature Controller showing dual digital display and control buttons

Figure 2.2: Front panel of the XY504 controller, highlighting the PV (red) and SV (green) displays, status indicators (AT, OUT1, OUT2, ALM1, ALM2), and control buttons (SET, R/S, Up, Down).

3. Specifications

Parameter Value
Model XY504
Type Intelligent PID Temperature Controller
Material ABS (Acrylonitrile Butadiene Styrene)
Power Supply 100-240VAC, 50/60Hz
Max Input Range 0-1300 ℃ (Adjustable)
Display Type Dual Line, Four Digit Digital Display (Celsius)
Control Method PID, ON/OFF
Alarm Output ALM1
Dimensions (W x H x D) Approx. 48 x 96 x 78 mm (1.9 x 3.8 x 3.1 inches)
Product Weight 165 Grams
Dimensions of the Annadue XY504 PID Temperature Controller

Figure 3.1: Physical dimensions of the XY504 controller, showing width (48mm), height (96mm), and depth (78mm).

4. Safety Information

Please read and understand all safety instructions before installing or operating the Annadue XY504 PID Temperature Controller. Failure to follow these instructions may result in electric shock, fire, or damage to the device.

  • Ensure the power supply voltage matches the controller's specifications (100-240VAC).
  • Disconnect power before making any wiring connections or performing maintenance.
  • Installation and wiring should be performed by qualified personnel.
  • Do not operate the controller in environments with excessive moisture, dust, or corrosive gases.
  • Ensure proper grounding to prevent electrical hazards.
  • Do not disassemble or modify the controller.

5. Setup and Installation

The XY504 controller is designed for panel mounting. Follow these steps for proper installation and wiring.

5.1 Panel Mounting

  1. Cut a panel cutout of approximately 45 x 92 mm (1.77 x 3.62 inches).
  2. Insert the controller into the cutout from the front.
  3. Secure the controller using the provided mounting frames from the rear of the panel.
Annadue XY504 PID Temperature Controller with mounting frames

Figure 5.1: The XY504 controller shown with its two mounting frames, which are used to secure the unit into a panel cutout.

5.2 Wiring Connections

Refer to the wiring diagram on the side of the controller and the figures below for correct electrical connections. Ensure all connections are secure and insulated.

Side view of Annadue XY504 PID Temperature Controller with detailed wiring diagram

Figure 5.2: Side view of the XY504 controller, displaying the comprehensive wiring diagram for power, input, and output connections. This diagram details terminal assignments for AC power (100-240V), SSR output, relay output, alarm, and sensor input (TC/RTD).

Rear view of Annadue XY504 PID Temperature Controller showing terminal block

Figure 5.3: Rear view of the XY504 controller, showing the screw terminal block where all electrical connections are made. The terminals are numbered for easy identification according to the wiring diagram.

Bottom view of Annadue XY504 PID Temperature Controller showing terminal block

Figure 5.4: Bottom view of the XY504 controller, providing another perspective of the terminal block for wiring, ensuring all connections are visible and accessible.

Wiring Key:

  • Power Supply (AC 100-240V): Connect to terminals 1 and 2.
  • SSR Output: Connect to terminals 3 and 4.
  • Relay Output: Connect to terminals 5, 6, and 7 (Common, Normally Open, Normally Closed).
  • Alarm Output (ALM1): Connect to terminals 8 and 9.
  • Sensor Input (TC/RTD): Connect to terminals 10, 11, 12 (specific connections depend on sensor type, refer to diagram).

6. Operating Instructions

This section outlines the basic operation and configuration of the Annadue XY504 PID Temperature Controller.

6.1 Power On and Display

Upon powering on, the controller will display the Process Value (PV) in the upper red display and the Set Value (SV) in the lower green display. Status indicators (AT, OUT1, OUT2, ALM1, ALM2) will illuminate according to the current operating state.

6.2 Setting the Temperature (SV)

  1. Press the SET button once. The SV display will begin to flash.
  2. Use the Up () and Down () arrow buttons to adjust the desired set temperature.
  3. Press the SET button again to confirm the new SV and exit the setting mode.

6.3 PID Self-Tuning (AT Function)

The self-tuning function automatically calculates optimal PID parameters for your specific application, improving temperature stability and control accuracy.

  1. Ensure the controller is connected to the heating/cooling element and sensor.
  2. Set the desired temperature (SV).
  3. Press and hold the SET button for approximately 3-5 seconds until the "AT" indicator starts flashing. This indicates that self-tuning has begun.
  4. The controller will cycle the output to analyze the system's thermal characteristics. This process may take some time, depending on the system's inertia.
  5. Once self-tuning is complete, the "AT" indicator will stop flashing, and the controller will operate with the newly calculated PID parameters.

Note: During self-tuning, the temperature may overshoot or undershoot the set value. This is normal behavior as the controller learns the system's response.

6.4 Advanced Parameter Settings

For advanced configurations such as input type selection, alarm settings, or manual PID parameter adjustment, refer to the detailed parameter menu. Accessing this menu typically involves pressing and holding the SET button for an extended period (e.g., 5-10 seconds) or a specific key combination. Consult the full instruction manual provided with the product for a complete list of parameters and their functions.

7. Maintenance

Regular maintenance helps ensure the longevity and accurate operation of your XY504 PID Temperature Controller.

  • Cleaning: Periodically wipe the front panel with a soft, dry cloth. Do not use abrasive cleaners or solvents.
  • Inspection: Regularly check wiring connections for looseness or signs of damage. Ensure the sensor is clean and properly installed.
  • Environment: Maintain a clean, dry, and well-ventilated environment for the controller.

8. Troubleshooting

If you encounter issues with your XY504 controller, refer to the following common problems and solutions.

Problem Possible Cause Solution
No display/Power off No power supply; Incorrect wiring Check power connections and voltage. Verify wiring according to diagram.
PV display shows "HHHH" or "LLLL" Sensor open circuit; Sensor short circuit; Incorrect sensor type setting Check sensor wiring. Replace faulty sensor. Verify input type setting in parameters.
Temperature not stable/Overshooting PID parameters not optimized; ON/OFF control selected Perform PID self-tuning (AT function). Ensure PID control mode is selected.
Output not activating Wiring error; Output type mismatch; Temperature not reaching set point Check output wiring. Verify output type setting. Ensure SV is set correctly and PV is within control range.
Alarm not triggering Alarm settings incorrect; Alarm output wiring error Check alarm parameters (e.g., alarm type, deviation). Verify alarm output wiring.

If the problem persists after attempting these solutions, please contact customer support.

9. Warranty and Support

For warranty information and technical support, please refer to the documentation provided with your purchase or contact the vendor directly. Keep your proof of purchase for warranty claims.

Manufacturer: Annadue

© 2023 Annadue. All rights reserved. This manual is subject to change without notice.