Datakom DKM 224

Datakom DKM-0224 Alarm Annunciator User Manual

Model: DKM 224

1. Introduction

This manual provides comprehensive instructions for the installation, operation, and maintenance of the Datakom DKM-0224 Alarm Annunciator. The DKM-0224 is a 24-channel alarm annunciator designed for use in generator sets and industrial automation systems, providing visual and audible alerts for various operational conditions.

It features optically isolated digital inputs with noise-cancelling filters and adjustable detection delay. The module includes 3 relay outputs for horn, bell, and internal failure, and supports RS-485 Modbus RTU communication for remote monitoring.

Front view of Datakom DKM-0224 Alarm Annunciator

Figure 1.1: Front panel of the Datakom DKM-0224 Alarm Annunciator, showing 24 alarm channels with red/green LEDs, and control buttons for Reset, Horn, Test, and Acknowledge (ACK).

2. Key Features

  • 24 optically isolated digital inputs with noise-cancelling filters.
  • Adjustable detection delay for inputs (2ms to 500ms).
  • 3 configurable relay outputs (Horn, Bell, Internal Failure) rated at 5A/250V.
  • Bicolor (red/green) LED indicators for each channel, indicating alarm status.
  • Front panel pushbuttons for alarm acknowledgment, reset, and test.
  • RS-485 Modbus RTU communication for remote monitoring and control.
  • Wide supply voltage range: 19-150VDC or 85-305VAC.
  • Designed for front panel mounting.
  • Generator protection features with built-in alarms and warnings.

3. Setup and Installation

3.1 Panel Mounting

The DKM-0224 is designed for front panel mounting. Ensure adequate space for installation and ventilation.

Panel cut-out dimensions for Datakom DKM-0224

Figure 3.1: Panel cut-out dimensions (140mm x 140mm) and side view with minimum depth requirement (55mm) for the DKM-0224.

The required panel cut-out dimensions are 140mm x 140mm. The minimum depth required behind the panel is 55mm.

3.2 Wiring Connections

Refer to the back view diagram for detailed wiring instructions. All connections should be made by qualified personnel.

Back view of Datakom DKM-0224 with wiring terminals

Figure 3.2: Back view of the DKM-0224 showing power supply terminals, RS-485 connections, relay outputs, and 24 digital input terminals (IN-01 to IN-24).

  • Power Supply: Connect the main power supply to the designated terminals. The unit accepts 19-150VDC or 85-305VAC.
  • Digital Inputs (IN-01 to IN-24): Connect your alarm sources to these 24 optically isolated inputs. Each input can handle up to 30V DC/AC.
  • Relay Outputs: Connect external devices like horns or bells to the "WATCHDOG", "BELL", and "HORN" relay output terminals. These are rated 5A/250V.
  • RS-485: For Modbus RTU communication, connect the RS-485 A, B, and G terminals to your communication network.

3.3 DIP Switch Settings

The DKM-0224 features DIP switches on the back panel for configuring input filter delay and RS-485 baud rate.

  • Filter Delay (S1-S3): Adjust the input detection delay from 2ms to 500ms to prevent false alarms from transient signals. Refer to the back panel diagram for specific switch combinations.
  • Baud Rate (S4): Set the RS-485 communication baud rate to either 9600 bd or 19200 bd to match your system.
  • Node Address (S5-S8): Configure the Modbus node address using DIP switches S5-S8.

4. Operation

The DKM-0224 provides clear visual and audible indications for alarm conditions. Understanding the LED states and pushbutton functions is crucial for proper operation.

Detailed description of DKM-0224 alarm LEDs, audible warnings, relay outputs, and pushbutton functions

Figure 4.1: Detailed operational guide for the DKM-0224, explaining LED behaviors, audible warnings, relay functions, and pushbutton controls.

4.1 Alarm LEDs

  • FAST FLASH (Red): Indicates the first detection of a fault.
  • SLOW FLASH (Red): Activated when the ACK (acknowledge) pushbutton is pressed and the fault signal is still active.
  • STEADY ON (Red): Activated if the fault signal disappears at SLOW FLASH condition.
  • LED OFF: The alarm LED turns off when the RESET pushbutton is pressed and the fault signal is not present.

4.2 Audible Warnings

  • When a fault signal is detected, the internal buzzer turns on with a period of 1 second. If the ACK pushbutton is pressed, the buzzer turns off. If ACK is not pressed within 1 minute, it switches to slow sound mode (beeps once every 10 seconds).

4.3 Relay Outputs

  • HORN RELAY: If any "red" alarm LED turns on, then the horn relay also turns on. The relay turns off when the HORN pushbutton is pressed.
  • BELL RELAY: If any "green" alarm LED turns on, then the bell relay also turns on. The relay turns off when the ACK pushbutton is pressed.
  • WATCHDOG RELAY: A watchdog relay turns on. If the board fails, then the watchdog relay turns off.

4.4 Other LEDs

  • HORN/BELL LED: The HORN relay turns on if the red LEDs are active. If the HORN relay is not on and the BELL relay is on, then the green LEDs are active. Both are off when no alarms are active.
  • SAFE/FAIL LED: If an internal fault condition is detected in the unit, this LED will turn on "red", otherwise it turns on "green".

4.5 Pushbutton Functions

  • ACK (Acknowledge): When ACK is pressed, fast flashing LEDs switch to slow flash (or steady on) mode, and the internal buzzer turns off.
  • RESET: When RESET is pressed, all alarm LEDs turn off and both relay bells turn off. If a fault signal is present, the alarm will occur again.
  • TEST: When pressed, all LEDs will turn on and green, alternatively and the buzzer sounds.
  • HORN: When pressed, HORN and BELL relays will turn on alternatively for 1 second.

5. Maintenance

The Datakom DKM-0224 is designed for reliable operation with minimal maintenance. Regular checks can help ensure its longevity and proper function.

  • Cleaning: Keep the front panel clean and free of dust. Use a soft, dry cloth for cleaning. Avoid abrasive cleaners or solvents.
  • Connection Checks: Periodically inspect all wiring connections to ensure they are secure and free from corrosion.
  • Environmental Conditions: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent damage.

6. Troubleshooting

If the DKM-0224 is not functioning as expected, consider the following common issues:

  • No Power:
    • Verify the power supply connections are correct and secure.
    • Ensure the power source is providing the correct voltage (19-150VDC or 85-305VAC).
  • Alarm Not Activating:
    • Check the input wiring for the specific channel.
    • Ensure the alarm source is active and providing the correct signal to the input.
    • Verify DIP switch settings for filter delay are not excessively long, potentially delaying alarm detection.
  • Audible Alarm Not Sounding:
    • Check if the internal buzzer is enabled (if configurable).
    • Ensure the ACK button has not been pressed, silencing the buzzer.
  • Relay Output Not Activating:
    • Verify the relay output wiring is correct.
    • Ensure the associated alarm condition is active and the relay logic is met (e.g., red LED for Horn relay).
    • Check the WATCHDOG relay for internal fault indications (SAFE/FAIL LED).
  • Communication Issues (RS-485):
    • Check RS-485 wiring (A, B, G).
    • Verify DIP switch settings for baud rate and node address match the communication system.
    • Ensure proper termination resistors are used on the RS-485 bus if applicable.

7. Technical Specifications

The following table details the technical specifications of the Datakom DKM-0224 Alarm Annunciator.

Technical specifications table for Datakom DKM-0224

Figure 7.1: Overview of technical specifications, back view wiring, and panel cut-out dimensions for the DKM-0224.

ParameterValue
Supply Input19-150VDC (optional 88-400VDC, 85-270VAC)
Power Consumption< 4 VA
Fault Inputs24 opto-isolated inputs, with positive inputs and common negative terminals, protected against high voltage and electrical noise.
Input Impedance40k-ohms (opt. 130k-ohms)
Input CurrentMax. 30mA @ 1VDC
Surge Protection1000V / 50us
Isolation1000V AC, 1 minute
Filter Delay2-5-10-20-50-100-200-500ms selectable
Visual Warnings26 ultra-bright and bicolor LEDs (red-green)
Audible WarningInternal 23mm buzzer, 80dB
Relay Outputs3 outputs, 5A @ 250V AC
Serial PortRS-485
Signal TypeRS-485
ProtocolModbus RTU
Baud Rate9600 / 19200 baud
Isolation1000V AC, 1 minute
Operating Temp. Range-20°C ... +70°C
Storage Temp. Range-40°C ... +85°C
Max. Relative Humidity%95 non-condensing.
Protection DegreeIP 65 (Front, with gasket), IP 30 (Rear panel)
EnclosureFlame retardant ROHS compliant, high temperature ABS/PC (UL94 V0)
InstallationFlush mount with rear retaining plastic brackets.
ConnectorsTwo part connection system.
Cable Sectionmax. 2.5mm²
Dimensions164x164x60mm (WxHxD)
Panel Cut-out140x140mm
Weight400 gr
EU Directives2006/95/EC (LVD), 2004/108/EC (EMC)
Reference StandardsEN 61010 (safety), EN 61326 (EMC)

8. Warranty and Support

Information regarding the product warranty and technical support is typically provided by the manufacturer, Datakom, or your authorized reseller at the time of purchase. Please refer to your purchase documentation or contact Datakom directly for details on warranty coverage, service, and technical assistance.

For further information, you may visit the official Datakom website or contact their customer support.

Related Documents - DKM 224

Preview DATAKOM DKM-0216 Alarm Anons Ünitesi - Teknik Özellikler ve Fonksiyonlar
DATAKOM DKM-0216 Alarm Anons Ünitesi hakkında detaylı bilgiler, enerji ve otomasyon sistemleri için özellikler, teknik şartnameler, kurulum yönergeleri ve operasyonel fonksiyonlar.
Preview DKM-0216 Alarm Annunciator Unit User Manual
Comprehensive user manual for the Datakom DKM-0216 Alarm Annunciator Unit, covering installation, operation, features, Modbus communication, and technical specifications.
Preview DKM-401 Digital Multimeter: Installation and Technical Specifications
Comprehensive guide for the DATAKOM DKM-401 Digital Multimeter, covering installation, electrical safety, technical specifications, and operational functions for 3-phase distribution panels.
Preview DKG-705 User Manual: Generator Synchronization and Control
Comprehensive user manual for the DATAKOM DKG-705 Automatic Mains Failure (AMF), parallel-to-mains, and dual genset synchronization unit with J1939 interface. Learn about installation, features, operation, and troubleshooting.
Preview DPR-02 Voltage Protection Relay (Line to Neutral) - Datakom
The Datakom DPR-02 is a three-phase voltage protection relay for line-to-neutral applications. It protects against over-voltage, under-voltage, and phase rotation issues in distribution substations, generators, motors, transformers, and compensation systems. Features include adjustable voltage limits, trip and reset delays, and phase sequence protection.
Preview DATAKOM D-300 MK3 Advanced Genset Controller User Manual
This user manual provides detailed information on the DATAKOM D-300 MK3 Advanced Genset Controller, covering its functionalities, communications, installation, programming, and technical specifications for industrial generator control.