Burndy KSA2

BURNDY KSA2 Split Bolt Connector User Manual

Model: KSA2

1. Introduction

The BURNDY KSA2 Split Bolt Connector is designed for making reliable electrical connections between two conductors. This connector is suitable for a range of aluminum conductors from 8 AWG to 2 AWG. Constructed from high-strength aluminum and tin-plated for enhanced conductivity and corrosion resistance, the KSA2 ensures a secure and durable connection. This manual provides essential information for the safe and correct installation and maintenance of your BURNDY KSA2 Split Bolt Connector.

BURNDY KSA2 Split Bolt Connector

Image 1.1: The BURNDY KSA2 Split Bolt Connector. This image displays the connector's main body, the split bolt, and the hexagonal nut used for tightening, highlighting its robust construction.

2. Important Safety Information

Always observe the following safety precautions to prevent personal injury or damage to equipment:

  • Qualified Personnel Only: Installation and maintenance should only be performed by qualified and trained electrical personnel.
  • De-energize Circuits: Ensure all circuits are de-energized and locked out before beginning any work on electrical connections. Verify with a voltage tester.
  • Personal Protective Equipment (PPE): Always wear appropriate PPE, including safety glasses, gloves, and arc-rated clothing.
  • Proper Tools: Use only insulated and appropriate tools for electrical work.
  • Manufacturer's Instructions: Follow all manufacturer's instructions and local electrical codes.
  • Material Compatibility: Ensure the connector is compatible with the conductor material (aluminum in this case) and size.

3. Product Components

The BURNDY KSA2 Split Bolt Connector consists of the following primary components:

  • Connector Body: The main aluminum, tin-plated housing that encloses the conductors.
  • Split Bolt: The threaded bolt that passes through the connector body, designed to apply pressure to the conductors.
  • Hexagonal Nut: Used to tighten the split bolt, securing the conductors within the connector body.
BURNDY KSA2 Split Bolt Connector detailed view

Image 3.1: A detailed view of the BURNDY KSA2 Split Bolt Connector. This image provides a closer look at the threads of the bolt and the interior design of the connector, illustrating how it grips the conductors.

4. Technical Specifications

SpecificationValue
ModelKSA2
Conductor Range8 AWG to 2 AWG (Aluminum)
MaterialAluminum, Tin Plated
Length1.24 inches (31.5 mm)
Width0.69 inches (17.5 mm)
Recommended Torque275 in-lb (31.07 Nm)
ManufacturerHubbell (Burndy Brand)

5. Setup and Preparation

Before installing the BURNDY KSA2 Split Bolt Connector, ensure the following preparatory steps are completed:

  1. De-energize Circuit: Confirm that the electrical circuit is completely de-energized and secured against accidental re-energization.
  2. Gather Tools: Collect all necessary tools, including a torque wrench, wire strippers, and a wire brush.
  3. Inspect Conductors: Examine the conductors for any damage, nicks, or corrosion. Damaged sections should be removed.
  4. Strip Insulation: Carefully strip the insulation from the ends of the conductors to the appropriate length, ensuring enough bare conductor is exposed to fully seat within the connector. Avoid nicking the conductor strands.
  5. Clean Conductors: For aluminum conductors, thoroughly clean the stripped ends with a wire brush to remove any oxidation. Apply an oxide inhibitor compound (not supplied) to the cleaned conductor surfaces immediately to prevent re-oxidation.

6. Installation Instructions

Follow these steps to properly install the BURNDY KSA2 Split Bolt Connector:

  1. Separate Connector: Loosen the hexagonal nut on the split bolt connector sufficiently to allow the conductors to be inserted into the grooves.
  2. Insert Conductors: Insert the prepared (stripped, cleaned, and inhibited) conductors into the opposing grooves of the split bolt connector. Ensure each conductor is fully seated and makes good contact with the connector body.
  3. Initial Tightening: Hand-tighten the hexagonal nut until it is snug and the conductors are held in place.
  4. Torque Application: Using a torque wrench, tighten the hexagonal nut to the recommended torque value of 275 in-lb (31.07 Nm). Apply torque gradually and evenly. Over-tightening can damage the connector or conductors, while under-tightening can lead to a poor connection and overheating.
  5. Inspect Connection: After tightening, visually inspect the connection to ensure the conductors are securely held and there are no exposed bare wires beyond the connector body.
  6. Insulate Connection: Once the connection is complete and verified, properly insulate the entire connector and exposed conductor areas using appropriate electrical tape or heat-shrink tubing, as required by local codes and application.

7. Maintenance

The BURNDY KSA2 Split Bolt Connector is designed for long-term reliability with minimal maintenance. However, periodic inspection is recommended:

  • Visual Inspection: Periodically inspect the connection for any signs of overheating (discoloration), corrosion, or physical damage.
  • Tightness Check: If accessible and safe to do so (with power off), verify the tightness of the connection. Do not re-torque unless there is evidence of loosening or a specific maintenance procedure requires it.
  • Cleaning: If necessary, gently clean the exterior of the insulated connection with a dry, non-abrasive cloth.

8. Troubleshooting

Most issues with split bolt connectors arise from improper installation. Refer to the following for common problems:

ProblemPossible CauseSolution
Connection OverheatingInsufficient torque, improper conductor cleaning, incorrect conductor size.De-energize circuit. Disassemble, clean conductors, apply oxide inhibitor, re-install with correct torque. Verify conductor size.
Loose ConnectionInsufficient torque during installation, vibration.De-energize circuit. Re-tighten to specified torque. Consider vibration dampening if applicable.
Corrosion at ConnectionImproper cleaning of conductors, lack of oxide inhibitor, environmental exposure.De-energize circuit. Disassemble, thoroughly clean conductors, apply oxide inhibitor, re-install. Ensure proper insulation.

9. Warranty Information

For specific warranty details regarding the BURNDY KSA2 Split Bolt Connector, please refer to the official warranty statement provided by Burndy or Hubbell. Warranty terms typically cover defects in materials and workmanship under normal use and service. Keep your purchase receipt as proof of purchase.

10. Customer Support

If you require technical assistance, have questions about installation, or need to report a product issue, please contact Burndy customer support. Contact information can typically be found on the official Burndy or Hubbell website, or through your authorized distributor.

Related Documents - KSA2

Preview Burndy Type YGL-C Hygrid Cross Connector: Specifications, Ordering, and Installation Tools
Detailed technical specifications, dimensions, and ordering information for the Burndy Type YGL-C Hygrid Compression Ground Grid Cross Connector. Includes compatibility with various HYPRESS™ tools and dies, application details for conductors, ground rods, and rebar, and UL/CSA certifications.
Preview BURNDY Technical Reference: Electrical Connection Principles, Hardware, and Cable Data
This BURNDY technical reference provides comprehensive data on electrical connection principles, including creep, surface oxide, and corrosion. It details hardware specifications with recommended tightening torques for steel and aluminum bolts, and UL 486A/UL 486B compliant screws. Extensive cable data tables for copper, aluminum, and ACSR conductors are also included, making it an essential guide for electrical professionals.
Preview BURNDY Master Catalog: Electrical Connectors, Terminals, and Distribution Solutions
The BURNDY Master Catalog provides a comprehensive overview of electrical connection and distribution products, including terminals, lugs, splices, and power distribution blocks. Discover high-quality solutions for industrial, utility, and commercial applications, featuring detailed specifications and product information from BURNDY.
Preview Burndy Ferrule Dimensions and Recommended Tooling Guide
Detailed technical specifications for Burndy ferrules, including catalog numbers, AWG sizes, and precise dimensions (LI, D, DI, D2 MAX) in both inches and millimeters. Also lists compatible recommended tooling for each ferrule type.
Preview BURNDY Tools Full Line Catalog: Electrical Installation & Crimping Solutions
Explore the comprehensive BURNDY Tools Full Line Catalog, featuring advanced battery-powered, hydraulic, and manual tools for electrical installations. Discover innovative T3 Technology, crimpers, cutters, pumps, and accessories designed for reliability and efficiency.
Preview BURNDY Y750BH HYPRESSTM Hydraulic Crimping Tool Manual
Official manual for the BURNDY Y750BH HYPRESSTM hydraulic crimping tool, covering safety, operation, maintenance, specifications, and troubleshooting. The tool is a robust, C-shaped hydraulic crimper designed for remote power operation, used for tapping/splicing overhead lines and compression grounding systems. Learn how to safely and effectively use this professional-grade tool.