Raypak R5350/R6350/R8350

Raypak Ignition Control Module User Manual

Models: R5350, R6350, R8350 Heat Pump

1. Introduction

This manual provides essential information for the proper installation, operation, and maintenance of your Raypak Ignition Control Module for R5350, R6350, and R8350 series heat pumps. Please read this manual thoroughly before attempting any installation or service to ensure safe and efficient operation.

2. Safety Information

WARNING: HIGH VOLTAGE. DISCONNECT WIRING BEFORE SERVICING.

Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury, or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment. This control module should only be installed and serviced by a qualified service technician.

  • Always disconnect power to the heat pump unit before performing any work on the ignition control module.
  • Ensure all wiring connections are secure and comply with local electrical codes.
  • Do not operate the heat pump if any part of the ignition system is damaged or malfunctioning.
  • This module must be replaced with an identical part, Raypak Kit # 007374F, to ensure safe operation.

3. Product Overview

The Raypak Ignition Control Module is an automatic ignition control designed for use with Raypak R5350, R6350, and R8350 heat pump models. It manages the ignition sequence and monitors flame presence to ensure safe and reliable operation of the heat pump's heating system.

Raypak Ignition Control Module, front view

Figure 1: Front view of the Raypak Ignition Control Module.

The module features diagnostic status codes and specific timing sequences for pre-purge, inter-purge, post-purge, and heat-up phases. It also includes connections for igniter, flame sensor, valve, and fan.

Raypak Ignition Control Module with FENWAL label showing specifications and diagnostic codes

Figure 2: Detailed view of the control module's FENWAL label, displaying technical specifications and diagnostic codes.

The module's rear side provides mounting points for secure installation within the heat pump unit.

Raypak Ignition Control Module, back view

Figure 3: Back view of the Raypak Ignition Control Module, showing mounting points.

Included with the module are various wiring components, connectors, and fasteners necessary for installation.

Included accessories for Raypak Ignition Control Module, including wires, connectors, screws, and zip ties

Figure 4: Included accessories: wiring harness, wire nuts, screws, and zip ties.

4. Setup and Installation

Installation of the ignition control module requires electrical knowledge and should be performed by a qualified technician. Refer to the heat pump's service manual for specific wiring diagrams and mounting instructions.

4.1. Pre-Installation Steps

  • Ensure the heat pump unit is completely powered off at the main breaker.
  • Verify that the replacement module is the correct part number (Raypak Kit # 007374F).
  • Gather all necessary tools, including screwdrivers, wire strippers, and a multimeter.

4.2. Installation Procedure

  1. Carefully remove the existing ignition control module, noting all wire connections. It is recommended to take photos of the existing wiring before disconnection.
  2. Mount the new Raypak Ignition Control Module in the designated location using the provided screws.
  3. Connect all wires to the appropriate terminals on the new module. Refer to the wiring diagram in your heat pump's service manual.
  4. Ensure all connections are tight and secure. Use the provided wire nuts and zip ties for organization and safety.
  5. Once all wiring is complete, double-check all connections for correctness and security.
  6. Restore power to the heat pump unit.

5. Operating Instructions

The Raypak Ignition Control Module operates automatically as part of the heat pump's control system. Once installed and powered, it will initiate the ignition sequence when a call for heat is detected.

  • Ignition Sequence: Upon a call for heat, the module will begin a pre-purge cycle, followed by igniter activation and gas valve opening.
  • Flame Monitoring: The module continuously monitors the flame presence. If the flame is lost during operation, the module will attempt to re-ignite (recycle on loss of flame).
  • Safety Lockout: If ignition fails after multiple attempts, the module will enter a safety lockout mode, indicated by a diagnostic code.

Refer to your heat pump's main user manual for overall system operation and temperature settings.

6. Maintenance

The Raypak Ignition Control Module is designed for reliable, long-term operation with minimal maintenance. However, periodic inspection is recommended as part of your heat pump's overall maintenance schedule.

  • Visual Inspection: Annually inspect the module and its wiring for any signs of damage, corrosion, or loose connections.
  • Cleaning: Keep the module free from dust and debris. Use a soft, dry brush or compressed air for cleaning. Do not use liquid cleaners.
  • Professional Check: It is recommended to have a qualified technician inspect the entire heat pump system, including the ignition control, annually.

7. Troubleshooting

The FENWAL label on the control module provides diagnostic status codes to assist in troubleshooting. Observe the LED indicator on the module and refer to the table below:

Diagnostic Status Codes
Code Condition
ON System OK - no faults present
OFF Possible control fault - check power
1 Flash Low air - brief flashing normal on startup
2 Flashes Flame W/O Call for Heat - system fault
3 Flashes Ignition Lockout - TH-off to reset
4 Flashes Igniter Failure - check amp draw
5 Flashes Low 24 VAC - check control supply voltage
6 Flashes Internal Fault - replace control

If troubleshooting steps do not resolve the issue, contact a qualified service technician.

8. Specifications

8.1. General Product Specifications

  • Product Dimensions: 7.9 x 7.85 x 2.8 inches
  • Item Weight: 15.4 ounces
  • Manufacturer: Raypak
  • ASIN: B07L673SX8

8.2. Electrical and Operational Specifications (from FENWAL label)

  • Catalog Number: 35-673902-561
  • Ignition Time: 4 Seconds
  • Tries: 3
  • Recycle on Loss of Flame: Yes
  • PrePurge: 15 Sec.
  • InterPurge: 15 Sec.
  • PostPurge: 30 Sec.
  • Heatup: 20 Sec.
  • HS Igniter: 120VAC
  • Proving Current: 3.1A
  • Input: 24 VAC, 350 mA, 50/60 Hertz
  • Igniter: 120 VAC, 5A
  • Valve: 24 VAC, 5A
  • Fan: 120 VAC, 15A or 240 VAC, 8A
  • Operating Temperature: -40°C to +73 °C
  • Lockout & Pre-purge: 24 VAC, 1A

9. Warranty Information

Specific warranty details for the Raypak Ignition Control Module are typically provided with the original heat pump unit or can be obtained from your authorized Raypak dealer. Please retain your proof of purchase for warranty claims. Warranty coverage generally applies to defects in materials and workmanship under normal use and service.

10. Customer Support

For technical assistance, replacement parts, or service inquiries, please contact your authorized Raypak dealer or visit the official Raypak website. When contacting support, please have your heat pump model number and the ignition control module's catalog number (35-673902-561) available.