1. Introduction

This user manual provides essential information for the safe and effective installation, operation, and maintenance of the ABB Type CLE Current Transformer, Model 7524A63G05. This device is designed for accurate current measurement in industrial electrical systems. Please read this manual thoroughly before attempting any procedures to ensure proper handling and to prevent potential hazards.

2. Product Overview

The ABB Type CLE Current Transformer (CT) is a critical component for monitoring and protecting electrical circuits. It safely steps down high primary currents to a measurable level for instruments, meters, and relays. The Model 7524A63G05 features a robust design suitable for demanding industrial environments.

ABB Type CLE Current Transformer, front-side view

Figure 2.1: An overall view of the ABB Type CLE Current Transformer. This image displays the robust, dark-colored casing and the transparent terminal cover on top, indicating the primary and secondary connections. The toroidal shape allows for easy integration around a primary conductor.

ABB Type CLE Current Transformer, angled view

Figure 2.2: Another angled view of the ABB Type CLE Current Transformer, highlighting its compact design and the mounting points on the base. The nameplate is visible on the side, providing key operational specifications.

Close-up of ABB Type CLE Current Transformer terminal block and nameplate

Figure 2.3: A detailed close-up of the terminal block and the product nameplate. The transparent cover protects the secondary terminals (X1, X2) and shows the connection points. The nameplate clearly displays the model number, current ratio, and other electrical specifications.

Detailed view of ABB Type CLE Current Transformer nameplate

Figure 2.4: An extreme close-up of the ABB Type CLE Current Transformer's nameplate. This view allows for clear reading of critical data such as "TYPE CLE", "CURRENT TX.", "S# 7524A63G05", "RATIO 6000:5 AMPS", "60 HZ", "NSV 0.6 KV", "BIL 10 KV", and "ANSI ACC. CL. METERING 0.3 B0.1 THRU B1.8". It also indicates "Made in U.S.A." and the manufacturer "ABB Power T&D Company Inc."

3. Safety Information

WARNING: Electrical shock hazard. Installation and maintenance should only be performed by qualified personnel.

  • Always de-energize the primary circuit before installing or servicing the current transformer.
  • Never open the secondary circuit of an energized current transformer. This can lead to dangerously high voltages and potential injury or equipment damage.
  • Ensure all connections are secure and properly insulated.
  • Verify the correct polarity before connecting the CT to metering or protection devices.
  • Wear appropriate personal protective equipment (PPE) when working with electrical systems.

4. Setup and Installation

Installation of the ABB Type CLE Current Transformer requires adherence to local electrical codes and safety standards. It is recommended that a certified electrician or qualified technician perform the installation.

  1. De-energize Circuit: Ensure the primary circuit where the CT will be installed is completely de-energized and locked out according to safety protocols.
  2. Mounting: Securely mount the CT using appropriate hardware. The CT is designed to encircle the primary conductor.
  3. Primary Conductor: Pass the primary conductor through the center opening of the current transformer.
  4. Secondary Connections: Connect the secondary terminals (X1 and X2) to the metering or protection device. Observe correct polarity as indicated on the nameplate (H1-H2 for primary, X1-X2 for secondary). X1 typically corresponds to H1, and X2 to H2.
  5. Grounding: Ensure the secondary circuit of the CT is properly grounded at one point, typically at the X2 terminal, to prevent high voltage buildup.
  6. Verify Connections: Double-check all wiring for correctness and tightness.
  7. Re-energize: Once installation is complete and verified, the primary circuit can be safely re-energized.

5. Operating Instructions

The ABB Type CLE Current Transformer operates passively by inducing a proportional current in its secondary winding based on the primary current flowing through its core. Once installed, it requires no active user intervention for its primary function.

  • Monitoring: The output of the CT (typically 5 Amps at rated primary current) is fed into a connected meter, relay, or other monitoring device. Refer to the instruction manual of the connected device for its operation.
  • Load (Burden): Ensure the connected load (burden) on the secondary circuit does not exceed the CT's rated burden (e.g., B0.1 through B1.8 as indicated on the nameplate). Exceeding the burden can lead to inaccurate readings and potential damage.
  • Polarity: Correct polarity is crucial for accurate directional measurements and proper operation of protective relays.

6. Maintenance

The ABB Type CLE Current Transformer is designed for long-term, reliable operation with minimal maintenance. However, periodic inspections are recommended to ensure optimal performance and safety.

  • Visual Inspection: Periodically inspect the CT for any signs of physical damage, discoloration, or loose connections.
  • Cleaning: If necessary, gently clean the exterior of the CT with a dry, lint-free cloth. Do not use abrasive cleaners or solvents. Ensure the power is off before cleaning.
  • Terminal Check: Verify that all secondary terminal connections remain tight and free from corrosion. This should only be done with the primary circuit de-energized and the secondary circuit shorted or connected to a safe load.
  • Environmental Conditions: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent premature degradation.

7. Troubleshooting

Most issues related to current transformers stem from improper installation or external circuit problems. Always prioritize safety when troubleshooting.

ProblemPossible CauseSolution
No output from CT / Incorrect readings
  • Open secondary circuit
  • Incorrect wiring/polarity
  • Primary circuit de-energized
  • Faulty connected meter/device
  • CT burden exceeded
  • De-energize primary circuit. Check secondary connections for continuity and ensure they are properly terminated.
  • Verify wiring against schematic and nameplate.
  • Confirm primary circuit is energized and current is flowing.
  • Test connected device independently.
  • Reduce secondary load or replace CT with appropriate burden rating.
Overheating of CT
  • Overcurrent in primary circuit
  • Excessive secondary burden
  • Short circuit in secondary winding
  • Check primary circuit load.
  • Reduce secondary load.
  • De-energize primary circuit. Inspect secondary wiring for shorts.

If troubleshooting steps do not resolve the issue, contact ABB technical support or a qualified service professional.

8. Specifications

The following specifications apply to the ABB Type CLE Current Transformer, Model 7524A63G05:

  • Model Number: 7524A63G05
  • Brand: ABB (Asea Brown Boveri / ABB Power T&D Company Inc.)
  • Type: CLE Current Transformer
  • Current Ratio: 6000:5 Amps
  • Frequency: 60 Hz
  • Nominal System Voltage (NSV): 0.6 kV
  • Basic Impulse Level (BIL): 10 kV
  • ANSI Accuracy Class: Metering 0.3 B0.1 THRU B1.8
  • Outside Dimensions: Approximately 12" x 13" x 3" (30.5 cm x 33 cm x 7.6 cm)
  • Inside Dimensions (Window): Approximately 8" x 8" x 3" (20.3 cm x 20.3 cm x 7.6 cm)
  • Manufacturer Part Number: 236P750H07
  • UPC: 782451081325

9. Warranty and Support

For information regarding warranty coverage, technical support, or service for your ABB Type CLE Current Transformer, Model 7524A63G05, please contact ABB directly through their official website or customer service channels. Ensure you have your model number and any purchase details available when contacting support.

You can visit the official ABB website for more information: www.abb.com

Related Documents - 7524A63G05

Preview ABB RET650 Transformer Protection Relay - Product Guide
Explore the ABB RET650, a versatile transformer protection relay offering advanced differential, impedance, current, voltage, and frequency protection for power systems. This product guide details its features, applications, and technical specifications for reliable substation automation.
Preview ABB FH200A System pro M compact Residual Current Circuit Breaker: Installation and Technical Data
Comprehensive guide to the ABB FH200A System pro M compact residual current circuit breaker, covering technical specifications, installation procedures, electrical connections, and safety instructions.
Preview ABB PSE Softstarters: Features, Specifications, and Benefits for Industrial Motor Control
Explore the ABB PSE Softstarters, a series of compact digital soft starters offering advanced motor control, protection, and automation integration. This document details their technical specifications, key features like integrated motor protection and torque control, and real-world application benefits for various industries.
Preview ABB B21/B23/B24 Installation Manual
This installation manual from ABB provides detailed instructions for the B21, B23, and B24 series energy meters. It covers essential aspects such as mounting procedures, electrical connections for different models, basic settings configuration, and comprehensive technical specifications.
Preview ABB VM1 Vacuum Circuit Breaker Instruction Manual
Comprehensive instruction manual for the ABB VM1 vacuum circuit breaker, detailing its structure, function, installation, operation, maintenance, and technical specifications for medium voltage electrical systems.
Preview ABB Electrical Connector Accessories & Hardware Guide
Comprehensive guide to ABB's COLOR-KEYED COMPRESSION CONNECTOR SYSTEMS accessories, featuring Kopr-Shield compounds, Belleville and Dragon Tooth washers, hex bolts, nuts, sealants, lubricants, duct seal, and wire brushes for electrical connections.