Product Overview

The Febco Series 850U Double Check Valve Assembly is engineered to safeguard drinking water supplies from hazardous cross-connections. This valve is suitable for non-potable service applications such as irrigation, fireline, or industrial processing, adhering to national Plumbing Codes and water authority requirements.

Key features include:

  • Maximum working pressure: 175 Psi (12.1 bar)
  • Hydrostatic test pressure: 350 Psi
  • Temperature range: 32-140 degrees Fahrenheit
  • Valve body material: Bronze
  • Elastomers: Silicone
  • Springs: Stainless Steel
  • End connections: NPT ANSI/ASME B1.20.3
Febco 850U-QT Double Check Backflow Valve

Image: Febco 850U-QT Double Check Backflow Valve. This image displays the bronze valve assembly with union connections and quarter-turn shutoff handles. It shows the main body of the valve with two check valves and four test cocks, flanked by two quarter-turn ball valves with blue handles.

Safety Information

Always follow local plumbing codes and regulations during installation and maintenance. Ensure proper personal protective equipment (PPE) is used. Depressurize the system before any service or repair. Do not exceed the maximum working pressure of 175 Psi.

Setup and Installation

Installation should be performed by a qualified professional in accordance with all applicable local and national plumbing codes.

  1. Pre-Installation Check: Inspect the valve for any signs of damage during shipping. Ensure all components are present.
  2. System Preparation: Flush the upstream piping thoroughly to remove any debris that could damage the valve.
  3. Orientation: Install the valve in the correct flow direction as indicated by the arrow on the valve body. The valve must be installed horizontally.
  4. Connections: Use appropriate pipe thread sealant on NPT connections. Tighten connections securely but do not overtighten.
  5. Support: Provide adequate support for the valve and associated piping to prevent strain on the connections.
  6. Testing: After installation, slowly pressurize the system and check for leaks. Perform a backflow prevention device test as required by local codes.

Operating Instructions

The Febco 850U-QT features quarter-turn shutoff valves for easy operation.

  • Opening the Valve: Turn the blue handles of the quarter-turn shutoff valves so they are parallel with the pipe. This allows water to flow through the assembly.
  • Closing the Valve: Turn the blue handles of the quarter-turn shutoff valves so they are perpendicular to the pipe. This stops water flow through the assembly.
  • Test Cocks: The four test cocks (small brass fittings with screws) are used by certified testers to verify the proper operation of the check valves. Do not tamper with these unless performing a test.

Maintenance

Regular maintenance and testing are crucial for the proper functioning and longevity of the backflow preventer.

  • Annual Testing: This device must be tested annually by a certified backflow prevention device tester to ensure it is functioning correctly and providing the required protection.
  • Winterization: In climates where freezing temperatures occur, the valve must be drained or protected from freezing to prevent damage. Consult local codes for specific winterization procedures.
  • Inspection: Periodically inspect the valve for any visible signs of leaks, corrosion, or damage.
  • Repair: Repairs should only be performed by qualified personnel using genuine Febco replacement parts.

Troubleshooting

ProblemPossible CauseSolution
Water leaking from test cocksDebris in check valve, worn O-rings, or faulty check valve.Flush the system. If problem persists, have a certified technician inspect and repair/replace internal components.
Reduced flow downstreamPartially closed shutoff valves, debris in the valve, or a faulty check valve.Ensure shutoff valves are fully open. Flush the system. If problem persists, professional inspection is required.
Visible external leaksLoose connections, damaged valve body, or worn seals.Check and tighten connections. If valve body is damaged, replacement is necessary. For worn seals, professional repair is recommended.

Specifications

AttributeValue
Model Number2613
Series850U-QT
Size1 Inch
MaterialBronze
Max Working Pressure175 Psi (12.1 bar)
Hydrostatic Test Pressure350 Psi
Temperature Range32-140 degrees Fahrenheit
ElastomersSilicone
SpringsStainless Steel
Inlet Connection TypeNational Pipe Tapered (NPT)
Outlet Connection TypeMNPT
Product Dimensions (L x W x H)3 x 5 x 12.5 inches
Item Weight8.85 pounds
UPC643925017465

Warranty Information

Febco products are manufactured to high standards. For specific warranty details, please refer to the official Febco warranty statement provided with your product or visit the official Febco website. Typically, warranties cover defects in materials and workmanship under normal use and service.

Customer Support

For technical assistance, replacement parts, or further information, please contact Febco customer support. You can find contact details on the official Febco website or through your authorized distributor.

Febco Official Website: www.febcoonline.com

© 2024 Febco. All rights reserved. This manual is for informational purposes only.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.