1. Overview

The SMARTGEN HAT600N series ATS controller is an intelligent dual-supply module designed for automatic transfer switch (ATS) applications. It features programmable functions, automatic measurement capabilities, an LCD display, and digital communication. This controller integrates digital intelligence and networking to minimize operational errors, making it an ideal solution for ATS systems.

At its core, the HAT600N series ATS controller utilizes a microprocessor to accurately detect 2-way-3-phase voltage. It can make precise judgments and output passive control switch commands in response to abnormal voltage conditions, including over/under voltage, phase loss, and over/under frequency. The controller is designed with comprehensive consideration for various ATS applications, allowing direct use with Intelligent ATS, Contactor ATS, and Circuit Breaker ATS systems. Its compact structure, advanced circuitry, simple wiring, and high reliability make it suitable for a wide range of applications in electric power, telecommunications, petroleum, coal, metallurgy, railways, municipal administration, intelligent buildings, electrical devices, automatic control, and testing systems.

Front view of the SMARTGEN HAT600N ATS Controller with LCD screen and control buttons.

Figure 1: Front view of the SMARTGEN HAT600N ATS Controller. This image displays the controller's user interface, including the LCD screen, alarm indicator, setting buttons, and operational mode buttons (Manual, Auto, Open, Close, Test).

2. Performance and Characteristics

  • System type can be set for: Mains (1#) & Mains (2#), Mains (1#) & Generator (2#), Generator (1#) & Mains (2#), Generator (1#) & Generator (2#).
  • Backlit 128x64 LCD, optional Chinese and English display, push-button operation.
  • Measure and display 2-way 3 phase Voltage and Frequency:
    • 1#: Line-Line voltage (Uab, Ubc, Uca), Line-Nature voltage (Ua, Ub, Uc), Frequency (F1)
    • 2#: Line-Line voltage (Uab, Ubc, Uca), Line-Nature voltage (Ua, Ub, Uc), Frequency (F2)
  • Measure and display active power, apparent power, power factor and 3 phase current.
  • Over current alarm.
  • Over/under voltage, loss of phase, reverse phase sequence, over/under frequency protection.
  • Automatic/Manual mode. In manual mode, can force switch to close or open.
  • All parameters can be set on site. With two different passwords which ensures authorized staff operation only.
  • During genset testing ATS controller can be set either On-load or Off-load mode.
  • ATS Controller has function of automatic Re-closing.
  • Closing output signal can be set as on intervals or as continuous output.
  • Applicable for ATS of one neutral position, two neutral position and change over.
  • Applicable for 2 isolated neutral line for Generator and Mains.
  • Real-time clock (RTC).
  • Event log can record 99 items circularly.
  • Timely schedule can be set on monthly or weekly basis and trial can be set as with on- load or off -load.
  • Can control two generators to work in a cycle, even the genset running time and crank rest time can be set.
  • Widely range of DC power supply (8V to 35V). Max.80V DC input can be endured in an instant, or be supplied via HWS560 module (input AC 85V~560V, output DC 12V).
  • Wide space between connecting terminals of AC input. Max.625V input voltage.
  • With standard isolated RS485 communication interface. With "remote controlling, remote measuring, remote communication" function by the ModBus communication protocol.
  • Can check the current status of controller (including switch digital input, over Voltage, and under Voltage etc.).
  • Suitable for various AC systems (3 phase 4-wires, 3-phase 3-wires, single-phase 2-wire, and 2-phase 3-wire).
  • Modular design, flame-resisting ABS plastic shell, plug-in terminals and embedded installation. Compact structure with easy installation.

3. Setup and Installation

Proper installation is crucial for the safe and reliable operation of the HAT600N ATS Controller. This section provides general guidance; always refer to the detailed wiring diagrams and local electrical codes.

3.1 Wiring Diagrams

The HAT600N controller supports various ATS configurations. Below are illustrative wiring diagrams for common setups. Ensure you select the correct diagram for your specific ATS type (ATS3, SGQ-N/T, SGQ-M, VITZRO).

Detailed wiring diagrams for SMARTGEN ATS Control Modules, including ATS3, SGQ-N/T, SGQ-M, and VITZRO configurations.

Figure 2: Comprehensive wiring diagrams for different ATS control module types compatible with the HAT600N. Each diagram illustrates connections for 1# Voltage Input, 2# Voltage Input, 3-Phase Current Input, and RS485 communication, along with load and generator connections.

3.2 Mounting

The HAT600N features a modular design for embedded installation. Ensure adequate space for ventilation and access to terminals. The panel cutout dimensions are 186mm x 141mm.

3.3 Power Supply

The controller operates on a wide DC power supply range of 8V to 35V. It can withstand a maximum 80V DC input momentarily. Alternatively, it can be supplied via an HWS560 module (AC 85V~560V input, DC 12V output).

3.4 AC Voltage Input

The controller supports various AC systems (3-phase 4-wire, 3-phase 3-wire, single-phase 2-wire, and 2-phase 3-wire). Ensure correct wiring for voltage inputs (L-L and L-N) as per the specific model variant (HAT600N/HAT600NI or HAT600NB/HAT600NBI).

4. Operating Instructions

The HAT600N ATS Controller offers both automatic and manual operating modes, controlled via its push-button interface and LCD display.

4.1 Mode Selection

  • Automatic Mode: The controller continuously monitors the primary and secondary power sources. Upon detection of an abnormality in the primary source, it automatically initiates the transfer sequence to the secondary source. Once the primary source recovers, the system automatically transfers back.
  • Manual Mode: Allows for manual control of the transfer switch. In this mode, operators can force the switch to close or open using the dedicated buttons on the controller's front panel. This mode is typically used for testing or maintenance.

4.2 Parameter Settings

All operational parameters can be configured directly on site using the controller's push-buttons and LCD display. Access to these settings is protected by two different password levels to ensure only authorized personnel can make adjustments. Parameters include system type, voltage/frequency thresholds, transfer delays, and scheduling for genset trials.

4.3 Monitoring

The LCD display provides real-time monitoring of 2-way 3-phase voltage, frequency, active power, apparent power, power factor, and 3-phase current for both power sources. The controller also logs up to 99 events circularly, providing a history of operations and alarms.

5. Specifications

The following table details the technical specifications of the SMARTGEN HAT600N ATS Controller:

ItemContents
DC Power Supply8.0V-35.0V continuous power supply; HTS220/HWS560 power supply (without DC input).
Operating VoltageAC 160V-280V (HAT600N/HAT600NI) during AC power L1N1/L2N2 supply.
Power Consumption<2W (Standby mode: <2W)
AC Voltage Input
  • HAT600N/HAT600NI: 3P4W (L-L) (80-625)V, 3P3W (L-L) (80-625)V, 1P2W (L-N) (50-360)V, 2P3W (A-B) (80-625)V
  • HAT600NB/HAT600NBI: 3P4W (L-L) Not used, 3P3W (L-L) Not used, 1P2W (L-N) (50-280)V, 2P3W (A-B) (50-480)V
Rated Frequency50/60Hz
Close / Open Trip Relay Output16A AC250V Free Voltage relay output
Programmable Relay Output16A/7A AC250V Free Voltage relay output
Digital InputConnecting to GND
CommunicationRS485 isolated interface, MODBUS Protocol
Dimensions209mm x 153mm x 55mm
Panel Cutout186mm x 141mm
Operating Temp. RangeTemperature: (-25~+70)°C; Humidity: (20~93)%RH
Storage ConditionTemperature: (-25~+70)°C
Protection RankIP55 Gasket
Insulation StrengthApply AC2.2kV voltage between high voltage terminal and low voltage terminal; The leakage current is not more than 3mA within 1min.
Weight0.8kg (HAT600N, HAT600NI) / 1.0kg (HAT600NB/HAT600NBI)
Product Dimensions8.23 x 6.02 x 2.17 inches
Item Weight1.7 pounds

6. Maintenance

To ensure the longevity and optimal performance of your SMARTGEN HAT600N ATS Controller, regular maintenance is recommended. While the controller is designed for high reliability, periodic checks can prevent potential issues.

  • Visual Inspection: Periodically inspect the controller for any signs of physical damage, loose connections, or dust accumulation.
  • Cleaning: Keep the controller's exterior and display clean using a soft, dry cloth. Avoid using abrasive cleaners or solvents.
  • Terminal Checks: Ensure all wiring terminals are securely fastened. Loose connections can lead to intermittent operation or damage.
  • Environmental Conditions: Verify that the operating environment remains within the specified temperature and humidity ranges to prevent premature component failure.
  • Firmware Updates: Check the manufacturer's website for any available firmware updates that may improve performance or address known issues.

For any complex maintenance or repairs, it is recommended to contact qualified service personnel or SMARTGEN technical support.

7. Troubleshooting

This section provides general guidance for common issues you might encounter with the HAT600N ATS Controller. For detailed diagnostics, refer to the full product manual or contact technical support.

  • Controller Not Powering On:
    • Check the DC power supply connections and ensure the voltage is within the 8V-35V range.
    • If using an HWS560 module, verify its AC input and DC output.
    • Inspect fuses if present in the power supply line.
  • Automatic Transfer Not Occurring:
    • Ensure the controller is in "Automatic Mode".
    • Check voltage and frequency readings on the LCD for both sources to confirm abnormalities are detected.
    • Verify that protection parameters (over/under voltage, frequency, phase loss) are correctly set and not preventing transfer.
    • Inspect control wiring to the ATS mechanism.
  • Incorrect Readings on LCD:
    • Verify AC voltage and current input wiring according to the appropriate diagram (Figure 2).
    • Ensure the system type (3-phase 4-wire, etc.) is correctly configured in the controller settings.
  • Communication Issues (RS485):
    • Check RS485 wiring for correct polarity and secure connections.
    • Verify ModBus communication parameters (baud rate, address) are correctly set on both the controller and the connected device.

If the issue persists after performing these checks, contact SMARTGEN technical support for further assistance.

8. Warranty and Support

For information regarding the product warranty, please refer to the warranty card included with your purchase or visit the official SMARTGEN website. Warranty terms typically cover manufacturing defects under normal operating conditions.

For technical support, troubleshooting assistance, or inquiries about spare parts, please contact SMARTGEN customer service. You can find contact information on the SMARTGEN-America website or through your local distributor.

When contacting support, please have your product model (HAT600N) and any relevant purchase details ready to facilitate a quicker resolution.

© 2025 SMARTGEN. All rights reserved.