1. Introduction
This manual provides essential information for the safe and effective installation, operation, and maintenance of the ABB OT600U03 Disconnect Switch. This device is designed for industrial applications, providing a reliable means to isolate electrical circuits. Please read this manual thoroughly before any installation or operation to ensure proper handling and to prevent potential hazards.
2. Safety Information
WARNING: Electrical equipment can be dangerous. Installation, operation, and maintenance should only be performed by qualified and authorized personnel. Failure to follow these instructions can result in serious injury, death, or equipment damage.
- Always disconnect power before working on the switch or connected circuits.
- Use appropriate personal protective equipment (PPE), including insulated gloves, eye protection, and arc-flash protection.
- Ensure proper grounding and bonding of the equipment.
- Verify voltage and current ratings match the application requirements.
- Do not operate the switch if it appears damaged or if there are any signs of electrical arcing or overheating.
- Adhere to all local and national electrical codes and regulations.
3. Product Description and Features
The ABB OT600U03 is a robust, manually operated disconnect switch designed for high-current industrial applications. It features a 3-pole configuration, capable of handling up to 600 Amps at 600 VAC. Its sturdy construction ensures reliable performance in demanding environments.

Figure 3.1: Front-angled view of the ABB OT600U03 Disconnect Switch, showing the robust construction and the operating handle in an intermediate position.

Figure 3.2: Side view of the disconnect switch with the operating handle in the upright, likely "ON" or "OFF" position, indicating its manual operation mechanism.

Figure 3.3: Top-down view of the switch, highlighting the three main poles and the connection terminals, along with the handle mechanism.

Figure 3.4: Angled view of the switch with the handle in the down position, likely indicating the opposite state (e.g., "OFF" if Figure 3.2 is "ON").

Figure 3.5: Rear view of the disconnect switch, displaying various product labels and certifications, including voltage and current ratings.

Figure 3.6: Detailed close-up of the product label, showing specifications such as voltage, current, short circuit ratings, and manufacturer information.
Key Features:
- Manual Operation: Designed for direct manual control of power flow.
- High Current Capacity: Rated for 600 Amps, suitable for heavy-duty industrial applications.
- High Voltage Rating: Operates safely at up to 600 Volts AC.
- 3-Pole Configuration: Provides disconnection for three phases of an electrical circuit.
- Robust Construction: Built for durability and long-term reliability in industrial environments.
- IP54 International Protection Rating: Offers protection against dust ingress and splashing water from any direction.
4. Installation and Setup
Installation of the ABB OT600U03 Disconnect Switch must be performed by a certified electrician or qualified personnel in accordance with all applicable electrical codes and safety standards.
Installation Steps:
- Power Disconnection: Ensure all power to the circuit where the switch will be installed is completely disconnected and locked out/tagged out. Verify with a voltage tester.
- Mounting: Securely mount the disconnect switch to a stable surface or enclosure using appropriate hardware. The product dimensions are approximately 15 x 15 x 18 inches.
- Wiring: Connect the incoming and outgoing power cables to the designated terminals. Ensure correct phase sequence and secure all connections. The switch is designed for 3-way circuits. Refer to the product label for terminal torque specifications (e.g., 500 lb-in). Use Cu-Al conductors rated for 75°C wire only.
- Grounding: Connect the equipment grounding conductor to the designated ground terminal on the switch or enclosure.
- Enclosure (if applicable): If installing within an enclosure, ensure it provides adequate protection and ventilation.
- Pre-Operation Check: Before restoring power, visually inspect all connections for tightness and proper insulation. Confirm no tools or debris are left inside the enclosure.
5. Operation
The ABB OT600U03 Disconnect Switch is operated manually using the integrated handle. It has two primary positions: ON and OFF, providing a clear visual indication of the circuit status.
Operating Procedure:
- To Turn ON (Connect Power): Firmly move the operating handle to the "ON" position. This position typically locks the handle in place, indicating the circuit is closed and power is flowing.
- To Turn OFF (Disconnect Power): Firmly move the operating handle to the "OFF" position. This position isolates the circuit, preventing power flow. The handle may have a provision for padlocking in the "OFF" position for lockout/tagout procedures.
Always ensure the handle is fully engaged in either the ON or OFF position to prevent partial contact and potential arcing.
6. Maintenance
Regular maintenance helps ensure the longevity and safe operation of the disconnect switch. All maintenance should be performed by qualified personnel with power disconnected and locked out.
Maintenance Schedule and Tasks:
- Annual Inspection:
- Visually inspect the switch for any signs of physical damage, corrosion, or discoloration due to overheating.
- Check all electrical connections for tightness. Loose connections can cause overheating and arcing.
- Inspect the operating mechanism for smooth movement and proper engagement. Lubricate if necessary with a non-conductive lubricant suitable for electrical components.
- Clean any dust or debris from the switch and its enclosure using a dry, non-conductive cloth or vacuum.
- Contact Resistance Check (Every 3-5 years or as needed):
- Measure the contact resistance across each pole to ensure low resistance and efficient power transfer. High resistance can indicate worn contacts.
- Replacement: If significant wear, damage, or consistent operational issues are observed, the switch should be replaced by a qualified professional.
7. Troubleshooting
This section provides guidance for common issues. For complex problems, contact a qualified electrician or ABB technical support.
| Problem | Possible Cause | Solution |
|---|---|---|
| Switch does not operate smoothly. | Accumulation of dust/debris; lack of lubrication; mechanical damage. | Clean the mechanism. Apply appropriate lubricant. Inspect for damage and replace if necessary. |
| No power to load after switching ON. | Upstream power issue; loose connections; internal switch failure. | Check upstream circuit breakers/fuses. Verify all connections are tight. If issue persists, switch may need replacement. |
| Overheating of switch terminals. | Loose connections; overloaded circuit; undersized wiring. | Disconnect power and tighten all terminal connections. Verify circuit load is within switch ratings. Ensure correct wire gauge is used. |
| Visible arcing during operation. | Worn contacts; improper load breaking; faulty switch. | This indicates a serious issue. Immediately disconnect power upstream. The switch likely requires replacement. Do not operate. |
8. Specifications
| Attribute | Detail |
|---|---|
| Brand | ABB |
| Model | OT600U03 |
| Operation Mode | Manual |
| Current Rating | 600 Amps |
| Operating Voltage | 600 Volts AC |
| Circuit Type | 3-way (3 Poles) |
| Contact Type | Normally Open |
| Actuator Type | Hinge Lever |
| International Protection Rating | IP54 |
| Product Dimensions (L x W x H) | 15 x 15 x 18 inches |
| Weight | 13 Pounds |
| Manufacturer | ABB Group |
| Date First Available | March 29, 2016 |
9. Warranty and Support
Specific warranty details for the ABB OT600U03 Disconnect Switch are not provided in this manual. For warranty information, technical support, or service inquiries, please contact ABB Group directly or refer to their official website.
Manufacturer: ABB Group
Website: www.abb.com/lowvoltage (as indicated on product label)
Always provide the model number (OT600U03) and any relevant serial numbers when contacting support.