Allanson 2260-TP

Allanson Industrial Gas Ignitor

Model: 2260-TP

1. Introduction

This manual provides essential information for the safe and effective installation, operation, and maintenance of the Allanson Industrial Gas Ignitor, Model 2260-TP. This electronic ignition transformer is designed for industrial gas applications, providing reliable ignition for various heating systems.

Allanson Industrial Gas Ignitor Model 2260-TP

Figure 1: Allanson Industrial Gas Ignitor Model 2260-TP. This image displays the black rectangular electronic ignition transformer with a white label. The label clearly shows 'Allanson ELECTRONIC IGNITION TRANSFORMER CAT No. 2260-TP', along with primary and secondary voltage/current ratings. It also indicates 'MADE IN CANADA'. Electrical wires are visible, connected to one side of the unit.

2. Safety Information

WARNING: Installation and servicing of this ignitor must be performed by a qualified and licensed professional. Failure to follow these instructions could result in property damage, personal injury, or death.

3. Product Overview

The Allanson 2260-TP is an electronic ignition transformer designed to provide a high-voltage spark for igniting gas in industrial heating systems. It converts standard line voltage to a high-voltage output, ensuring reliable and efficient ignition.

Key Features:

4. Setup and Installation

Before You Begin:

  1. Ensure the power supply matches the ignitor's specifications (120V, 50/60Hz).
  2. Confirm the ignitor is compatible with your specific heating system.
  3. Gather necessary tools: screwdrivers, wire strippers, multimeter, mounting hardware.

Installation Steps:

  1. Power Disconnection: Turn off all power to the heating system at the main circuit breaker. Verify power is off using a multimeter.
  2. Remove Old Ignitor (if applicable): Carefully disconnect wiring and mounting hardware from the existing ignitor. Note wire connections for reference.
  3. Mounting: Securely mount the Allanson 2260-TP ignitor in the designated location using appropriate hardware. Ensure it is stable and free from vibration.
  4. Wiring: Connect the primary (input) wires to the 120V AC power supply according to the wiring diagram of your appliance. Connect the secondary (output) wires to the spark electrode or ignition rod. Ensure all connections are tight and insulated. Refer to the label on the ignitor for specific primary and secondary connections.
  5. Grounding: Ensure the ignitor and the appliance are properly grounded.
  6. Final Checks: Double-check all wiring connections. Ensure no loose wires or potential short circuits.

5. Operating Instructions

The Allanson 2260-TP ignitor operates automatically as part of the heating system's control sequence. Once properly installed and wired, it will generate a high-voltage spark when called upon by the system's control board to ignite the gas burner.

To Operate:

  1. Ensure all installation steps are completed and verified.
  2. Restore power to the heating system.
  3. Initiate a call for heat from the thermostat or control system.
  4. Observe the ignitor's operation. It should produce a visible spark at the electrode, leading to gas ignition.
  5. If ignition does not occur, refer to the Troubleshooting section.

6. Maintenance

The Allanson 2260-TP ignitor is designed for long-term reliability with minimal maintenance. However, periodic inspection of the entire ignition system is recommended as part of routine appliance servicing.

7. Troubleshooting

If the ignitor is not functioning correctly, perform the following checks. Always disconnect power before inspecting components.

Problem Possible Cause Solution
No Spark from Ignitor
  • No power to ignitor.
  • Faulty wiring connection.
  • Defective ignitor.
  • Faulty control board.
  • Check circuit breaker and power supply.
  • Verify all wiring connections are secure.
  • Test ignitor for proper voltage output (requires specialized equipment and knowledge).
  • Consult appliance manual for control board diagnostics.
Intermittent Spark/Ignition
  • Loose wiring connections.
  • Dirty or worn spark electrode.
  • Fluctuating power supply.
  • Tighten all electrical connections.
  • Clean or replace the spark electrode.
  • Have an electrician check the power supply.
Ignitor Sparks but No Gas Ignition
  • No gas supply.
  • Faulty gas valve.
  • Blocked burner orifice.
  • Improper spark gap.
  • Check gas supply to the appliance.
  • Test gas valve operation.
  • Clean burner orifices.
  • Adjust spark gap according to appliance specifications.

If problems persist after troubleshooting, contact a qualified HVAC technician or the manufacturer for assistance.

8. Specifications

Attribute Value
Manufacturer Allanson
Part Number 2260-TP
Item Weight 7 pounds
Item Package Quantity 1
Primary Voltage/Current 120V 50/60Hz 0.6A
Secondary Voltage/Current 15.6 kVpk 28 mA
Date First Available August 18, 2017

9. Warranty and Support

Specific warranty information for the Allanson Industrial Gas Ignitor #2260-TP is not provided in this manual. For details regarding warranty coverage, terms, and conditions, please refer to the documentation included with your purchase or contact Allanson directly through their official website or customer service channels.

For technical support or further assistance, please reach out to a qualified HVAC professional or the manufacturer's support team.

Related Documents - 2260-TP

Preview Allanson 2260 Series Electronic Ignitors Instruction Manual
Comprehensive instruction manual for Allanson 2260 series electronic ignitors (models 2260-TP, 2260-TPLP, 2260-TW, 2260-TWLP, 2260-P, 2260-TPLPJB). Includes installation, maintenance, testing, and mechanical specifications for commercial and industrial gas applications.
Preview Allanson OMNI Electronic Ignitor Type 2275U Instruction Manual
Instruction manual for the Allanson OMNI Electronic Ignitor, Type 2275U, providing application details, specifications, installation, maintenance, and testing procedures for reliable ignition in gas and oil systems.
Preview Allanson OMNI 2270U-3ST Electronic Ignitor Specification Guide
Detailed specification guide for the Allanson OMNI 2270U-3ST universal electronic ignitor, featuring a built-in 3-second timer and diagnostic tool for oil burner systems. Includes technical specifications, dimensions, and contact information.
Preview Allanson 2270U-3ST OMNI Universal Electronic Ignitor Specification Guide
Detailed specification guide for the Allanson 2270U-3ST OMNI Universal Electronic Ignitor, featuring a built-in 3-second timer and diagnostic capabilities for oil burner systems.
Preview Allanson Industrial Gas Transformers: Specifications and Cross-Reference Guide
Detailed specifications and cross-reference charts for Allanson Industrial Gas Transformers, covering models like 1092-H, 1092-PF-G, and others, with compatibility information for various burner manufacturers.
Preview Allanson ACL-SC-DMX DMX Sub-Controller Installation Manual
This installation manual provides detailed instructions for the Allanson ACL-SC-DMX DMX Sub-Controller, covering specifications, port configurations, wiring diagrams, and important safety precautions for RGBW lighting systems.