1. Introduction

This manual provides essential instructions for the installation, operation, maintenance, and troubleshooting of your APC Smart-UPS SRT 3000VA RM 230V (SRT3000RMXLI). This Uninterruptible Power Supply (UPS) is designed to provide high-density, true double-conversion online power protection for critical electronic equipment, including servers, voice/data networks, medical labs, and light industrial applications. Please read this manual thoroughly before installing or operating the UPS to ensure proper and safe usage.

2. Safety Information

Observe all warnings and operating instructions in this manual. Failure to do so may result in injury or equipment damage. This UPS contains hazardous voltages. Do not attempt to disassemble the unit. There are no user-serviceable parts inside.

General Safety

  • This UPS is intended for indoor use only.
  • Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
  • Ensure the ventilation openings on the UPS are not blocked. Maintain adequate clearance around the unit for proper airflow.
  • Connect the UPS power cable directly to a grounded wall outlet. Do not use extension cords or surge suppressors.

Battery Safety

  • Batteries are heavy. Remove the battery module before installing the UPS in a rack or tower configuration.
  • Battery service should be performed or supervised by personnel knowledgeable of batteries and the required precautions.
  • Do not dispose of batteries in a fire. The batteries may explode.
  • Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
  • Replace batteries with the same type and number of batteries as originally installed.

3. Package Contents

Carefully unpack the unit and inspect for shipping damage. If any damage is found, notify the carrier and dealer. The package should contain the following items:

  • APC Smart-UPS SRT 3000VA RM 230V (SRT3000RMXLI) unit
  • Battery module (may be pre-installed or separate)
  • Rack-mounting hardware (rails, brackets)
  • Tower stand (for tower configuration)
  • USB communication cable
  • Serial communication cable
  • Documentation CD
  • Safety information and warranty guide

4. Product Overview

The APC Smart-UPS SRT 3000VA RM 230V is a high-performance Uninterruptible Power Supply designed to protect your critical equipment from power disturbances. It features a rack/tower convertible form factor for flexible deployment.

APC Smart-UPS SRT 3000VA RM 230V front view

Figure 1: Front view of the APC Smart-UPS SRT 3000VA RM 230V. This image displays the front panel with the LCD display, control buttons, and ventilation grilles.

Key Components

  • Front Panel LCD Display: Provides real-time status information, configuration options, and alarm notifications.
  • Control Buttons: Used to navigate the LCD menu, power on/off the UPS, and perform self-tests.
  • Battery Module: Provides backup power during outages. Hot-swappable for easy replacement.
  • Input Power Connector: Connects the UPS to the utility power source.
  • Output Receptacles (IEC 320): Provide protected power to connected equipment.
  • Communication Ports (USB, Serial): For connecting to a computer or network management card for monitoring and control.
  • EPO (Emergency Power Off) Port: Allows for remote emergency shutdown of the UPS.

5. Setup

Follow these steps for initial setup of your UPS.

Step 1: Choose a Location

  • Place the UPS on a sturdy, level surface or install it in a standard 19-inch rack.
  • Ensure the ambient temperature is between 0°C and 40°C (32°F and 104°F).
  • Maintain at least 10 cm (4 inches) of clearance at the front and rear of the unit for proper ventilation.

Step 2: Install the Battery Module

If the battery module is not pre-installed, slide it into the battery bay until it clicks into place. Connect the battery cables as indicated by the labels.

Step 3: Connect to Utility Power

  • Connect the UPS input power cord to a grounded 230V AC outlet.
  • The UPS will perform a self-test and the LCD display will illuminate.

Step 4: Connect Equipment

  • Connect your critical equipment (servers, network devices, etc.) to the output receptacles on the rear of the UPS.
  • Ensure the total load does not exceed the UPS capacity (3000VA / 2700W).

Step 5: Connect Communication Cables (Optional)

  • Connect the USB or serial cable from the UPS to your computer or server for monitoring and graceful shutdown capabilities.
  • Install the PowerChute software (available from APC website) on your computer for advanced management.

6. Operating the UPS

Powering On the UPS

Press and hold the power button on the front panel until you hear a beep. The UPS will start up and provide power to connected equipment.

Powering Off the UPS

Press and hold the power button until the UPS shuts down. Ensure all connected equipment is safely shut down before powering off the UPS.

LCD Display and Navigation

The LCD display provides detailed information about the UPS status, battery charge, load level, and various settings. Use the navigation buttons (up, down, enter, escape) to browse through the menus and adjust settings.

Self-Test

Regularly perform a self-test to ensure the UPS battery and internal components are functioning correctly. This can typically be initiated via the LCD menu or PowerChute software.

7. Maintenance

Battery Replacement

The UPS batteries have a typical lifespan of 3-5 years. The UPS will indicate when the batteries need replacement. Refer to the safety information before attempting battery replacement. Use only APC-approved replacement battery modules (APCRBC152).

Cleaning

Clean the exterior of the UPS with a soft, damp cloth. Do not use solvents or abrasive cleaners. Ensure ventilation openings are free from dust and debris.

Environmental Considerations

Store the UPS in a cool, dry place when not in use. Avoid extreme temperatures and humidity, which can shorten battery life.

8. Troubleshooting

This section provides solutions to common issues you may encounter with your UPS.

ProblemPossible CauseSolution
UPS does not turn onNo utility power; Battery not connected; UPS faultCheck power outlet; Ensure battery cables are connected; Contact APC support if fault persists.
UPS beeps continuouslyOn battery power; Overload; Low batteryCheck utility power; Reduce connected load; Allow battery to recharge.
Battery not chargingBattery disconnected; Battery fault; Internal faultVerify battery connection; Replace battery if faulty; Contact APC support.
Connected equipment loses powerUPS overload; Battery depleted; UPS faultReduce load; Allow battery to recharge; Contact APC support.

9. Specifications

Detailed technical specifications for the APC Smart-UPS SRT 3000VA RM 230V (SRT3000RMXLI).

FeatureDetail
Model NumberSRT3000RMXLI
BrandAPC
Capacity3000 VA / 2700 Watts
Input Voltage230 Volts
Output Voltage230 Volts
Form FactorRack/Tower Convertible (2U)
Battery TypeLead Acid
Typical Runtime (Full Load)Approximately 4 minutes
Number of Outlets8 x IEC 320 C13, 2 x IEC 320 C19
Communication PortsUSB, Serial (RJ45), SmartSlot
Dimensions (H x W x D)8.5 cm x 43.2 cm x 63.5 cm (3.35 in x 17.0 in x 25.0 in)
Weight31.3 kg (69 lbs)
ColorBlack

10. Warranty and Support

Warranty Information

APC provides a standard warranty for this product. Please refer to the warranty card included in your package or visit the official APC website for detailed warranty terms and conditions specific to your region. Keep your proof of purchase for warranty claims.

Technical Support

For technical assistance, troubleshooting beyond this manual, or to inquire about replacement parts, please contact APC customer support. Support contact information can typically be found on the APC website or in the documentation provided with your unit. When contacting support, please have your model number (SRT3000RMXLI) and serial number ready.

© 2024 APC. All rights reserved. Information in this document is subject to change without notice.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.