Riello MG569 BWZG Control Unit Instruction Manual

Model: MG569 BWZG | Brand: Riello

1. Product Overview

The Riello MG569 BWZG is a sophisticated control unit designed for reliable and efficient operation of Riello gas burners. This unit manages the ignition, flame supervision, and safety functions of the burner, ensuring optimal performance and adherence to safety standards. It is a direct replacement for several older models, offering enhanced functionality and compatibility.

1.1 Compatibility

This control unit is compatible with the following Riello burner series:

It also replaces previous control unit models including 3002949, 3002967, 569SE, 568SE, 566SE rev3, 566SE rev2, 566SE rev1, and 525SE/G.

Riello MG569 BWZG Control Unit, top view showing terminal connections

Figure 1: Top view of the Riello MG569 BWZG Control Unit, illustrating the various terminal connections for power, ignition, and burner components.

2. Setup and Installation

Installation of the Riello MG569 BWZG control unit requires specialized knowledge of electrical systems and burner operation. It is strongly recommended that installation be performed by a qualified and certified technician to ensure safety and proper functionality.

2.1 Safety Precautions

2.2 Installation Steps (General)

  1. Remove Old Unit: Carefully disconnect and remove the existing control unit, noting all wiring connections.
  2. Mount New Unit: Securely mount the Riello MG569 BWZG control unit in the designated position.
  3. Connect Wiring: Connect all electrical wires according to the burner's wiring diagram. This typically includes connections for power supply (L1, N), ignition transformer, flame sensor, motor, and fuel valve. Ensure all connections are tight and secure.
  4. Grounding: Verify that the unit and burner system are properly grounded to prevent electrical hazards.
  5. Initial Checks: Before restoring power, double-check all connections for correctness and security.
  6. Restore Power: Carefully restore power to the burner system.
  7. Test Operation: Initiate a test firing sequence to ensure the burner ignites and operates correctly, and that all safety features are functioning.
Riello MG569 BWZG Control Unit, showing wiring terminals and mounting points

Figure 2: Another view of the Riello MG569 BWZG Control Unit, highlighting the terminal block for electrical connections and mounting screw locations.

3. Operating Instructions

The Riello MG569 BWZG control unit operates automatically once installed and powered. Its primary function is to manage the burner's ignition sequence, flame supervision, and shutdown procedures in case of malfunction.

3.1 Normal Operation Sequence

  1. Start-up: Upon receiving a call for heat, the control unit initiates a pre-purge cycle to clear the combustion chamber.
  2. Ignition: After pre-purge, the ignition transformer is activated, creating a spark, and the fuel valve opens to allow fuel into the combustion chamber.
  3. Flame Detection: The flame sensor (e.g., photocell or ionization probe) detects the presence of a flame. If a flame is established within the safety time, the ignition spark is cut off, and the burner continues to operate.
  4. Running: The burner operates under the supervision of the control unit, which continuously monitors the flame.
  5. Shutdown: When the call for heat ends, the fuel valve closes, and the burner shuts down. A post-purge cycle may follow.

3.2 Indicator Lights

The control unit may feature indicator lights (LEDs) to signal its operational status or fault conditions. Consult your burner's specific documentation for a detailed explanation of these indicators. Typically, a steady green light indicates normal operation, while a flashing or red light signifies a fault.

4. Maintenance

Regular maintenance is crucial for the longevity and safe operation of your burner system and its control unit. All maintenance should be performed by a qualified service technician.

4.1 Recommended Maintenance Schedule

Note: The control unit itself is a sealed component and is not user-serviceable. Any internal issues require replacement of the unit.

5. Troubleshooting

This section provides general guidance for common issues. For detailed diagnostics, consult a qualified technician.

ProblemPossible CauseAction
Burner does not start / No ignition
  • No power supply to the control unit.
  • Safety lockout (fault condition).
  • Faulty ignition transformer or electrodes.
  • No fuel supply.
  • Check main power switch and circuit breaker.
  • Press the reset button on the control unit (if present). If it locks out again, do not repeatedly reset.
  • Verify fuel supply valve is open.
  • Contact a qualified technician.
Burner ignites but immediately shuts down (flame failure)
  • Dirty or faulty flame sensor.
  • Insufficient combustion air.
  • Low fuel pressure.
  • Faulty control unit.
  • Inspect and clean flame sensor (if accessible and safe).
  • Ensure air intakes are clear.
  • Contact a qualified technician for fuel pressure and control unit diagnostics.
Control unit shows a fault code/light
  • Specific fault detected by the unit.
  • Refer to your burner's specific manual for fault code interpretation.
  • Attempt a single reset. If the fault persists, contact a qualified technician.

6. Technical Specifications

Riello MG569 BWZG Control Unit, side view showing product label with technical specifications

Figure 3: Side view of the Riello MG569 BWZG Control Unit, displaying the product label with key technical specifications.

FeatureDetail
Model NumberMG569 BWZG
ManufacturerRiello
Voltage210-230V ~ 50/60Hz
FuseT4A 250V~
Ignition Voltage18kVpk
Current11mArms
UPC748810822879
CompatibilityRiello BS1, BS2, BS3D, BS4D series burners
Replaces Models3002949, 3002967, 569SE, 568SE, 566SE rev3, 566SE rev2, 566SE rev1, 525SE/G

7. Warranty Information

Specific warranty terms for the Riello MG569 BWZG control unit are typically provided by the seller or manufacturer at the time of purchase. Please retain your proof of purchase for warranty claims.

Information regarding the availability of spare parts is currently unavailable. For any spare part inquiries, please contact your supplier or an authorized Riello service center.

8. Customer Support

For technical assistance, service, or further information regarding the Riello MG569 BWZG control unit, please contact:

When contacting support, please have your product model number (MG569 BWZG) and any relevant purchase details ready.

Related Documents - MG569 BWZG

Preview Riello 40 Series Residential Oil Burners F3 & F5 Installation Manual
This manual provides detailed installation instructions for Riello 40 Series Residential Oil Burners, models F3 and F5. It covers component identification, setup, mounting, electrical connections, nozzle placement, and adjustment procedures. The manual is intended for retrofit applications and includes technical data, specifications, and spare parts lists.
Preview Riello 40 BF Single Stage Operation Oil Burner Installation and Operating Manual
Comprehensive installation and operating manual for the Riello 40 BF single-stage oil burner, covering technical specifications, installation procedures, wiring diagrams, troubleshooting, and spare parts.
Preview Riello Gulliver RG2F Oil Burner Parts List and Diagram
Detailed spare parts list and component diagram for the Riello Gulliver RG2F light oil burner (Model 377T1, Code 3737770), including part numbers and English descriptions.
Preview Priročnik za namestitev, uporabo in vzdrževanje gorilnika RIELLO Gulliver RG1NR na plinsko olje
Ta dokument vsebuje podrobna navodila za namestitev, uporabo, vzdrževanje in odpravljanje napak enostopenjskega gorilnika RIELLO Gulliver RG1NR na plinsko olje, vključno s tehničnimi podatki, varnostnimi predpisi in postopki za odpravljanje težav.
Preview Riello P 140 P/N 471 M1 Heavy Oil Burner Installation and Maintenance Instructions
Comprehensive installation, use, and maintenance instructions for the Riello P 140 P/N 471 M1 heavy oil burner. Covers technical specifications, electrical diagrams, fuel supply systems, and adjustment procedures.
Preview Riello 40 G10 Light Oil Burner Installation and Maintenance Manual
This document provides comprehensive installation, use, and maintenance instructions for the Riello 40 G10 light oil burner. It includes technical data, diagrams, electrical wiring schematics, and combustion adjustment procedures.