1. Introduction
This manual provides essential information for the proper installation, operation, and maintenance of the Caleffi 553642A AutoFill Automatic Boiler Filling Valve. Please read these instructions thoroughly before proceeding with installation or use to ensure safe and efficient operation of your hydronic heating system.
2. Safety Information
WARNING: Improper installation or maintenance can lead to property damage, serious injury, or death. All work on hydronic heating systems should be performed by qualified personnel.
- Always depressurize and drain the system before attempting any installation or maintenance.
- Turn off all power to the boiler and associated components before beginning work.
- Wear appropriate personal protective equipment (PPE), including safety glasses and gloves.
- Ensure all connections are properly sealed to prevent leaks.
- Do not exceed the maximum operating pressure or temperature specified for the valve.
3. Product Overview
The Caleffi 553642A AutoFill Automatic Boiler Filling Valve is designed to automatically maintain the correct pressure in closed hydronic heating systems. It features a pre-adjustable design with a visual system pressure setting indicator for easy setup. The valve is constructed from durable brass and includes a manual shut-off valve, an integrated strainer, and a check valve for enhanced system protection and ease of service.

Figure 1: Caleffi 553642A AutoFill Automatic Boiler Filling Valve. This image shows the brass valve body with a gray top housing and an attached pressure gauge, indicating its primary function in monitoring system pressure.

Figure 2: Dimensional drawing of the Caleffi 553642A valve. This diagram provides key measurements and connection sizes (1/2" NPT) for proper installation planning.
Video 1: "Made in Caleffi". This video provides a general overview of Caleffi's manufacturing processes and commitment to quality, offering insight into the brand's production standards.
4. Setup and Installation
Installation should only be performed by a qualified heating technician in accordance with local codes and regulations.
4.1 Pre-Installation Checks
- Verify that the valve specifications match your system requirements.
- Ensure all necessary tools and additional plumbing components are available.
- Inspect the valve for any signs of damage before installation.
4.2 Installation Steps
- System Isolation: Shut off the main water supply to the boiler and turn off the boiler's power supply.
- System Drainage: Drain the boiler and associated piping to a safe level, ensuring no hot water remains.
- Valve Placement: Install the Caleffi 553642A valve on the cold water supply line to the boiler, typically before the expansion tank connection. Ensure the flow arrow on the valve body points towards the boiler.
- Connections: Use appropriate pipe thread sealant (e.g., PTFE tape or pipe dope) on all threaded connections. Tighten connections securely but do not overtighten. The valve features 1/2" NPT inlet and outlet connections.
- Water Supply Restoration: Slowly open the main water supply valve to the boiler.
- System Filling: Allow the system to fill. The AutoFill valve will automatically open to fill the system to its preset pressure.
- Leak Check: Carefully inspect all connections for leaks. Tighten as necessary.
5. Operating Instructions
5.1 Initial Pressure Setting
The Caleffi 553642A valve is factory preset to 15 psi. This is a common pressure for many residential hydronic systems. The visual system pressure setting indicator allows for easy verification.
5.2 Adjusting Outlet Pressure
If a different system pressure is required (within the 3-60 psi range):
- Depressurize: Briefly open a drain valve on the boiler to slightly reduce system pressure below the desired setting.
- Adjust: Rotate the adjustment knob on the top of the valve. Turning clockwise increases the set pressure, and counter-clockwise decreases it. Observe the pressure gauge while adjusting.
- Verify: Once the desired pressure is set, the valve will automatically maintain it. Monitor the system pressure gauge to confirm stability.
5.3 Manual Shut-off
The integrated manual shut-off valve allows for isolation of the filling valve from the water supply without affecting the main system. This is useful for maintenance or replacement of the filling valve itself.
6. Maintenance
Regular maintenance ensures the longevity and proper function of your Caleffi AutoFill valve.
- Strainer Cleaning: The integrated strainer should be periodically inspected and cleaned to prevent debris from affecting valve operation. To clean, isolate the valve using the manual shut-off, depressurize the section, remove the strainer cap, clean the mesh, and reassemble.
- Visual Inspection: Annually inspect the valve for any signs of leaks, corrosion, or damage.
- Pressure Verification: Periodically check the system pressure on the gauge to ensure it is being maintained correctly.
7. Troubleshooting
This section addresses common issues you might encounter with your Caleffi AutoFill valve.
7.1 Low System Pressure / Boiler Not Filling
- Check Water Supply: Ensure the main water supply to the valve is open.
- Check Manual Shut-off: Verify the manual shut-off valve on the AutoFill unit is fully open.
- Clogged Strainer: A dirty strainer can restrict flow. Refer to Section 6 for cleaning instructions.
- Valve Malfunction: If the above steps do not resolve the issue, the valve may be faulty and require replacement.
7.2 High System Pressure / Overfilling
- Expansion Tank: A faulty or undersized expansion tank is a common cause of high system pressure. Consult a technician to check the expansion tank.
- Valve Seat Contamination: Debris in the valve seat can prevent it from closing completely. Cleaning the strainer (Section 6) may help, but internal cleaning or replacement might be necessary.
- Valve Malfunction: The valve may be failing to regulate pressure correctly and require replacement.
7.3 Leaks
- Connection Points: Check all threaded connections for proper sealing. Tighten or re-apply thread sealant if necessary.
- Valve Body: If the leak is from the valve body itself, the valve may be damaged and require replacement.
8. Specifications
- Model Number: 553642A
- Brand: Caleffi
- Material: Brass
- Max Inlet Pressure: 230 psi
- Max Working Temperature: 150°F (65°C)
- Setting Pressure Range: 3 - 60 psi
- Preset Outlet Pressure: 15 psi
- Inlet Connection Type: National Pipe Tapered (NPT)
- Outlet Connection Type: NPT
- Number of Ports: 2
- Product Dimensions: 7 x 15 x 5 inches
- Item Weight: 1.8 Pounds
- Specification Met: ASME, ASTM, ANSI
9. Warranty and Support
For warranty information, technical support, or replacement parts, please contact Caleffi directly or the authorized seller from whom you purchased the product. Keep your proof of purchase for warranty claims.
Caleffi Contact Information: Please refer to the official Caleffi website or product packaging for the most current contact details.