1. Introduction
This manual provides essential instructions for the safe installation, operation, and maintenance of the Fulham Lighting FHSAC1UNV40C FireHorse Hot Spot Plus All-in-One LED Driver & Emergency System. This unit integrates an LED driver with an emergency lighting system, offering 0-10V dimming and programmable output for various LED applications. Please read this manual thoroughly before installation and retain it for future reference.
2. Safety Information
WARNING: Risk of electric shock. Installation and servicing must be performed by qualified personnel only. Disconnect power before servicing.
- Ensure all wiring complies with national and local electrical codes.
- Do not install in locations where the ambient temperature exceeds the specified operating range.
- This device is designed for dry and damp locations only.
- Proper grounding is required to prevent electric shock.
- Do not attempt to open or modify the unit. There are no user-serviceable parts inside, except for the replaceable battery.
3. Product Overview
The FHSAC1UNV40C is a compact, all-in-one solution for LED lighting, combining a high-performance LED driver with an integrated emergency backup system. It features a replaceable battery and supports 0-10V dimming. The output current is programmable, allowing for flexible application with various LED modules.

Image 3.1: The Fulham FHSAC1UNV40C FireHorse Hot Spot Plus unit, showing the integrated LED driver and emergency battery components.
4. Specifications
| Feature | Description |
|---|---|
| Model Number | FHSAC1UNV40C |
| Input Voltage | 120-277VAC |
| Output Voltage | 11-55VDC |
| Normal Operation Power | Up to 40W |
| Emergency Power Output | 5W or 10W (User-selectable) |
| Programmable Output Current | 250mA - 1400mA |
| Dimming | 0-10V Dimming |
| Emergency Run Time | 700 lumens for 180 min or 1400 lumens for 90 min (using 140LPW LED module) |
| Battery Type | LiFePO4, 3200mAh |
| Battery Charge Time | 12 Hours |
| Dimensions | 6.32 x 3.05 x 1.14 inches (Unit) |
| Weight | 1.67 pounds |
| Operating Temperature | 0-55°C (32-131°F) |

Image 4.1: Key features of the FireHorse Hot Spot Plus system, including compatibility, installation flexibility, and emergency illumination duration.
5. Setup and Installation
IMPORTANT: All installation procedures must be performed by a qualified electrician in accordance with the National Electrical Code and local regulations.
5.1 Pre-Installation Checks
- Verify that the input voltage (120-277VAC) matches the building's electrical supply.
- Ensure the LED module's voltage and current requirements are compatible with the FHSAC1UNV40C's output range.
- Confirm the installation environment is suitable (dry/damp location, within specified ambient temperature).
5.2 Wiring Instructions
Refer to the wiring diagram provided on the unit label for specific connections. General wiring steps include:
- Input Power: Connect the AC input wires (Black, White, Green/Ground) to the building's electrical supply.
- LED Output: Connect the LED output wires (typically Red/Positive, Blue/Negative) to the LED module.
- Dimming Control: Connect the 0-10V dimming wires (Purple/Dim+, Gray/Dim-) to a compatible 0-10V dimmer or control system.
- Test Switch: Connect the illuminated test switch wires as indicated. This switch is used for manual testing of the emergency function.
- Battery Connection: Ensure the internal battery is properly connected. The unit will begin charging the battery upon initial power-up.
5.3 Programmable Output Current
The output current can be programmed to match the specific requirements of the LED module. Consult the product datasheet or contact Fulham Lighting support for detailed instructions on programming the output current. This typically involves a specific programming device or procedure.
6. Operating Instructions
6.1 Normal Operation
When AC power is supplied, the FHSAC1UNV40C operates as a standard LED driver, providing power to the connected LED module. The 0-10V dimming input allows for adjustment of the LED brightness.
6.2 Emergency Operation
In the event of an AC power failure, the unit automatically switches to emergency mode, powering the LED module from its internal battery. The emergency power level (5W or 10W) is user-selectable during installation.

Image 6.1: Illustration of emergency lighting functionality, where lights illuminate during a power failure.
6.3 Test Switch and Self-Diagnostics
The illuminated test switch provides visual indication of the unit's status and allows for manual testing of the emergency function. The unit also features switchable self-diagnostics, which automatically perform periodic tests of the battery and emergency circuitry. Refer to the unit's label for specific diagnostic indicator patterns.
7. Maintenance
7.1 Battery Charging
The internal LiFePO4 battery requires a minimum of 12 hours to fully charge after installation or a prolonged power outage. Ensure continuous AC power is supplied to allow for proper battery charging.
7.2 Monthly Testing
Perform a monthly 30-second functional test by pressing and holding the test switch. The LED module should illuminate in emergency mode. Release the switch, and the unit should return to normal operation.
7.3 Annual Testing
Conduct an annual 90-minute (or 180-minute, depending on selected output) full discharge test. Interrupt AC power to the unit for the specified duration. The LED module should remain illuminated for the entire test period. If the LED module does not remain illuminated for the full duration, the battery may need replacement.
7.4 Battery Replacement
The battery is replaceable. When replacement is necessary, use only the specified Fulham replacement battery (Model FHSBATL2-3.2L). Disconnect AC power before replacing the battery. Dispose of old batteries according to local regulations.
8. Troubleshooting
| Problem | Possible Cause | Solution |
|---|---|---|
| LED module does not illuminate in normal mode. | No AC power, incorrect wiring, faulty LED module, incorrect output current programming. | Check AC power supply. Verify wiring connections. Test LED module. Confirm output current programming. |
| LED module does not illuminate in emergency mode. | Battery not charged, battery faulty, incorrect wiring, faulty emergency circuit. | Allow 12 hours for battery charging. Perform battery test. Verify wiring. Replace battery if necessary. |
| Emergency run time is shorter than specified. | Battery not fully charged, battery nearing end of life. | Ensure full 12-hour charge. Replace battery if it fails annual test. |
| LED module flickers or dims unexpectedly. | Unstable AC power, dimming control issue, incompatible LED module. | Check AC power quality. Verify 0-10V dimming connections and dimmer compatibility. Ensure LED module is compatible. |
If troubleshooting steps do not resolve the issue, contact Fulham Lighting technical support.
9. Warranty and Support
For specific warranty information and technical support, please refer to the official Fulham Lighting website or contact their customer service department. Keep your purchase receipt as proof of purchase.
Fulham Lighting Contact Information:
Visit www.fulham.com for support and product information.