Datakom DSD-080

Datakom DSD-080 Earthquake Shutdown Panel with Battery

User Manual

Model: DSD-080 | Brand: Datakom

1. Introduction

The Datakom DSD-080 Seismic Security Panel is designed to monitor seismic motions indicative of a strong earthquake. Upon detection, it provides relay output signals to shut down critical installations such as natural gas and LPG systems, generators, and elevators, thereby reducing potential damage. The unit features a graphical display screen that shows the current system status.

The DSD-080 incorporates highly sensitive triple-axis seismic sensors and is designed for maintenance-free operation with self-test capabilities. Its earthquake sensing specifications conform to ANSI 241.80 (1981), ASCE 25-97, and TS-12884 (2002) standards.

Operating on mains power, the DSD-080 includes an internal 24V/1.2Ah battery for backup, providing automatic battery charging and ensuring continued operation during power failures. In low battery conditions, the unit activates audible and visible alarms.

2. Important Safety Information

VERY IMPORTANT: This Datakom item is not sold for usage in USA and Canada.

Early sensing time is dependent on the distance of the unit from the seismic epicenter. Generally, a 1-second early warning time is possible for every 8 kilometers. For example, if the earthquake epicenter is 40 km away, a 5-second early warning may be provided before the arrival of destructive S (secondary) waves.

Due to its high sensitivity, the early warning system may generate false alarms. For instance, a small magnitude earthquake might be detected as the P (primary) waves of a stronger earthquake.

3. Product Overview

Datakom DSD-080 Earthquake Shutdown Panel front view

Figure 3.1: Front view of the Datakom DSD-080 panel, showing the display, operational indicators, and control buttons.

The DSD-080 features a clear graphical display for system status and indicators for operational status, battery health (OK/Low), and mains failure. Control buttons are provided for navigation and reset functions.

4. Features

  • Wide operating voltage range (85-305VAC)
  • Conforms to international earthquake standards
  • Triple-axis motion detection
  • Automatic self-test function
  • Internal audible warning system
  • Internal 24V battery for backup power
  • 5 programmable relay outputs (5A capacity)
  • Visual indicators for battery status
  • Wide operating temperature range (-10°C to +70°C)
  • Suitable for 1-3 phase gasoline and diesel gensets
  • Designed for front panel mounting
  • Survives cranking dropouts
  • Generator protection, built-in alarms and warnings

5. Setup and Installation

5.1 Connection Diagram

Datakom DSD-080 Connection Diagram

Figure 5.1: Wiring diagram for the DSD-080, illustrating power supply, battery, relay outputs, and solenoid valve connections.

The DSD-080 requires connection to a power supply (85-300VAC) and its internal battery. It provides multiple relay outputs (RL1-RL4) and common terminals (COM) for connecting to external devices such as solenoid valves (e.g., 24VDC solenoid valve shown). Ensure all connections are made securely and according to local electrical codes.

5.2 Mounting

The unit is designed for front panel mounting. Ensure adequate space for ventilation and access to connections. Refer to the product dimensions in the specifications section for precise cutout requirements.

6. Operating Instructions

6.1 Power On

Once all connections are made and power is supplied, the unit will perform an automatic self-test. The display will show system status, and indicators will illuminate accordingly.

6.2 Status Indicators

  • OPERATIONAL: Indicates the unit is functioning correctly.
  • BATTERY OK: Indicates the internal battery is charged and healthy.
  • LOW BATTERY: Indicates the internal battery charge is low.
  • MAINS FAILURE: Indicates loss of primary power supply.

6.3 Reset Function

The RESET button on the front panel can be used to clear alarms or initiate a self-test. Press and hold the button as instructed by the on-screen prompts or for specific troubleshooting scenarios.

6.4 Earthquake Detection

Upon detecting seismic activity exceeding the programmed threshold, the unit will activate its audible warning, illuminate relevant indicators, and trigger the programmable relay outputs to shut down connected systems.

7. Maintenance

The DSD-080 is designed to be maintenance-free. However, regular checks are recommended to ensure optimal performance:

  • Visual Inspection: Periodically inspect the unit for any physical damage, loose connections, or signs of wear.
  • Battery Check: Monitor the 'BATTERY OK' and 'LOW BATTERY' indicators. While the unit has automatic charging, prolonged 'LOW BATTERY' status may indicate a battery issue.
  • Cleaning: Keep the front panel and display clean using a soft, dry cloth. Avoid abrasive cleaners or solvents.
  • Functionality Test: If possible and safe, periodically test the system's response to simulated seismic events or use the self-test function if available through the menu.

8. Troubleshooting

  • Unit Not Powering On: Check the main power supply connection (85-305VAC) and ensure it is live. Verify the internal battery is connected and charged.
  • 'MAINS FAILURE' Indicator On: Confirm the main power supply is active. If power is present, check the wiring to the unit.
  • 'LOW BATTERY' Indicator On: Allow time for the internal battery to charge. If the indicator persists, the battery may need replacement or there could be an issue with the charging circuit.
  • False Alarms: Review the 'IMPORTANT NOTICE' section regarding sensitivity. Ensure the unit is mounted securely and not subject to non-seismic vibrations.
  • Relays Not Activating: Check the programming of the relay outputs. Verify connections to the external devices.

For issues not resolved by these steps, please contact Datakom support.

9. Technical Specifications

CategorySpecification
Operating Voltage85 to 305VAC
Supply Power4W maximum
Battery Charge Voltage27.5VDC (+/-0.2V)
Battery Charge Current100mA, maximum
Low Battery Voltage Limit22V (+/- 0.3V)
Current Drain from Battery10mA max from 24VDC (all relays passive); Additional 6mA for each energized relay
Battery Capacity24VDC, 1.2Ah
Operation from Battery>24 hours (typically 72 hours)
Self TestAt power-on and reset
Switching5 relay outputs (5A / 30VDC / 250VAC)
Audible Warning90dB 1m buzzer
Operating Temperature Range-10 to +70 °C
Relative Humidity%10 to %90 (non-condensing)
Weight1900 grams (approximately)
Dimensions (W x H x D)192 x 120 x 65mm
Sensor Specifications
Sensor TypeTriple axis polysilicon semiconductor acceleration sensor
Sensor Operating Limits±2g
Sensor Failure LimitMore than 50g
Accelerating ThresholdTS12884, ANSI Z21.80 (1981), ASCE 25-97
Detection Delay0.5s, maximum
Frequency Range0.5Hz to 25Hz

10. Support and Contact Information

For technical assistance, inquiries, or further information regarding the Datakom DSD-080 Earthquake Shutdown Panel, please contact:

DATAKOM Electronics Ltd.
Tel: +90-216 4668460
Fax: +90-216 3646565
E-mail: datakom@datakom.com.tr
Website: www.datakom.com.tr

Related Documents - DSD-080

Preview DKG-705 User Manual: Generator Synchronization and Control
Comprehensive user manual for the DATAKOM DKG-705 Automatic Mains Failure (AMF), parallel-to-mains, and dual genset synchronization unit with J1939 interface. Learn about installation, features, operation, and troubleshooting.
Preview DPR-02 Voltage Protection Relay (Line to Neutral) - Datakom
The Datakom DPR-02 is a three-phase voltage protection relay for line-to-neutral applications. It protects against over-voltage, under-voltage, and phase rotation issues in distribution substations, generators, motors, transformers, and compensation systems. Features include adjustable voltage limits, trip and reset delays, and phase sequence protection.
Preview DKM-401 Digital Multimeter: Installation and Technical Specifications
Comprehensive guide for the DATAKOM DKM-401 Digital Multimeter, covering installation, electrical safety, technical specifications, and operational functions for 3-phase distribution panels.
Preview DATAKOM D-300 MK3 Advanced Genset Controller User Manual
This user manual provides detailed information on the DATAKOM D-300 MK3 Advanced Genset Controller, covering its functionalities, communications, installation, programming, and technical specifications for industrial generator control.
Preview Datakom D-500 MK3 Jeneratör Kontrol Cihazı Kullanım Kılavuzu
Datakom D-500 MK3, gelişmiş özelliklere sahip bir jeneratör kontrol cihazıdır. Bu kullanım kılavuzu, cihazın kurulumu, bağlantıları, fonksiyonları ve teknik özelliklerini detaylı olarak açıklamaktadır.
Preview DATAKOM DKM-0216 Alarm Anons Ünitesi - Teknik Özellikler ve Fonksiyonlar
DATAKOM DKM-0216 Alarm Anons Ünitesi hakkında detaylı bilgiler, enerji ve otomasyon sistemleri için özellikler, teknik şartnameler, kurulum yönergeleri ve operasyonel fonksiyonlar.